| 1 | Taking downfor servicingof split type AC 1.5TR Capacity including cleaning of cooling coil, air filters/plasma filters etc, (Indoor unit), condenser, compressors, fan motor etc,(Out door unit) with vacuum cleaner Or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, Remote control unit including PCB, fan, blower, etc., changing electrical connections if requiredand keepingthe AC unit in satisfactory working condition after necessary servicing and refixing the same in existing position complete all specified and as directed by Engineer-in-Charge. |
| 2 | Taking downfor servicingof split type AC 2.0TR Capacityincluding cleaning of cooling coil, air filters/plasma filters etc, (Indoor unit), condenser, compressors, fan motor etc,(Out door unit) with vacuum cleaner or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, Remote control unit including PCB, fan, blower, etc., changing electrical connectionsand keepingthe AC unit in satisfactory working condition after necessary servicing and refixing the same in existing position complete all specified and as directed by Engineer-in-Charge. |
| 3 | Taking downfor servicingofWindow type AC 1.5TRCapacityincluding cleaning of cooling coil, air filters , condenser, compressors, fan motor etc with vacuum cleaner or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, remote control unit including PCB, fan, blower, etc, changing electrical connections andkeepingthe AC unit in satisfactory working condition after necessary servicing/ repair/ replacement of defective spares as required and refixing the same in existing positioncomplete all specified and as directed by Engineer-in-Charge. |
| 4 | Taking downfor servicingofWindow type AC 2.0 TRCapacityincluding cleaning of cooling coil, air filters , condenser, compressors, fan motor etc with vacuum cleaner or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, remote control unit including PCB, fan, blower, etc, changing electrical connections andkeepingthe AC unit in satisfactory working condition after necessary servicing/ repair/ replacement of defective spares as required and refixing the same in existing positioncomplete all specified and as directed by Engineer-in-Charge. |
| 5 | Supply and fix in repairs starting relay for 1.5 TR compressor all as specified and directed. |
| 6 | Supply and fix in repairs starting relay for 2 TR compressor all as specified and directed. |
| 7 | Supply and fix in repairs over load protector for 1.5 TR compressor all as specified and directed. |
| 8 | Supply and fix in repairs over load protector for 2TR compressor all as specified and directed. |
| 9 | Supply and fix in repairs Thermostat switch for 1.5 TRsplit/window type AC all as specified and directed. |
| 10 | Supply and fix in repairs Thermostat switch for2 TR split/Window type AC all as specified and directed. |
| 11 | Supply and fix in repairs of Starting capacitor 80-100 Mfd capacity in metal containerall as specified and directed. |
| 12 | Supply and fix in repairs of Starting capacitor 120-150 Mfd capacity in metal containerall as specified and directed. |
| 13 | Supply and fix in repairs of running capacitor 36 Mfd capacity in metal container pin type all as specified and directed. |
| 14 | Supply and fix in repairs of running capacitor 50±4 Mfd capacity in metal container pin type all as specified and directed. |
| 15 | Supply and fix in repairs of running capacitor 50±6 Mfd capacity in metal container pin type all as specified and directed. |
| 16 | Supply & Fix Running capacitor 10 mfd metal body pin type complete all as specified and directed |
| 17 | Supply & Fix Running capacitor 6 mfd metal body pin type complete all as specified and directed |
| 18 | Supply & Fix Running capacitor 4 mfd metal body pin type complete all as specified and directed |
| 19 | Supply & Fix Running capacitor 2.5 mfd metal body pin type complete all as specified and directed |
| 20 | Supply and fix in repairs suction copper pipe line heavy duty 1/2\"\" diaand flair nuts from indoor to outdoor unit of split AC 1.5 /2 TR capacity all as specified and directed. |
| 21 | Supply and fix in repairs discharge copper pipe line heavy duty 1/4\" diaand flair nuts from indoor to outdoor unit of split AC 1.5 TR /2 TR capacity all as specified and directed. |
| 22 | Supply and fix in repairs discharge copper pipe line heavy duty 5/8\" dia and flair nuts from indoor to outdoor unit of split AC 1.5 TR /2 TR capacity all as specified and directed. |
| 23 | Supply and fix in repairs discharge copper pipe line heavy duty 3/8\" diaand flair nuts from indoor to outdoor unit of split AC 1.5 TR /2 TR capacity all as specified and directed. |
| 24 | Supply and fix in repairs discharge copper pipe line heavy duty 3/4\" diaand flair nuts from indoor to outdoor unit of split AC 1.5 TR /2 TR capacity all as specified and directed. |
| 25 | Supply and fix in repairsPVC pipe nylon imbraided 15 mm dia for condenser water drain fitted with clamps/ concealed in wall all as specified and directed. |
| 26 | S&F Foam insulation for copper tubing of size 1/2\"\" dia complete all as specified and directed. |
| 27 | S&F Foam insulation for copper tubing of size 5/8\"\" dia complete all as specified and directed. |
| 28 | S&F Foam insulation for copper tubing of size 1/4\"\" dia complete all as specified and directed. |
| 29 | S&F Foam insulation for copper tubing of size 3/8\"\" dia complete all as specified and directed. |
| 30 | S&F Foam insulation for copper tubing of size 3/4\"\" dia complete all as specified and directed. |
| 31 | Dismantling of defective condensing unit of split type AC of 1.5 TR capacity and supply & fixing new condensing unit complete with condensing copper coilcomplete all as specified and directed. |
| 32 | Dismantling of defective condensing unit of split type AC of 2 TR capacity and supply & fixing new condensing unit complete with condensing coppercoil, complete all as specified and directed. |
| 33 | Dismantling of burnt blower motor of 1.5 TR split AC (indoor unit) and supply & fixing blower motor of same manufacturer of AC. Make of AC Carrier/Voltas /Blue staras per sample complete all as specified and directed. |
| 34 | Dismantling of burnt blower motor of 2 TR split AC (indoor unit) and supply & fixing blower motor of same manufacturer of AC. Make of AC Carrier/Voltas /Blue star/LG/Samsungas per sample complete all as specified and directed. |
| 35 | Dismantling of burnt condenser motor of 1.5 TR split AC (Outdoor unit) and rewinding & refixingcondensermotor at same position including replacement of bearing bushing complete. Make of AC Carrier/Voltas /Blue staras per sample complete all as specified and directed. |
| 36 | Dismantling of burnt condenser motor of 2 TR split AC (Outdoor unit) and rewinding & refixing condenser motor at same position including replacement of bearing bushing complete. Make of AC Carrier/Voltas /Blue star/LG/Samsungas per sample complete all as specified and directed. |
| 37 | Dismantling of burnt swing motor of 1.5 TR split AC (indoor unit) and supply & fixing swing motor of same manufacturer of AC. Make of AC Carrier/Voltas /Blue star/LG/Samsungas per sample complete all as specified and directed. |
| 38 | Dismantling of burnt swing motor of2 TR split AC (indoor unit) and supply & fixing swing motor of same manufacturer of AC. Make of AC Carrier/Voltas /Blue star/LG/Samsungas per sample complete all as specified and directed. |
| 39 | Supply and charging (Top up) the AC unit of 1.5 TR /2 TR split type AC unit with Refrigerant Gas compatible to R-22 typein required quantity complete all as specified and directed. |
| 40 | Supply and charging (Top up) the AC unit of 1.5 TR /2 TR split type AC unit with Refrigerant Gas compatible to R-134 typein required quantity complete all as specified and directed. |
| 41 | Supply and charging (Top up) the AC unit of 1.5 TR /2 TR split type AC unit with Refrigerant Gas compatible to R-410 typein required quantity complete all as specified and directed. |
| 42 | Supply and charging (Top up) the AC unit of 1.5 TR /2 TR split type AC unit with Refrigerant Gas compatible to R-32 typein required quantity complete all as specified and directed. |
| 43 | Supply and chargingthe ACunit of 1.5/2/2.5/3.5/4.5 TR split type AC unit with Nitrogen Gas for detecting of leakages required as per site quantity complete all as specified and directed. |
| 44 | Supply and fixed in repairs ofsuction valve size 1/2\" complete all as specified and directed |
| 45 | Supply and fixed in repairs of discharge valve size 1/4\" complete all as specified and directed. |
| 46 | Supply and fixed in repairs ofsuction valve size 5/8\" complete all as specified and directed . |
| 47 | Supply and fixed in repairs of discharge valve size 3/8\" complete all as specified and directed. |
| 48 | Dismantling of un-serviceable cooling coil unitany type any size of indoor unit of split type Air Conditioner of capacity 1.5 TRby cutting the suction line and discharge line, and providing new cooling copper coil unit of indoor unit (of same capacity), including testing on completion complete all as directed by the Engr-in-Charge. |
| 49 | Dismantling of un-serviceable cooling coil any type any size of indoor unit of split type Air Conditioner of capacity 2.0 TRby cutting the suction line and discharge line, and providing new cooling copper coil of indoor unit (of same capacity),including testing on completion complete all as directed by the Engr-in-Charge. |
