| 1 | MEERUT |
| 2 | PART - I : Electrical Works |
| 3 | Electrical Works Supply |
| 4 | Supply includingpacking and forwarding, transportation, delivery at storageto site 25kVA, 11/0.433kV Outdoor type, 3 Ph, 50Hz, Cu wound, Dyn11,ONAN Distribution Transformer complete with all accessories and first oil filled as per tender speciifcation. Transformer shall be as per SEB approved make.(Star rating / Efficiency class of transformer shall be as per SEB standard during executiion). |
| 5 | Supply of 11kV double pole structure with 9 mtr RCC poles including cross bracing’s of ISMC ,GOS with earth switch, polymeric type LA’s & pin insulator, HG fuses, ACSR conductor, stay sets, earthing, alkathine tube etc. as per the specification including civil works. Make of all components shall be as per SEB approved make. |
| 6 | Supply of Switchboards |
| 7 | Design, engineering, manufacture, shop testing, supply includingpacking and forwarding, transportation, delivery at storage and from storage to site of power distribution board (PDB) : |
| 8 | 415 V, 36 KA single front type indoor PDB to receive input power consisting ofbus bar chamber, cable alley,outgoing with Fuse complete with wiring, indication lamp, ammeter, voltmeter, MFM (Multi Function Meter) etc including all labour and materials with operating mechanism, all accessories, mandatory spares as per data sheet, auxiliaries with FLP LCS(Local Control switch) for tripping the main incomer of PDB etc complete in all respects as specified in technical specification, data sheet & SLD no. & as per standard Specification. |
| 9 | Single In-comer 100A (with Single phase Protection ) 4P MCCB (with Micro processor and based O/C,S/C & E/F RELASE with LSIG & Shunt trip) etc as required along with VMR. |
| 10 | Outgoing with 3 nos. 63 Amp 4 pole MCCB(with TM based O/C,S/C & E/F RELASE) for i)Auxiliaries of Engine driven compressor like Exhaust fan/ lighting, etcii) Air Compressor iii) APFC Panel |
| 11 | Outgoing with 2 nos. 32 Amp TPN MCCB (with TM based O/C,S/C & E/F RELASE) for UPS and Static Bypass. |
| 12 | Outgoing with 3 no. 40A Fuse and 3 nos. 10A DP MCBwith Timer(24Hrs) Auto/Mannual |
| 13 | Outgoing with 3 no. 40A Fuse and 3 nos. 10A DP MCBwithout Timer |
| 14 | Outdoor type dust & weather proof sheet steel (2 mm thick) enclosed MCCB of following rating for mounting on wall or pedestal. 100A, 415V, 4 Pole, AC-23 duty and suitable for termination of 3.5 x 95/50 sq.mm A2XFY cable on incomer terminals andoutgoing terminals, with RYB indication. |
| 15 | Supply includingpacking and forwarding, transportation, delivery at storage of lighting fixtures complete with mounting bracket, flame proof/non flame proof, control gear box/ Junction Box ,glands ,lugs as per the type of fixture, lamps etc. including civil work with pipe inserts for cables and connecting work, with all material and labour as per specifications, drawings and instruction of Engineer-in-charge. Work to be completed in all respects. |
| 16 | Street lighting, integral flame proof well glass fixture (CMIFR approved for Zone-1/2 gas group IIA & IIB) with 72 W LED luminaire with flame proof control gear/ Junction box (Model no. FLPW-1095 of Baliga make or equivalent) |
| 17 | Supply of Integral flame proof Flood Light fixture (CMIFR approved for Zone-1/2 gas group IIA & IIB) with 72 W LED luminaire (Baliga make or equivalent) |
| 18 | Supply of Street lighting pole 6mtr high GI octagonal pole (Type BOP-6030 of Bajaj make or equivalent) complete with bracket, GI clamps for fixing flame proof control gear box as per standard drawing & specification. |
| 19 | Design, engineering, supply includingpacking and forwarding, transportation, delivery at storage, of the complete earthing and lightning protection system, earth electrodes/ pit, earth main ring, earthing of electrical equipments, instrument panels, field instruments, process equipments and pipes/ flanges including all associated civil work with all material (Like Bitumen coating) and labour as per specification and drawings approved by the company in with IS 3043. |
| 20 | Earth Pits- GI PIPE Electrode (size 3.0 m long, 65NB Class-B) with 6 mm thick chequered plate cover |
| 21 | Earth Pits- Copper plate Electrode with 6 mm thick chequered plate cover |
