| 1 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm (L) ×450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1400 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts16 mm dia,600 mm long, J type i/c 2 nos. template anchor plates of size 225mm×225mm×3mm and providing DCW HDPE for cable entry and exit as required for 3 m and 5 mtr pole. |
| 2 | Fabrication, supply & erection of 5.0 mtr height, minimum 3 mm thick, bottom dia of 130 mm & top dia of 70mm, base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate heightfrom the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor - 4 nos. & shorting links on DIN channel i/c providing and fixing DIN channel of suitable length, 6 Amp. SPMCB \"C\" characteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be either embossed or Rivited plate on the pole. Galvanization as per relevant IS code etc as required. |
| 3 | Fabrication,Supplying,Installation,testing,Commissioning of 12 mtr high mast System with its accessories ,Mast shaft shall be in one section , hot dip galvanized 4mm thick(Single dip ) inside & out sides &suitable for wind velocity as per IS 875 part3 .There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For High Mast head frame ,2 point suspension system, 5*2.5 sqmm Cu conductor with steel wire rope 5mm dia. (7/19construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminariessymmetrically And its control gears boxes and lighting finial ,the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panelhousing suitable RCC (1:2:4) shallowfoundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia - 3700 mm (approx.) - 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the high mast considering The safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4Nos S.P MCB,63Amp.DPIsolator etc as reqd. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS. |
| 4 | Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 40 mm dia galvanised pipe with tightening bolts complete as required. |
| 5 | Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 40 mm dia galvanised pipes with tightening bolts complete as required. |
| 6 | Supply of arms of GI pipe of size 20mm/25mm dia B class 700 MM long bent medium grade with 25 mm width 5mm thick MS clamps set 2 no.s with 3/8 nut and bolts for fixing of GI pipe in various sizes suitable to existing RCC/ MS poles per relevant standard specifications. |
| 7 | Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80 , under voltage and over voltage protection,EMI EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) 135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 50 Watt |
| 8 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg 120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) 135 lm/Wattoutput . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C). 100 Watt |
| 9 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm |
| 10 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm |
| 11 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*4 sqmm |
| 12 | Providing and laying of HDPE PIPE OF 40mm outer dia with PN 4 rating by hand Moling/Mannual method Confirming to IS 4984 592 |
| 13 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. asreqd. |
| 14 | Supply and fabrication of pole protection system made up 8 SWG steel wire mesh of size 25 mm x 75 mm rectangular with 50 mm x 50 mmx6mm MS angle iron for supporting the mesh i/c MV Danger Plate anf grounding the protection system in suitable quality of CC etc |
| 15 | Providing and fiving name board made of MS Sheet 90x60cm, 1mm thick with frame of MS angle 50x50x6mm, two diagonal braces at the back of the sheet of MS flat 40x6mm, total height of the board above ground level 2.40m, length of legs below ground 0.30m embedded in CC block 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) 30x30x45cm including excavation and removal of surplus earth with in 50m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in-Charge |
| 16 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size) |
| 17 | Providing and fixing of Stainless steel name plate of size 6×8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required |
| 18 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) includingexcavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 19 | Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size in the existingmasonry open duct as required. upto 35 sqmm |
| 20 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq.mm |
| 21 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 22 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 23 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 meter length along the pole for protection of under ground cable as required. |
| 24 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 25 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, andlift upto 1.5 metres, including getting out the excavated soil and disposal of excavatedsoil as directed within a lead of 50 metres. |
| 26 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |