| 1 | Excavation in trenches in soft/loose soil not exceeding1.5 meter wide and not exceeding 1.5 meter deep for laying of cable, pole foundation, etc including taking out old brick cable protection cover and getting out forming bottom surface to required gradient complete all as specified and directed. |
| 2 | Excavation in trenchesexc 1.5m wide and exc 1.5m deep for foundation of poles/stays/cable etc and getting out in soft /loose soil complete all as specified and directed by Engr-in-Charge. |
| 3 | Returning, filling in, earth including spreading, leveling watering and well ramming in layers each not exceeding 25 cm thick each layer complete all as specified and directed. |
| 4 | Removal of surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point complete all as specified and directed. |
| 5 | Material and labour for sand cushioning with fine sand for cable protection laid in trenches 8 cm before laying of cable and 15 cm after laying and stretching the cable complete all as specified and directed.Note:- Punned down thickness as laid down in SSR Part I shall be measured and paid. |
| 6 | Material and labour brick protection layer for cables laid in trenches using sub-class ‘B’ bricks laid dry width wise acrose the line of cable (perpendicular to the direction of cable) complete all as specified and directed. |
| 7 | Dismantling & taking out old damaged PCC/Steel pole of any sizeandremoving from site of work complete all as specified and directed. |
| 8 | Taking down old faultiLT UG Cable of size 10/ 16 Sqmm 4 core, complete all as specified and directed. |
| 9 | Taking down old faultiLT UG Cable of size 25/ 35 Sqmm 3.5 core, complete all as specified and directed. |
| 10 | Supply, laying and testing LT cable XLPE Insulated, armoured, heavy duty electric cable with aluminium conductor 1100 Volts grade cross sectional area 35 sq mm 3.5 core complete all as specified and directed. |
| 11 | Supply, laying and testing LT cable XLPE Insulated ,armoured, heavy duty electric cable with aluminium conductor 1100 Volts grade cross sectional area 25 sq mm 3.5 core complete all as specified and directed. |
| 12 | Supply, laying and testing LT cable XLPE Insulated ,armoured, heavy duty electric cable with aluminium conductor 1100 Volts grade cross sectional area 16 sq mm 4 core complete all as specified and directed. |
| 13 | Supply, laying and testing LT cable XLPE Insulated ,armoured, heavy duty electric cable with aluminium conductor 1100 Volts grade cross sectional area 10 sq mm 4 core complete all as specified and directed. |
| 14 | Supply and fixing LED street light fitting 90 Watt 230 V AC, Warm White with 100 LPW and 3000k CCT, outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection. Input voltage-220 V to 240 V AC,50 Hz,Operating voltage-140 V to 270 V,50 Hz. Impact Protection -IK 07/IK 08. Average life L 70 B 50 -50000 hours (minimum).Lumen Efficacy of minimum 100 Im/Watt. Open/Short circuit protection, Phase to Pahse protection (Operating at 440 V). Over voltage protection,Surge voltage protection upto 10 KV & other safety tests as per IS 15885 Part2/Sec 13 complete all as specified and as directed.Make : Crompton, Havells or Philips.Note:-1. Stensil cut on each street light with CA No. will be arranged by Contractor.2. Removing of existing street light and cable, if any, is included.3. During defect liability period the street light fitting shall be made functional within 7 days of intimation, otherwise the cost of such street light fitting/fittings will be recovered |
| 15 | Suplying and fixing in repair 1100 volts grade heavy duty 4 Sq mm two core cable PVC insulated aluminium Stranded conductor, served with inner shething of PVC sheathed in service conections one twin core cable flat or circular complete all as specified and as directed by Engineer-in-Charge. |
| 16 | Supply and fixing GI pipe bracket for street light fittings made out of 40 mm dia GI pipe medium grade 1.2 mtr long bent to required angle/shape with and2xpair of MS clamps made out40mmx5mm MS flat iron bolts, nuts complete including two coat of synthetic enamel paint (first grade) over a coat of red oxide complete all as specified and as directed by Engineer-in-Charge. |
| 17 | Supply & fixing of flood light fitting on High mast pole 16/20 mtr height ofpressure die cast aluminum LED of 150 Watt as light source and electronicdriver , made up of pressure die cast housing withtoughned glass and secondary lenses with IP66 protection. System efficacy >110/120 LPW, 10kV SPD Aesthetically designed roadway luminiare with excellent thermal management . Make- Crompton/ Phillips / Havells.Note:-1. Stensil cut on each street light with CA No. will be arranged by Contractor.2. Removing of existing flood light and cable on High mast pole 16/20Mtr height, if any, is included.3. During defect liability period the street light fitting shall be made functional within 7 days of intimation, otherwise the cost of such street light fitting/fittings will be recovered. |