| 22 | GI Strip (50X6) mm |
| 23 | GI Strip (25X3) mm |
| 24 | Design, engineering,supply includingpacking and forwarding, transportation, delivery at storage, of the 1.1kV grade XLPE insulated, PVC sheathed, FRLS power and control cables (conforming to IS:7098 and specification) including Cable glands & Lugs etc.of following sizes in trenches/ excavated under ground trench /trays, pulling through pipes and its proper sealing, cutting of paved area, roads etc. |
| 25 | 3.5x 50 mm2 A2XFY |
| 26 | 3.5x 35 mm2 A2XFY |
| 27 | 4x 25 mm2 A2XFY |
| 28 | 4x10 mm2 2XWY |
| 29 | 4x 6 mm2 2XWY |
| 30 | 4x 2.5 mm2 2XWY |
| 31 | Supply of following sizes of HDPE Pipe as per approved drawingsand directions of Engineer-In-Charge. |
| 32 | 50 mm NB |
| 33 | 80 mm NB |
| 34 | 100 mm NB |
| 35 | 150 mm NB |
| 36 | Supplyoffollowingincludingnecessary clamp, bolts, rawl plugs etc. |
| 37 | Shock hazard charts |
| 38 | First Aid Boxes |
| 39 | Carbon-di-oxide(CO2) type fire extinguisher 4.5 Kg capacity Complete with gunmetal valve conforming to IS : 3224 With ISI mark, Discharge horn with bend & wall fixing Bracket With Mfg. Test certificate. |
| 40 | Cautionboards |
| 41 | Single Line Diagram in teak wood wall cabinet with glass door |
| 42 | Wooden key box with glass cover |
| 43 | Supply of 1.1kV grade insulated mats required for maintenance of electrical equipment in substation as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge as per IS 15652and Indian Electricity Rules. |
| 44 | Supply of following Hot Dip Galvanized Ladder/Perforated Type cable trays (as per IS 2629) including bends, tee, crosses,horizontal and vertical splices along with cable tray cover(Wherever required for Asthetic look ) etc. as required including supply of all G.I hardwares, all labour and material as required as per standard drawings, specification and direction ofEngineer-in-charge.Perforated type, made from 50mm height and 2.5 mm thick sheet steel & galvanized (86 microns) of following sizes. |
| 45 | 150mm wide |
| 46 | 300mm wide |
| 47 | Supply of 2 Coats of Primer Painted & Fabricated support structure. |
| 48 | UPS SYSTEM |
| 49 | Design, engineering, manufacture, shop testing, supply, packing and forwarding, transportation, delivery at storage ,inspection, packing, forwarding, delivery including commissioning spares as required of UPS systems as per specification, block diagram and following rating: |
| 50 | 3KVA, 230 V Single phase, 50 Hz, single industrial type, UPS system suitable for input Power supply voltage of 320V-460V-TPN with healthy single-Phase Selection, Output 230V +/-1%, AC with Bypass supply, Battery Bank, and 2.0 hrs. Battery backup (VRLA, 12V) and battery capacity shall not be less than 13.0 KVAh (where KVAH = battery AH x 12 V x No. of Batteries). As per enclosed Specification, Block diagram & Data sheet and shall be complete in all respect. Including All interconnecting cables among UPS, Rectifier, battery stand, ACDB etc (30 mtr shall be considered between battery bank and UPS panel, 30 mtr cable shall be considered between ACDB and UPS panel. |
| 51 | 230 V, 36 KA single front type indoor wall mounted ACDB to receive input from UPS consisting of Incomer 32A DP MCB & Outgoing 10 Nos. 6A to 10A DP MCB, complete with wiring, indication lamp, ammeter, voltmeter etc including all labour and materials with operating mechanism & all accessories. |
| 52 | Erection Material |
| 53 | Supply of MS base frame support for switch gear and bracket for misc. electrical equipment,cable tray support out of roled MS section,pipes,plates etc including welding, bolting, reveting, supply of necessary anchor bolts and grouting etc supply of paints applying one coat of anti rust primer two finish coats of approved synthetic enamel paints including bracking walls, floors etc for structure as required including supply of all GI hardware materials including all labour and materials complete as required and the direction of Engineer-in-charge. |
| 54 | For COCO/RO/OLS/MS/DBS/DCU |
| 55 | Supply of electrical accessories including, cable tags, cable tie ,Flexible pvc conduit,cable marker, nickle plated lugs, double compressed brass cable glands,brass adaptar/reducers/nipples, fixing of metallic anchor fasteners for supporting of cable trays and misc. electrical switchgear including all labour and materials complete as required and as per directions of Engineer-In-Charge. |