| 50 | M&L for carrying out pressure leak test of split ACs 1.5 / 2.0 TRcapacities by Nitrogen gas pressure for detecting leak in cooling unit refrigerant pipe and repairing the leak by welding or brazing of cooling unit and refrigerant pipe, putting under pressure for leak checking after repairs of leak pipe including gas charging transporting & carrying out Tools and Plant required at sitecomplete all as specified and directed. Note : Cost of Nitrogen gas will be paid under respective schedule |
| 51 | M&L for carrying out pressure leak test of split ACs 2.0 TRcapacities by Nitrogen gas pressure for detecting leak in cooling unit refrigerant pipe and repairing the leak by welding or brazing of cooling unit and refrigerant pipe, putting under pressure for leak checking after repairs of leak pipe including gas charging transporting & carrying out Tools and Plant required at sitecomplete all as specified and directed.Note : Cost of Nitrogen gas will be paid under respective schedule |
| 52 | M&L carrying out pressure leak test of 1.5 TR windowAC by Nitrogen gas pressure for detecting leak in cooling unit refrigerant pipe and repairing the leak by welding or brazing of cooling unit and refrigerant pipe, putting under pressure for leak checking after repairs of leak pipe including gas charging transporting & carrying out Tools and Plant required at site complete all as specified and directed. Note : Cost of Nitrogen gas will be paid under respective schedule |
| 53 | M&L carrying out pressure leak test of 2.0 TR windowAC by Nitrogen gas pressure for detecting leak in cooling unit refrigerant pipe and repairing the leak by welding or brazing of cooling unit and refrigerant pipe, putting under pressure for leak checking after repairs of leak pipe including gas charging transporting & carrying out Tools and Plant required at site complete all as specified and directed. Note : Cost of Nitrogen gas will be paid under respective schedule |
| 54 | Dismantling of defective worn out wiring of indoor unit of split AC of capacity 1.5 TR including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 55 | Dismantling of defective worn out wiring of indoor unit of split AC of capacity 2 TR including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 56 | Supply and fixing in repairs front grillfor window AC of 1.5 TR /2TR of existing make complete all as specified and directed. |
| 57 | S&FPVC insulated and PVC round sheathed copper conductor (flexible) industrial cable, (FRLS) 1100 Volts, conforming to IS 694 of size 2.5 sqmm 3 Core connecting electrical equipment\"s with terminal lugs / clips as per site requirement, complete all as specified and as directed. |
| 58 | S&F Bottom tray of 1.5 ton /2 ton capacity window type AC made out of 14 SWG mild steel sheet Including painting with two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed. |
| 59 | Taking out existing out door unit of split type Air Conditioner including refrigerant lines and electrical connections (of capacity 1.5 TR / 2.0 TR) and re-fixing atnew location as directedalongwith fixing arrangement with nuts and bolts complete all as directed by the Engr-in-Charge. (Note :- Excess requirement of refrigerant pipe line, AC outdoor metallic stand ,electric connection cable , drain pipe topping up of refrigerant gas shall be measured and paid separately under relevant item of this schedule) |
| 60 | Taking out existing indoor unit of split type Air Conditioner including refrigerant lines and electrical connections of capacity 1.5 TR / 2.0 TR) and re-fixing atnew location alongwith fixing arrangement with screwed on wooden gutkaon wall surface and making good the disturbed surfacescomplete all as directed by the Engr-in-Charge. (Note :- Excess requirement of refrigerant pipe line, electric connection cable ,drain pipe and topping up of refrigerant gas to be measured and paid separately under relevant item of this schedule) |
| 61 | S&F Compressor sealed unit for Split type Air Conditioner of capacity 1.5 tonreciprocating compressor by removing of old burnt compressor andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc.Note :- Charging of gas refrigerant will be paid and measured separately |
| 62 | All as per item No 61 here in before but 2 TR capacity reciprocating compressor |
| 63 | All as per item No 61 here in before but 1.5 TR capacity rotary type |
| 64 | All as per item No 61 here in before but 2 TR capacityrotary compressor |
| 65 | S&FCondenser fan blade suitable for 1.5 TR capacity Split type Air Conditionerincluding taking out old one complete all as specified and as directed. |
| 66 | S&FCondenser fan blade suitable for 2.0 TR capacity Split type Air Conditionerincluding taking out old one complete all as specified and as directed. |
| 67 | S&FRoller runner, suitable for 1.5 TRcapacity Split type Air Conditionerincluding taking out old one complete all as specified and as directed. |