| 18 | Supply and fixingautomatic street light switch outdoor type double door2 mm thick CRCA sheet factory made cubical type power coated, dust and vermin proof panel suitable size for 415 volts , AC 3 phase, 4 wire, 50 HZ of size (600(H) x 600 (W) x 350 (D) with Chemical Treatment with 9 Tank pre Treatment Process Method for Degreasing, Derusting and Phosphating Powder Coating Siemens grey. wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm , thimbles including cable entry glands, all as directed. Base frame of the panel shall be made of angle iron of size 50 x 50 x 6 mm embedded in PCC (1:3:6) type C-2 using 40 mm stone aggregate of upto 1/2 mtr height below GL & 1/2 mtr for above GL. Contd...18.01/- |
| 19 | (i) Panel having common aluminium bus bar of capacity 120 Amp TPN each and suitable capacity.(ii) Incomming :-(a) MCCB Adjustable type thermal released based capacity, 63 Amp 4 Pole ICU = ICS = 25 KA - 01 No .(Incoming)(iii) Outgoing:-(a)MCCB Adjustable type of capacity, 40 Amp 3 Pole ICU = ICS = 10 KA - 01 No (b)Power contactor MNX 40 Amps Cat part No- CS94190 of L&T - 01 No(c)Timer Switchdigital type Astro pro Cat part No- AS2DCDS of L&T - 01 No(iv) Auto/Manual Selector switch with indicator lamp - 01 Set. |
| 20 | Earthing complete with galvanized mild steel earth plate electrode size 600 mm x 600 mm x 6.3 mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 50 mm bore medium grade galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50 mm bore light grade galvanized iron protection pipe for earth strip 32 x 6 mmupto 7.5 m length, charcoal, common salt, complete all as shown in EP No 1 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion, complete all as specified and directed.Note : GI earth strip 32 x 6 mm more than 7.5 mtr if required will be measured and paid separately. |
| 21 | Material and labour for galvanised iron pipe light grade (ISI marked) 40 mm bore for passing of cables etc. laid in trenches, under floors, roads or fixed to walls including all fittings as required and MS clamps nuts & bolts etc complete all as specified and directed. |
| 22 | Material and labour for galvanised iron pipe light grade (ISI marked) 50 mm bore for passing of cables etc. laid in trenches, under floors, roads or fixed to walls including all fittings as required and MS clamps nuts & bolts etc complete all as specified and directed. |
| 23 | Material & labour for boring holes under pucca metalled road suitable for laying 100/80 mm bore pipe for crossing cable not less than one metre below ground level,including getting out,disposal rubbish off to a distance upto 50 meter after making good road with same material to match with existing surface complete all as specified and as directed |
| 24 | Supply and fixingLTPre-stressed concrete pole 9.0 metres long of cross section 102 mm x 172 mm at top and 102 mm x 279 mm at bottom class 10 complying with requirementof IS 1678-1978 incl painting of poles with two coats of synthetic enamel paint/over a coat of primer in black and white strips upto 1.5 mtrheight from top of PCC as directed(PCC and earth work shall be measured and paid separately).complete all as specified and directed |
| 25 | Supply, Installation and Fixing LT Cable junction box shall be made out of Thermoplastic Polycarbonate and size should be not less than 200mm x 160mm x 98 mm(upto Cable Size 16/25sq.mm). The Polycarbonate JB shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive,IP 65 in accordance with IEC 60529,Weatherproof UV-resistant, rainwater-proof, temperature-resistant. The gasket material of JB shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22& IEC 60670 - 2 - 5. The JB Colour according to RAL 7035. The Junction Box shall be with four side screw and they will be sealable without any accessories. The manufacturer of Junction Box / Enclosure shall be submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3,UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade & Terminal Stud with Current Carrying Capacity upto 63Amps. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector including MCB SP, 6 Amp and Chromium plated clamps, suitable Cable Gromets and nut bolts and complete all accessories.Note:- Manufacturer should submit routine test certificate of CJB/PJB |
| 26 | Supply & fixing 1.5 sqmm, 3 core PVC insulated and FR PVC round sheathed copper conductor flexible cable, 1100 volts grade for connection from Junction Box to street light fittings complete all as specified and directed. |
| 27 | Supply and Laying concealed Rigid non-metallic, ISI marked, PVC conduit 20mm dia exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed. |
| 28 | M&L for cement concreted (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation of polesfilling and mass concreting, complete all as specified and directed. |
| 29 | M&L for cement concreted (1:3:6) type C-2 using 40 mm graded crushed stone aggregatein foundation of pole/ stay assembly/feeder pillar box/LT panel,etc, incl necessary form work and fair finsh to exposed surfaces without using extra cement etc, complete all as specified and directed. |
| 30 | M&L Cement concreted (1:2:4) type B-1 using 20 mm graded stone aggregate as in foundation of electric poles/struts/ etc including necessary form work, fair finished surfaces without using extra cement, complete all as specified and directed. |