| 56 | For COCO/RO/OLS/MS/DBS/DCU |
| 57 | Supply of required material for construction of Cable pit with pit cover (SFRC cover HD-20 of IS-12592) including civil works repair, concrete wall/brick wall & its materials, cable conduits interface & its water sealing, cable support structure including all labour and materials complete in all aspect as per approved drawings and directions of Engineer-In-Charge. |
| 58 | 500X500(of inside clearance)X 600(Depth) |
| 59 | 750X750(of inside clearance)X800(Depth) |
| 60 | 1000X1000(of inside clearance)X1000(Depth) |
| 61 | ELECTRICAL WORKS - ERECTION |
| 62 | Installation, Testing and Commissioning of 25kVA, 11/0.433kV Outdoor type, 3 Ph, 50Hz, Cu wound, Dyn11,ONAN Distribution Transformer complete with all accessories and first oil filled as per tender speciifcation. Transformer shall be as per SEB approved make.(Star rating / Efficiency class of transformer shall be as per SEB standard during executiion). |
| 63 | Installation, Testing and Commissioning of 11kV double pole structure with 9 mtr RCC poles including cross bracing’s of ISMC ,GOS with earth switch, polymeric type LA’s & pin insulator, HG fuses, ACSR conductor, stay sets, earthing, alkathine tube etc. as per the specification including civil works. Make of all components shall be as per SEB approved make. |
| 64 | STATUTORY APPROVALS, PERMISSIONS : Coordination & Liasioning with statutory authorities for obtaining Licence/NOC/ Approval /Permission with statutory authorities for GAIL Gas as required for setting of CNG stations .However, all the statutory payment required for such Licence/NOC/ Approval /Permission shall be reimbursed by GGL at actuals against production of documentary evidence and this statutory payment at actuals shall be over and above the coordination and liasioning charges in the items below.The bidder shall note that the rates for the items are inclusive of all expenses (except for statutory payments which shall be reimbursed on actuals) for carrying out the liasioning and coordination work till obtaining the final Licence/NOC/ Approval /Permission.To submit application on behalf of Gail gas to SEB for the incoming power Installation, Testing and Commissioning along with all the required documents, obtaining NOC from SEB for final charging, obtaining drawing approval from CEIG before commencemnt of work and obtaining safety & comissionming approval of Transformer by CEIG and SEB.The price shall be inclusive of Application Fee,liaisioning, Local Transport, Incidental travelling etc, and all other expenses. |
| 65 | Installation, Testing and Commissioning of Switchboards |
| 66 | Design, engineering, manufacture, shop testing, Installation, Testing and Commissioning includingpacking and forwarding, transportation, delivery at storage and from storage to site of power distribution board (PDB) : |
| 67 | 415 V, 36 KA single front type indoor PDB to receive input power consisting ofbus bar chamber, cable alley,outgoing with Fuse complete with wiring, indication lamp, ammeter, voltmeter, MFM (Multi Function Meter) etc including all labour and materials with operating mechanism, all accessories, mandatory spares as per data sheet, auxiliaries with FLP LCS(Local Control switch) for tripping the main incomer of PDB etc complete in all respects as specified in technical specification, data sheet & SLD & as per standard Specification . |
| 68 | Single In-comer 100A (with Single phase Protection ) 4P MCCB (with Micro processor and based O/C,S/C & E/F RELASE with LSIG & Shunt trip) etc as required along with VMR. |
| 69 | Outgoing with 3 nos. 63 Amp 4 pole MCCB(with TM based O/C,S/C & E/F RELASE) for i)Auxiliaries of Engine driven compressor like Exhaust fan/ lighting, etcii) Air Compressor iii) APFC Panel |
| 70 | Outgoing with 2 nos. 32 Amp TPN MCCB (with TM based O/C,S/C & E/F RELASE) for UPS and Static Bypass. |
| 71 | Outgoing with 3 no. 40A Fuse and 3 nos. 10A DP MCBwith Timer(24Hrs) Auto/Mannual |
| 72 | Outgoing with 3 no. 40A Fuse and 3 nos. 10A DP MCBwithout Timer |