| 68 | S&FRoller runner, suitable for2.0 TRcapacity Split type Air Conditionerincluding taking out old one complete all as specified and as directed. |
| 69 | Taking down indoor unit of 1.5 TRcapacity by preserving the existing gas in outdoor unit, checking and overhauling the complete indoor unit part by part and refixing at same position including testing complete all as directed by the Engr-in-Charge. (Note:-The repair of indoor motor, filters and roller runnerto be measured and paid separately under relevant item of this BOQ) |
| 70 | Taking down indoor unit of 2.0 TR capacity by preserving the existing gas in outdoor unit, checking and overhauling the complete indoor unit part by part and refixing at same position including testing complete all as directed by the Engr-in-Charge.(Note:-The repair of indoor motor, filters and roller runnerto be measured and paid separately under relevant item of this BOQ) |
| 71 | S&F in replacement of AC Outdoor metallic stand for fixing out door unit complete all as specified and as directed. |
| 72 | Taking down unserviceable blower motor base (2mm thick Mild Steel Sheet) of 1.5 TR/2TR capacity split AC and supply and fixing new blower motor base by welding / fixing by nut and boltrefixing the blower motor after completing the base and aligning the motorcomplete as directed by the Engr-in-Charge. |
| 73 | S&F Compressor sealed unit ofWindow type Air Conditioner of capacity 1.5 TR reciprocating typeby removing of old burnt compressor andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes complete all as directed by the Engr-in-Charge. |
| 74 | All as per item No 73 here in before but 2.0 TR capacity reciprocating compressor. |
| 75 | All as per item No 73 here in before but 1.5 TR capacity rotary type . |
| 76 | All as per item No 73 here in before but 2.0 TR capacity rotary compressor. |
| 77 | S&FCooling coil condenser unit of Window type Air Conditioner of capacity 1.5/2.0 TR including providing connections and fixing in proper position including taking down old one complete all as directed by the Engr-in-Charge. |
| 78 | Taking downunserviceable blower motor of existing make/model ofwindow type Air Conditioner 1.5 TRand refixing in proper position after rewinding and repair including providing all connections, complete all as directed by the Engr-in-Charge. |
| 79 | Taking downunserviceable blower motor of existing make/model ofwindow type Air Conditioner2.0 TR and refixing in proper position after rewinding and repair including providing all connections, complete all as directed by the Engr-in-Charge. |
| 80 | S&F Blower motor fan blade of existing make/model ofwindow type Air Conditioner1.5 TRincluding providing all connections, in proper position as in repaircomplete all as directed by the Engr-in-Charge. |
| 81 | S&F Blower motor fan blade of existing make/model ofwindow type Air Conditioner2 TRincluding providing all connections, in proper position as in repaircomplete all as directed by the Engr-in-Charge. |
| 82 | S&FRunner of existing make/model ofWindow type Air Conditioner1.5 TR including providing all connections, in proper position as in repaircomplete all as directed by the Engr-in-Charge. |
| 83 | S&FRunner of existing make/model ofWindow type Air Conditioner2 TR including providing all connections, in proper position as in repaircomplete all as directed by the Engr-in-Charge. |
| 84 | Taking down window type Air Conditioner, shifting and installation of same at other location within two Km radius including cutting and opening of existingbrick work and making good dismantled portion in cement mortar 1:3 as required in exc. Half Brick but not exc. one brick thick Walls and providing a coat ofwhite wash on finished surface complete all as specified and as directed. |
| 85 | M&L Cutting openings, through brick wall for fixing of window type Air Conditioner including necessary wooden frame work not less than 2\" by 2\" thick size as per AC modelincluding fair finish of side walls in cement mortar (1:6) with three coats white wash, cleaning and stacking bricks removing surplus serviceable bricks, hard-core etc to store and rubbish not exc 50m complete all as specified and as directed. |
| 86 | S&F Single phase preventer 415 type SPPR (Auto reset 540 volts un balance) complete all as specified and as directed. |
| 87 | Supply and fix power contactor 2 pole, coil voltage 230Volts of capacity 25 Amps Complete all as specified and directed:- |
| 88 | Supply and fix power contactor 3 pole, coil voltage 415 Volts of capacity32 Amps Complete all as specified and as directed:- |
| 89 | Supply and Fix Timer single phase analogue type 230 volts complete all as specified and directed. |
| 90 | Supply and fix remote control hand setfor 2.0TR capacity split AC complete all as specified and as directed. |
