| 1 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 3 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 4 | Earthing with GI earth pipe 4.5 metre long ,40 mm dia including accessories,and providingmassonary encloser with cover plate having locking arrangement and watering pipe etc. with charcoal /cock and salt as required. |
| 5 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Up to 35 sqmm |
| 6 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sqmm |
| 7 | Supplying and fixing of light class GI pipe of 50 mm dia (nominal) 3 meters length along the pole for protection of under ground cable as required. |
| 8 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 9 | S/L of following size DWCHDPEPipe ISI marked along with all accessories like socket ,bend ,couplers etc.conforming to IS 14930 ,partII complete with fittingand cutting ,jointing etc .direct in ground (75 cm below ground level )including excavationand refilling the trench but excluding sand cushioning and protective covering etc, complete as required (a)63mm dia (OD-63mm ID -51mm nominal ). |
| 10 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.63 mm· dia (OD-63 mm ID-51 mm nominal) |
| 11 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 12 | Providing and fixing name board made of MS Sheet 90x60cm, 1mm thick with frame of MS angle 50x50x6mm, two diagonal braces at the back of the sheet of MS flat 40x6mm, total height of the board above ground level 2.40m, length of legs below ground 0.30m embedded in CC block 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) 30x30x45cm including excavation and removal of surplus earth with in 50m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in-Charge |
| 13 | Providing and fixing of Stainless steel name plate of size 6×8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required |
| 14 | Fabrication, Supplying, Installation, testing, Commissioning of 12 metres semi high mast System with its accessories, Mast shaft shall be in one section, hot dip galvanized 4mm thick(Single dip) Inside & out sides &sultable for wind velocity as per IS 875 part3.There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For seml High Mast head frame,2 point suspension system,5 X 2.5 sqmm Copper conductor with steel wire rope 5mm dia. (7/19 construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminaries symmetrically and its control gears boxes and lighting finial,the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) 16 nos.and reinforcement of cold twisted bar of 8 mm dia 3700 mm (approx.) 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the semi high mast considering the safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4 Nos S.P MCB,1 . Double pole 16Amp. MCB etc as reqd. Logo/Name of manufacturer shall be either embossed or Rivited plate on the pole. Galvanization as per relevant IS. |
| 15 | Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size 25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh i/c MV danger plate and grounding the protection system in suitable quality of CC etc as reqd. |
| 16 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure diecastaluminumbodywithbuiltinorseparate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IESTM -21-11 report , CCT3000°K /4000°K /5700°K /6000°K/ 6500°K (As per ANSI Bin) , SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 100 watt |
| 17 | Supply of XLPE insulated, PVC sheathed Al. Conductorarmoured cable 1.1 KV grade confirmingto IS-7098 of following Size (a) 2 X 6 Sqmm. |
| 18 | Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. |
| 19 | Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 20 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete |
| 21 | Stone tile work for wall lining upto 10 m height with special adhesive over 12mm thick bed of cement mortar 1:3 (1 cement :3 coarse sand), including pointing in white cement with an admixture of pigment to match the stone shade. 8 mm thick (mirror polished and machine cut edge)Granite stone of any colour and shade |
| 22 | Fabrication, supplying, installation, testing and commissioning of openable Signage made of electrocut computerised automated individual letters in hindi & English, total Covering Area and design as per direction of Engineer in charge, Letters to be made from powder coated sheet with 100-150 mm bottom profiles bended along 4-5mm thick sheet of unbreakable Acrylic Sheet to be used in front which will be pinned to the profile. Approved Color, Vinyl (UV) to be used for Colorful look on the front of Acrylic sheet, Letters back should be duly powder coated/painted with Primer & two coats of approved Color Enamel or Duco paint. The signage shall have a system for easy graphic changes and easy access for maintenance. The illumination source shall be of LEDs or approved equivalent modules with individual current regulator/power supply driver module for every signage complete with all internal wiring etc along with connectors for connections to achieve required and uniform illuminations,specifications and design as per the directions of Engineer in charge. LEDspecification :Lumen output : 2500 lumens/sq mtr (minimum) radiance angle : 120 degree and above Illumination should be uniform and suitable arrangement should be made for installation of the whole structure using Gi pipes, angles etc but excluding foundation work. |
| 23 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. asreqd. |