| 1 | Taking out old serviceable /unserviceable under ground cable from trenches/poles /pipe/floor of size16 Sqmm 3.5/4 corecomplete all as specified and directed. |
| 2 | Taking out old serviceable /unserviceable under ground cable from trenches/poles /pipe/floor of size50 Sqmm 3.5/4 corecomplete all as specified and directed. |
| 3 | Reuse and laying only old cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm3.5/4 Core complete all as specified and directed. |
| 4 | Laying only old servicable cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5/4 Core complete all as specified and directed. |
| 5 | Supplying , laying ,passing through pipe , connecting and testingUG cable XLPE insulated ,armoured heavy duty electric cable with aluminium conductor ,1100volts grade XLPE Cable ofsize 16 Sqmm, 4 Core complete all as specified and directed.Make: Polycab/Plaza/Havalls/Finolex |
| 6 | Ditto all as per item No 5 above but XLPE Cable ofsize 50 Sqmm, 3½ Core . |
| 7 | Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc complete complete all as specified and directed. |
| 8 | Returning filling in, soil including spreading, levelling, watering and well ramming in layers not exc 25 cm. Complete all as specified and directed. |
| 9 | Removing surplus excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point. Complete all as specified and directed. |
| 10 | M&L for sand cushioning in trenches for protection of LT under ground cable including watering and consolidation complete all as specified and directed.(Note:- Only punned thickness shall be measured and paid) |
| 11 | Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat of size 250mm x 150mm x 40mm complete all as specified and directed. |
| 12 | M&L for drilling hole underhard standing /road in different locations as per site requirement (between 03 mtr to 12mtr maximum) for laying ofpipe, for protection of cable etc by any means and without disturbing the top surfaceand making good the disturbed surface if any complete all as specified and directed. |
| 13 | Supply and laying GI tube light grade 80 mm bore complete for protection of cables etc complete all as specified and directed. Make : Tata/Jindal/swastik/ Prakash Surya. |
| 14 | Servicing and repair / maintenance of LT panel Boardincluding checking of MCCB,s,Bus bar , cable lugs, voltmeter, ammeter and CTcoil etc for healthy operation and repairs / replacement of MCCB, BUS bar, Voltmeter, Ammeter ,Current Transformers (CTs) and replacing of defective control wiring if any replacement of defective cable lugs and complete forIndoor type / Outdoor type LTPanel of various capacity including necessary addition/ alternationofpanel including cutting/welding/hinges of front and back side of panel board /feeder to match the existing panel board/feeder. Complete all as specified and directed.Note:- Major spares like MCCB, Volt meter,Ammeter, Busbar and CT\"s, Epoxy insulatorwill be measured and paid seperately. |
| 15 | S&F in repair of MCCBsthermal magnetic type of capacity 160 Amps, 4 Pole, breaking capacity 36KA including necessery fixing arrangement complete all as specified and directed. |
| 16 | Ditto as per item No 15 above but 200 Amps 4 Pole having breaking capasity 36 KA . |
| 17 | Ditto as per item No 15 above but250 Amps, 4 Pole having breaking capacity 36 KA . |
| 18 | Ditto as per item No 15 above but400 Amps, 4 Pole having breaking capacity 36 KA . |
| 19 | Ditto as per item No 15 above but630 Amps, 4 Pole having breaking capacity 50 KA . |
| 20 | S&F for in repair/replacement ofhigher efficiency crystalline SPG solar panel of 30 watt capacity with 14 AH battery mounting height 5 to 6 mtr IP 65 protection complete all as specified anddirected. Note :- All spares for repairing the Solar light for making it functional included in quoted unit rate and no extra cost will be paid to contractor on this account. |
| 21 | S&F in repair/replacement ofhigher efficiency crystalline SPG solar panel of 20 watt capacity rated voltage 12.8 V DC with 10.5 AH battery mounting height 5 to 6 mtr of IP 65 protection complete all as specified and directed.Note :- All spares for repairing the Solar light for making it functional included in quoted unit rate and no extra cost will be paid to contractor on this account. |
| 22 | S&F PVC insulated unsheathed multistranded 4 sqmm single core copper conductor cable 1100 V, grade confirming to IS 694 FRLS fixed on control wiring of LT panel/ACB including provision of copper/Aluminium lugs, Copper brass,nut bolts etc complete all as specified and directed. Make: Plaza/Polycab/Finolex /Havells. |
| 23 | M&L for painting of existing LT/HTpole upto 9 / 11meter heightwith twocoat of aluminium paint complete including preparation of old painted surfaces and including makingblue / black colour paintstrip of 15 cm width including writing the Pole Nos.complete all as specified and directed. |