| 91 | Supply and fix remote control hand setfor 1.5TR capacity split AC complete all as specified and as directed. |
| 92 | Supply and fix remote control hand setmake suitable for 2.0TR capacity window type AC complete all as specified and as directed. |
| 93 | Supply and fix remote control hand set suitable for 1.5 TR capacity window type AC complete all as specified and as directed. |
| 94 | M&L for servicing including cleaning of condenser coil fins with mild detergent, cleaning of indoor unitand descaling of condenser coil forVertical type3 phase Air Conditioner, of any make/capacity after taking down the outdoor unit and refixing in the existing location or any where and replacement of insulation of suction & discharge line complete all as specified and as directed. |
| 95 | S&F PCB kit complete for Verticaltype Air Conditionerof any make and capacity complete all as specified and as directed. |
| 96 | S&F Compressor sealed unit for Vertical type Air Conditioner of capacity 2.0TR by removing of old burnt compressor andfixing as per manufacturer instruction complete all as specified and as directed.Note :- Charging of Refrigerant gas will be measured and paid separately |
| 97 | S&F Compressor sealed unit for Vertical type Air Conditioner of capacity 3.5TR by removing of old burnt compressor andfixing as per manufacturer instruction complete all as specified and as directed.Note :- Charging of Refrigerant gas will be measured and paid separately |
| 98 | S&F Compressor sealed unit for Vertical type Air Conditioner of capacity 4.5 TR by removing of old burnt compressor andfixing as per manufacturer instruction complete all as specified and as directed.Note :- Charging of Refrigerant gas will be measured and paid separately |
| 99 | Taking downunserviceable Condenser motor of existing make/model ofVertical type Air Conditioner 2.5/3.5/4.5TR (Outdoor) and refixing in proper position after rewinding and repair including providing all connections, complete all as directed by the Engr-in-Charge |
| 100 | Taking downunserviceable blower motor of existing make/model ofVertical type Air Conditioner 2.5/3.5/4.5 TR (Indoor) and supply and fixing in proper position including providing all connections, complete all as directed by the Engr-in-Charge |
| 101 | Dismantling of defective condensing unit of Vertical type AC of 2.5 TR capacity and supply & fixing new condensing unit complete with condensing coppercoil, complete all as specified and directed. |
| 102 | Taking out existing out door unit of Vertical type Air Conditioner including refrigerant lines and electrical connections (of capacity 2.5/3.5/4.5 TR ) and re-fixing atnew location as directed including providing PCC platform of size 900 mm x 600 mm x 200 mm (1:4:8) ) type D-2 using40 mm graded crushed stone aggregate)alongwith fixing arrangement with nuts and bolts complete all as directed by the Engr-in-Charge. (Note :- Excess requirement of refrigerant pipe line, electric connection cable and drain pipe shall be measured and paid separately under relevant item of this schedule) |
| 103 | Taking out existing indoor unit of Vertical type Air Conditioner including refrigerant lines and electrical connections of capacity 2.5/3.5/4.5 TR) and re-fixing atnew location alongwith fixing arrangementand making good the disturbed surfacescomplete all as directed by the Engr-in-Charge. (Note :- Excess requirement of refrigerant pipe line, electric connection cable and drain pipe to be measured and paid separately under relevant item of this schedule) |
| 104 | Dismantling of defective refrigerator of any make and capacityincluding transportation to workshop and back for thorough checking of all accessories and components, repairs and reassembling the same after repair/replacement of defective accessories/components and testing complete all as directed by Engr-in-charge . |
| 105 | Supply & Fix Cooling chamber including cooling coil of existing size shape suitable for refrigerator of size and of capacity 165/180 ltrs complete all as specified and directed |
| 106 | Supply & Fix Cooling chamber including cooling coil of existing size shape suitable for refrigerator of size and of capacity 280/310 ltrs complete all as specified and directed |
| 107 | Supply & Fix Thermostat defrost type switch suitable for refrigerator of capacity 165/220/310 ltrs complete all as specified and directed |
| 108 | Supply & Fix PTC Relay with overload suitable for refrigerator of capacity 165/190/200 ltrs complete all as specified and directed |
| 109 | Supply & Fix PTC relay with overload suitable for refrigerator of capacity 250/286/310 Litre complete all as specified and directed |
| 110 | Supply & Fix Capillary tube of size 0.36mm dia for any type/size refrigerator complete all as specified and directed |
