| 1 | Maintenance of Street Lighting as per Inventory and Terms Conditions attached i/c cleaning of fittings/fixtures, keping the system healthy all the time, replacement/repairing of defective material, fixing new material, as per direction of engineer incharge providing special T& P like crane,trolly ladder etc by deploying 1 no wireman & 1 no. khallasi i/c maintaining record of complaints. etc. as required. |
| 2 | Supplying and Replacement of following defective items in the existing street light feeder pillars i/c conections testing etc. complete as requried. a) Digital Timer Switch( 24 hours Programmable) with 1 year warranty. |
| 3 | Coil for Contactor Type MNX 110/ML-6 |
| 4 | Spare Contact kit for ML4 |
| 5 | 3 Pole Power Contactor ML 6,2 NO+2NC with AC1 rating of 125 Ampere and AC3 rating 110 ampere |
| 6 | Supplying and replacement offollowing rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.a) 150 A, 16 kA,TPMCCB |
| 7 | b) 200 A, 25 kA,TPMCCB |
| 8 | Supplying and replcement of following Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching)<5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). i.)90 watt |
| 9 | 150 watt |
| 10 | 200 Watt |
| 11 | Supplying and drawing following sizes of FLRS PVC insulated copper conductor. Single core cable in the existing surface/recessed steel /PVC conduit/pole as required.a) 3 x 2.5 Sq.mm |
| 12 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 13 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 14 | Supplying of following size of XLPE insulated / PVC sheathed Aluminium Conductor armourd power cable of 1.1 KV grade i/c making, connection testing etc. as reqda) 2 Core x 16Sq.mm |
| 15 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. a) Upto 35 sq.mm |
| 16 | Laying of one no. PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/Stone Ware/Metal pipe/DWC pipe as reqd.a) Upto 35 sq.mm |
| 17 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend,couplers etc confirming to IS 14930 ,part II complete with fitting and cutting,jointing etc direct in ground(75 cm below ground level) i/c excavation & refilling the trench but excluding sand cushioning and protective covering etc complete as required.i.)90 mm dia(OD-90mm & ID-76 mm nominal) |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 19 | Supplying and making straight through joint with cast resin compound i/c ferrules and other jointing material for following size of PVC insulated and PVC sheathed/XLPE Aluminum conductor cable of 1.1 KV grade as reqd.a)2 Core x 16Sq.mm |
| 20 | Cleaning ,servicing,overhauling ,rewiring of burnt wires and repainting of existing street light feeder pillars& number painting,connection, including repairing of brick work,plastering, testing complete as required |
| 21 | Fabrication an fixing of 1mm thickness of GI sheet of size approx 350mm x 150 mm corresponding to connector box of pole including fasterner/nuts as per engineer -in-charge acomplete as required. |
| 22 | Supply and replacement of5 Amp.to 32 Amp rating 240/415 Volts,C Curve Miniature Circuit Breaker suitable for inductive load for following poles in the existing MCB DB complete with connection, testing commissionig etc. as required.a)Single Pole |
| 23 | b) Double Pole |