| 73 | Outdoor type dust & weather proof sheet steel (2 mm thick) enclosed MCCB of following rating for mounting on wall or pedestal. 100A, 415V, 4 Pole, AC-23 duty and suitable for termination of 3.5 x 95/50 sq.mm A2XFY cable on incomer terminals andoutgoing terminals, with RYB indication. |
| 74 | Installation, Testing and Commissioning includingpacking and forwarding, transportation, delivery at storage of lighting fixtures complete with mounting bracket, flame proof/non flame proof, control gear box/ Junction Box ,glands ,lugs as per the type of fixture, lamps etc. including civil work with pipe inserts for cables and connecting work, with all material and labour as per specifications, drawings and instruction of Engineer-in-charge. Work to be completed in all respects. |
| 75 | Street lighting, integral flame proof well glass fixture (CMIFR approved for Zone-1/2 gas group IIA & IIB) with 72 W LED luminaire with flame proof control gear/ Junction box (Model no. FLPW-1095 of Baliga make or equivalent) |
| 76 | Installation, Testing and Commissioning of Integral flame proof Flood Light fixture (CMIFR approved for Zone-1/2 gas group IIA & IIB) with 72 W LED luminaire (Baliga make or equivalent) |
| 77 | Installation, Testing and Commissioning of Street lighting pole 6mtr high GI octagonal pole (Type BOP-6030 of Bajaj make or equivalent) complete with bracket, GI clamps for fixing flame proof control gear box as per standard drawing & specification. |
| 78 | Installation, Testing and Commissioning includingpacking and forwarding, transportation, delivery at storage, of the complete earthing and lightning protection system, earth electrodes/ pit, earth main ring, earthing of electrical equipments, instrument panels, field instruments, process equipments and pipes/ flanges including all associated civil work with all material (Like Bitumen coating) and labour as per specification and drawings approved by the company in with IS 3043. |
| 79 | Earth Pits- GI PIPE Electrode (size 3.0 m long, 65NB Class-B) with 6 mm thick chequered plate cover |
| 80 | Earth Pits- Copper plate Electrode with 6 mm thick chequered plate cover |
| 81 | GI Strip (50X6) mm |
| 82 | GI Strip (25X3) mm |
| 83 | Installation, Testing and Commissioning, Laying includingpacking and forwarding, transportation, delivery at storage, of the 1.1kV grade XLPE insulated, PVC sheathed, FRLS power and control cables (conforming to IS:7098 and specification) including Cable glands & Lugs etc.of following sizes in trenches/ excavated under ground trench /trays, pulling through pipes and its proper sealing, cutting of paved area, roads etc. |
| 84 | 3.5x 35 mm2 A2XFY |
| 85 | 3.5x 50 mm2 A2XFY |
| 86 | 4x 25 mm2 A2XFY |
| 87 | 4x10 mm2 2XWY |
| 88 | 4x 6 mm2 2XWY |
| 89 | 4x 2.5 mm2 2XWY |
| 90 | Installation, Testing and Commissioning of following sizes of HDPE Pipe |
| 91 | 50 mm NB |
| 92 | 80 mm NB |
| 93 | 100 mm NB |
| 94 | 150 mm NB |
| 95 | Installation, Testing and Commissioningoffollowingincludingnecessary clamp, bolts, rawl plugs etc. |
| 96 | Shock hazard charts |
| 97 | First Aid Boxes |
| 98 | Carbon-di-oxide(CO2) type fire extinguisher 4.5 Kg capacity Complete with gunmetal valve conforming to IS : 3224 With ISI mark, Discharge horn with bend & wall fixing Bracket With Mfg. Test certificate. |
| 99 | Cautionboards |
| 100 | Single Line Diagram in teak wood wall cabinet with glass door |
| 101 | Wooden key box with glass cover |
| 102 | Installation and laying of 1.1kV grade insulated mats required for maintenance of electrical equipment in substation as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge as per IS 15652and Indian Electricity Rules. |
| 103 | Erection testing and commissioning of following Hot Dip Galvanized Ladder/Perforated Typecable trays (as per IS 2629) including bends, tee, crosses,horizontal and vertical splices along with cable tray cover(Wherever required for Asthetic look ) etc. as required including supply of all G.I hardwares, all labour and material as required as per standard drawings, specification and direction ofEngineer-in-charge.Perforated type, made from 50mm height and 2.5 mm thick sheet steel & galvanized (86 microns) of following sizes. |
| 104 | 150mm wide |
| 105 | 300mm wide |
| 106 | Painting work of 2 Coats of Primer Painted & Fabricated support structure. |
| 107 | UPS SYSTEM |