| 24 | M&L for Spray painting to existing LT panel board/Feeder pillar/yard structure with two coats of synthetic enamel high glow paintIst gradeincluding preparation/cleaningof steel surfaces complete all as specified and directed. |
| 25 | M&L for earthing complete with galvanized steel earth plate electrode of size 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 3.25 meter below ground level) connected to galvanised iron strip of size 32mm x 6 mm main earthing lead by means of galvanized bolts, uts and washers with connected to earth test point & to main switch board /paneletc. all as specified and testing on completion with and including all necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 using 20mm graded stone aggregate for earth pit with 40mm x 40mm x 6 mm mild steel angle iron frame for cover, pre cast RCC (1:2:4)type B-1 using 20mm graded stone aggregate 40mm thick cover reinforced with 8 mm dia TMT bars 3 Nos both way with 40mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel,wire mesh all as shown in electrical plate no. 3 of SSR Part I of 2009and 15 mm dia GI light grade pipe earth lead protectioncomplete all as specified and directed. |
| 26 | M&L for GI strip of size 25mm x 4 mmfor Earth continuity conductor or main earthing leadfixed on wallon insulator or PVC pipe or chases or burried in ground or fixed to polesor any other indicated situation for loop earthing etccomplete all as specified and directed. |
| 27 | Labour only for removing all vegetation for LT Panel/Feeder Pillar nearof 2 Mtr all around and complete all as specified and directed. |
| 28 | Supply and fixingLTDanger notice plate of size 200mm x150 mm made of mild steel 1.6 mm thick and vitreous enamel wide on both side and inscription in signal red colour with skull and bone on front side complete all as spiced and directed. |
| 29 | S&F in repair aluminium thimble , cableglandand lux after disconnecting from panel and taking down burnt cable from panel of different location and cutting out the burnt portion of cable and extended the cable from cable loop, preparation of cable including necessary connection and testing complete for 25 Sqmm 3.5 core to 50 sqmm 1100 volt grade sizes complete all as specified and directed.(Note : (i)01 Job consisting of 04 Nos Lugs/thimble at one end of cable(ii) Rate of necessary Earthh work for opening of loop if requried at site are deemed to be included in the quoted unit rate). |
| 30 | Ditto all as per item No 29herein above but sizeof cable 70 sqmm to 120 Sqmm 3.5 core 1100 volt grade complete all as specified and directed. |
| 31 | Cutting and trimming of tree branches/ pushes 2 mtr all around of single pole any size obstructing lumination of street light pole removing trimmed tree branches and bushes. complete all as specified and directed. |
| 32 | S&F aviation light fitting with integral LED aviation light comprising of aluminium housing with polycarbonate enclosure capacity 20 Watt complete all as specified and directed. Make:Philips/Havells/Syska/L&T/Bajaj. |
| 33 | S&Fflood light fitting with new generation energy saving environement friendly long life exclusive innovative die cast aluminium IP66LED flood light with high power LEDs as light source of capacity 120 Watt complete all as specified and directed. Make:- Havells/Philips/Bajaj/Syska. |
| 34 | Supply,installation,commissioning and testing of cubical, outdoortype CPRI approved LT bus bar Box totally enclosed weather and vermi proof, fully compartmentalised , protection of enclosure IP-65 complete with two coat synthetic enamel paint over one coat of red oxide primer, locking arrangement, front size and rear side opening arrangement of suitable size, mounted on angle iron stand of angle size 50mm x 50mm x 6mm having minimum height 45cm from floor level inculding necessary,excavation and earth work, PCC foundation ( mini 45 cm hight from GL), making all incoming and out going connection with suitable size copper cable including cable lugs , cable gland etc and withconsisting the following items:-. (a) 4 Nos bus bar of equal size made by copper conductor with PVC insulated coloured heat shrinkabal type sleeves , ratingbus bar 100 Amps, mounted on non cracking resin type insulator - 1 Setwith suitable capacity of CT,s, Ammeter , volt meter, selector switch and indication lamp , LED indication lamps for ON, OFF & RYB, etc(b) MCCB ,3 phase and neutral, 415 V thermal magnetic type, 4 poles,rating 63 Amps , with rupturing capacity 16 KA - 1 No (incoming).complete all as specified and directed. |
| 35 | S&F in replacement 1100 volts grade heavy duty cable PVC Copper conductor , servedPVC sheathed in service connection of size 2.5 Sqmm 2 core complete all as specified and directed. Make: Plaza/Finolex/polycab/Havells. |
| 36 | Supply and fix three phase street light control PVC encloser IP 66 with timer,contractor rating 40 Amps/TP,MCB rating 40 Amps/TPN astronomical type max load 12-18KW complete all as specified and directed. |