| 1 | S& F Industrial interlocked switched sockets surface/wall mounting socket 63 Amp 3P+N+E4 pole with straight plug 63 Amp 3P+N+E, IP 66 protection, IEC 6039 standard type and sockets enclosure DX3 cabinet IP 66 protection 5 module fixed on wall/surface with including incomming MCB TPN 63 Amp, 4P, 10 KA complete all as specified and directed. |
| 2 | M&L for sub main wiring with four run single of core 10 Sqmm PVC insulated unsheathed muitistranded, FRLS copper conductor cable drawn through and including provision of PVC conduit 32 mm dia medium grade ISI marked and its accessories concealed in walls and connecting terminals to DBs/Switch board including providing two run of 10 sqmm PVC insulated unsheathed multi stranded FRLS copper cable as earth continuity conductor and connecting to common earth dolly complete all as specified and directed.NOTE:- (i) Four runs of 10 sq.mm copper conductor, two run of 10 sq.mm copper earth continuity conductor and one run of 32 mm dia PVC conduit shall be measured as one unit length.(ii) Extra length of cable / wire required for connection to MCBs shall not be measured and the rate quoted per unit shall deemed to be inclusive of the same accordingly. |
| 3 | M&L for submain/circuit wiring with two run of single core 2.5 Sqmm PVC insulated, unsheathed, multistranded FRLS copper conductor 1100 V including 25 mm dia in PVC conduit medium grade ISI marked with all conduit accessories such as Tees, elbows, junction boxes as required concealed in wall alongwith one run of 2.5 Sqmm single core PVC insulated unsheathed FRLS copper conductor as continuous earth wire and connecting to common earth dolly all as specified and directed for 3/5 pin 16 Amp socket outlet on independent board.Note:- Switch, socket and Gl box to be measured and paid for separately |
| 4 | Supply and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 15/16 A modular switch and 15/16 modular socket, conncetion etc. As required at site complete all as specified and directed. |
| 5 | Material & Labour for earthing with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI strip 25x5 mm as earthing lead connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia, 2.7 mtr long Gl medium grade watering pipe, 40mm dia GI light grade earth lead protection pipe, Cl frame and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternatee layer complete including removal of old u/s earth earth plates all as specified and directed by Engr-in-Charge. |
| 6 | Supply Install, testing and commissioning of 1.5 TR capacity, split type air conditioning unit (Inverter type) complete with drive motor, air cooled condenser with all accessories varied speed and dual rotary compressor, including fixing the outdoor units as per manufacture\"s recommendation and fixing of indoor (high wall) unit on wall, providing and making interconnection, including refrigerant piping with nitryle rubber insulation and control cable from indoor unit to outdoor unit upto a distance of 3.0m, power cabling (Max 3.0m from Isolator/Enclosure) to unit, first charging of refrigerant gas (R-32) including cordless remote, drain piping of 25mm dia for connecting drain lines from indoor unit to maximum of 3.0m to nearest drain points, with minimum 5 star rating and EER 3.2 of capacityoutdoor support stand if required complete all as specified and directed.Make:-Voltas/LG/Hitachi/Blue Star / Daikin. |
| 7 | Supply Install, testing and commissioning of 2 TR capacity, split type air conditioning unit (Inverter type) complete with drive motor, air cooled condenser with all accessories varied speed and dual rotary compressor, including fixing the outdoor units as per manufacture\"s recommendation and fixing of indoor (high wall) unit on wall, providing and making interconnection, including refrigerent piping with nitryle rubber insulation and control cable from indoor unit to outdoor unit upto a distance of 3.0m, power cabling (Max 3.0m from Isolator/Enclosure) to unit, first charging of refrigerant gas (R-32) including cordless remote, drain piping of 25mm dia for connecting drain lines from indoor unit to maximum of 3.0m to nearest drain points, with minimum 5 star rating and EER 3.2 of capacityoutdoor support stand if required complete all as specified and directed. Make: Voltas/LG/Hitachi/Blue Star / Daikin. |
| 8 | Supply and fix Voltage stabiliser for automatic operation, single phase naturally air cooled indoor type& designed for input variation between 170V to 250 V with output voltage stabilised at 230V with accuracy of + 2.5% and capacity 4.0 KVA (for 1.5TR & 2 TR AC) |
| 9 | M&L for Sub main wiring complete with 2 runs of 4 sq.mm PVC insulated and unsheathed 1100V grade multistranded FRLS grade copper conductor cable drawn through and including provision of PVC medium grade conduit 25mm dia and its accessories concealed in wall and connecting terminal ends to DB\"s including providing One run of 4 sq.mm PVC insulated unsheathed multistranded FRLS grade copper cable as earth continuity conductor and connecting to common earth dolly, complete all as specified and directed.NOTE:- (i) Two runs of 4 sq.mm copper conductor, One run of 4 sq.mm copper earth continuity conductor and one run of 25mm dia conduit shall be measured as one unit length.(ii) Extra length of cable / wire required for connection to MCBs shall not be measured and the rate quoted per unit shall deemed to be inclusive of the same accordingly. |
| 10 | S&F 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20A \"C\" curve, SP MCB, in sheet metal enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc as required. |