| 108 | Installation, Testing and Commissioning, packing, forwarding, delivery by equipment supplier at site including commissioning spares as requiredof UPS systems as per specification, datasheet, block diagram of the following rating : |
| 109 | 3KVA, 50 Hz, Industrial Type,single UPS system suitable for input Power Installation, Testing and Commissioning voltage of 320V-460V- TPN (184-265V/Ph) , output 230 V +/- 1%, AC withBypass Installation, Testing and Commissioning, Battery Bank , and 2.0 hrs. Battery backup (VRLA, 12V) and battery capacity shall not be less than 14 KVAh (where KVAH = battery AH x 12 V x No. of Batteries). Charger rating shall not be less than 6.5 kW. All interconnecting cables among UPS, Rectifier, battery stand, ACDBetc (30 mtr shall be considered between battery bank and UPS panel, 30 mtr cable shall be considered between ACDB and UPS panel and any other cable which is not defined here but necessary for satisfactory operation of the UPS system). |
| 110 | 230V, 36 KA single front type indoor wall mounted ACDB to receive input from UPS consisting of Incomer 32A DP MCB & Outgoing 10 Nos. 6A to 10A DP MCB, complete with wiring, indication lamp, ammeter, voltmeter etc including all labour and materials with operating mechanism & all accessories. |
| 111 | Erection Material |
| 112 | Installation,welding and Commissioning of MS base frame support for switch gear and bracket for misc. electrical equipment,cable tray support out of roled MS section,pipes,plates etc including welding, bolting, reveting, Installation, Testing and Commissioning of necessary anchor bolts and grouting etc Installation, Testing and Commissioning of paints applying one coat of anti rust primer two finish coats of approved synthetic enamel paints including bracking walls, floors etc for structure as required including Installation, Testing and Commissioning of all GI hardware materials including all labour and materials complete as required and the direction of Engineer-in-charge. |
| 113 | For COCO/RO/OLS/MS/DBS/DCU |
| 114 | Installation, Termination and Commissioning of electrical accessories including, cable tags, cable tie ,Flexible pvc conduit,cable marker, nickle plated lugs, double compressed brass cable glands,brass adaptar/reducers/nipples, fixing of metallic anchor fasteners for supporting of cable trays and misc. electrical switchgear including all labour and materials complete as required and as per directions of Engineer-In-Charge. |
| 115 | For COCO/RO/OLS/MS/DBS/DCU |
| 116 | Civil Constructionof required material for the construction of Cable pit with pit cover (SFRC cover HD-20 of IS-12592) including civil works repair, concrete wall/brick wall & its materials, cable conduits interface & its water sealing, cable support structure including all labour and materials complete in all aspect as per approved drawings and directions of Engineer-In-Charge. |
| 117 | 500X500(of inside clearance)X 600(Depth) |
| 118 | 750X750(of inside clearance)X800(Depth) |
| 119 | 1000X1000(of inside clearance)X1000(Depth) |
| 120 | MECHANICAL & TUBING WORKS |
| 121 | SS TUBE LAYING & TESTING |
| 122 | Laying of SS Tubes with PVC tube clamp, Hydro testing at 375 bar and commissioning of SS tubes along with fittings, hose, mass flow meter and valves as given below and as per Technical Specification and scope of work including handling, lifting, transportation from stores tolocation of CNG stations. |
| 123 | 1”OD X 0.120” min Wall thk.SS Tube |
| 124 | ¾”OD X 0.095” min Wall thk.SS Tube |
| 125 | ½”OD X 0.083” min Wall thk.SS Tube |
| 126 | Supply of SS Tubes as per Technical Specification |
| 127 | 1”OD X 0.095” min Wall thk.,Material SS316 SS Tube (Refer TS) |
| 128 | ¾”OD X 0.095” min Wall thk.,Material SS316 SS Tube (Refer TS) |
| 129 | ½”OD X 0.083” min Wall thk.,Material SS316 SS Tube (Refer TS) |
| 130 | Note: Quantities beyond mentioned quantities may be provided as free issue. |
| 131 | Supply of SS Fittings |
| 132 | Union |
| 133 | Size : 1\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 134 | Size : ¾” OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 135 | Reducing Union |
| 136 | Tube OD 1\" x Tube OD ¾\", Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 137 | Equal Tee |
