| 1 | Point wiring for light/fan/bell in 20 mm HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification no. WG-PW/SW |
| 2 | Point wiring for independent plug in 20 mm HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire,flush type switch, earthing and required accessories as per specification no. WG-PW/SW |
| 3 | Supplying and erecting anodized aluminium light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs at L70B50 including driver with end caps on provided PVC Block/wooded board with minimum 2 years warranty as per specification No. FG-IDF/LED. |
| 4 | Supplying and erecting Energy Saving Ceiling fan of 3 star rating as per BEE 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF |
| 5 | Supplying and erecting electronic type step regulator for ceiling fan 600/ 900/ |
| 6 | Supplying, installing, testing and commissioning of 1400 VA to 1600 VA Digital pure sine wave inverter based on Insulated Gate Bipolar Transistor (IGBT) technology single phase 230V,50 Hz complete as per specification no. AP-INV (Without batteries) |
| 7 | Supplying and erecting 12 V/200Ah Tubular battery with battery terminal wire, duly charged complete with 36 months warranty complete |
| 8 | Supplying & erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW |
| 9 | Supplying and erecting PVC insulated PVC round sheathed FR 2.5 sq.mm (50 no. x 0.25mm dia.) 3 core flexible multi stranded copper industrial cable for voltage grade up to 1.1 kV |
| 10 | Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on provided iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 |
| 11 | Supplying, erecting & marking SP MCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 12 | Supplying, erecting & marking DP MCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 13 | Supplying, erecting & marking FP MCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 14 | Supplying, installing and testing earthing with galvanised iron earth plate size 60 x 60 x 0.6 cm complete with all accessories of GI materials & recording the results as per specification No. EA-EP |
| 15 | Supplying and erecting fan hook box of 10 mm M.S. round bar bounded to the R.C.C. bars upto 50 mm length each side and pierced through a 16 S.W.G. thick aluminium/M.S. Bowl 100 mm dia. or equivalent square size and having depth upto 75 mm complete erected with duly painted by one coat of red oxide paint and two coats of paint erected in position and without any leakage of slurry of cement concrete on either side of the box and positioned to the bottom level of the slab. Please Enable Macros to View BoQ information |