| 138 | Size:1\" OD x 1\" OD x 1\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 139 | Size:3/4\" OD x 3/4\" OD x 3/4\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 140 | Size:½” OD x ½” OD x ½” OD, Material:SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 141 | Nut |
| 142 | ¾ \" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 143 | ½\" OD, Material : SS316(Rated pressure : 6000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 144 | 1\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 145 | Front Ferrule |
| 146 | 3/4\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 147 | ½\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 148 | 1\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 149 | Back Ferrule |
| 150 | 3/4\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 151 | ½\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 152 | 1\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 153 | Plug |
| 154 | Size : ¾\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 155 | Size : 1\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 156 | Size : ½\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 157 | Cap |
| 158 | Size : ¾\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 159 | Size : 1\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 160 | Size : ½\" OD, Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 161 | Reducing Union Tee |
| 162 | ¾\" OD x ½\" OD x ¾\" OD, Material : SS316(Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 163 | Male Connector |
| 164 | 1/2\" NPT male to 3/4\" OD Material : SS316 (Rated pressure : 5000 PSI @ 70°F Temperature : 0°F to 400°F) |
| 165 | Supply of SS Ball Valvesconforming to Technical Specification for SS Ball Valves of following sizes, specifications as indicated below : |
| 166 | 2-Way Floating Normal Bore Ball Valve ¾\" |
| 167 | 3-Way Trunnion Mounted, Reducer BoreBall Valve ½\" OD end Connection and ¼” NPT (F) bottom end connection |
| 168 | 2-Way Floating Normal Bore Ball Valve 1/2\" |
| 169 | ERECTION OF MECH. EQUIPMENT |
| 170 | Handling (including lifting and transportation from Client\"s store within GA toCNG stations)and erecting in position, the following equipmenteither on the foundation oron roof at ~ 3 to 4 m above ground level.Contractor\"s scopeincludes supply of all material and accessories including but not limited to any fixtures, clamps, gasket, nut bolts, etc.. Scope also includes supply of all lifting tools / necessary accessories and hiring of cranes for same. |
| 171 | Type-I; Cascade 4500/3000 L water capacity, Erection at + Ground level |
| 172 | DISMANTLING, SHIFTING, RE-INSTALLATION & COMMISSIONING OF CNG Decompression unit and Conversion of DBS to Online |
| 173 | Dismantling,disconnecting cables,earthing, SS tube,pipe, removal of Decompression unit/Daughter Booster Compressor along with related accessoriesfrom one Station within GA and shifting/transportation including loading, unloading and then installation, erection, testing and commissioning of same equipment along with accessories, cablesatother station within GANote: The above item also includesbreaking/dismantling of foundation if required, supply of pipes/cables ,pipe fittings, foundation bolts, supervision of OEM required for installation and commissioning of the equipment at other station. |
| 174 | Handling including lifting and transportation of dispenser frame from Client\"s store within city to CNG stations and Erection at + Ground Level |
| 175 | The quantities given above against individual items are indicative and shall not be considered to be binding.The quantities may increase or decrease at site at the time of actual execution and as per the discretion of Owner/ Engineer-in-charge.The unit rate shall be operated to work out the final payment due to Contractor. |
| 176 | ERECTION OF MECH. EQUIPMENT |
| 177 | Supply, erection & commissioning of following miscellaneous items as per technical specification and at locations (within the stations) as directed by EIC |
| 178 | Fire fighting Equipments |
| 179 | Stored Pressure Type DCP -9 Kg confirming to IS 15683 and as per TS |
| 180 | DCP -75 Kg confirming to IS 10658 and as per TS |
| 181 | CO2 – 4.5 Kg confirming to IS 15683 and as per TS |
| 182 | Sand Bucket Stand with 4 Nos. Bucket and as per TS |