| 111 | Supply & Fix Copper pencil strainers of size 4\" long double mouth complete all as specified and directed |
| 112 | Supply & Fix PCB with Wiring set complete consisting of PVC insulated flexible wire with stranded copper conductor of size 1.5 sqmm and fixing clips for refrigerator all types. |
| 113 | Supply & FixBimetal2 wire/3wire /4 wire complete all as specified and directed |
| 114 | Supply & Fix Forst free fan motor SP 230 volts complete all as specified and directed |
| 115 | Supply & Fix Sensor for cooling coil complete all as specified and directed |
| 116 | Supply & FixPCBtimer of refrigerator 180-310ltrsrequired as per site complete all as specified and directed |
| 117 | Supply & Fix Condenser coil for 165 to 200 Ltrs complete all as specified and directed |
| 118 | Supply & Fix Condenser coil for 250 to 310 Ltrs complete all as specified and directed |
| 119 | S&F ofheating coil including fixing accessories suitable for 250/286/310 ltrscomplete all as specified and directed |
| 120 | Taking out burnt compressor after disconnecting suction and discharge line and supply and fixing new compressor as per existing including testing complete all as specified and directedfor Refrigerator of Capacity 165/180 Ltrs (Re- Charging of gas will be measured and paid separately) |
| 121 | Taking out burnt compressor after disconnecting suction and discharge line and supply and fixing new compressor as per existing including testing complete all as specified and directedfor Refrigerator of Capacity 285/310 Ltrs (Re- Charging of gas will be measured and paid separately) |
| 122 | Dismantling of defective water cooler storage type of 40/80/120/150 ltrs capacityincluding transportation to workshop and backfor thorough checking/including all accessories and components re-assembling the same after repair/ replacement of defective accessories/components including testing complete all as specified and directed. |
| 123 | Supply & Fix Aluminium fan blade for blower motor for water cooler of capacity 40/80/120/150 ltrs complete all as specified and directed |
| 124 | Supply & Fix PCB and Wiring set complete consisting of PVC insulated cable wiring stranded copper conductor connecting clips etc suitable for water cooler 40/80/120/150 ltrs complete all as specified and directed |
| 125 | Supply & Fix Thermostat including plastic regulating knob as per existing for water cooler of cooling capacity 40/80/120/150 ltrs complete all as specified and directed |
| 126 | Supply & Fix Relay for water cooler type suitable for water cooler storage cooling capacity 40/80 /120/150ltrs/hrs complete all as specified and directed |
| 127 | Supply & Fix Over load protector for compressor suitable for water cooler of capacity 40/80120/150 Ltrs complete all as specified and directed |
| 128 | Supply & Fix Self closing bib tap/push tap 15mm dia chromium plated steel suitable for water cooler 40/80/150/120 ltr/hrs capacity. |
| 129 | Supply & Fix PVC connection pipe high density 15mm dia 300mm long including jubilee clamps for inner connection from tank outlet to tap. |
| 130 | Supply & Fix 15 mm dia PVC connection pipe 450 mm long complete with PVC union at both end complete all as specified and directed |
| 131 | Supply & Fix 15 mm dia Float valve PVC complete with all accessories complete all as specified and directed |
| 132 | Supply & Fix new compressor suitable for 40/40 ltr/hrs storage capacity including testingall as specified and directed by Engineer-in-Charge. (Recharging of gas will be measured and paid separately). |
| 133 | Supply & Fix new compressor suitable for 40/80 ltr/hrs storage capacity including testingall as specified and directed by Engineer-in-Charge. (Recharging of gas will be measured and paid separately). |
| 134 | Supply & Fix new compressor suitable for 120 ltr/hrs storage capacity including testingall as specified and directed by Engineer-in-Charge. (Recharging of gas will be measured and paid separately). |
| 135 | Supply & Fix new compressor suitable for 150 ltr/hrs storage capacity including testingall as specified and directed by Engineer-in-Charge. (Recharging of gas will be measured and paid separately). |
| 136 | Taking out old burnt Condenser fan motor and supply and fixing of new blower motor and testingsuitable for water coolerany make or type. |
| 137 | Dismantling of defective deep freezer including transportation to workshop and back of any capacity, sizeand type for thorough checking of all accessories and components re-assembling the same after repair/ replacement of defective accessories/components including testing complete all as specified and directed by the Engr-in-Charge |
| 138 | Supply & Fix new deep fridgecompressor for storage capacity of 400 ltrs deep freezer including testingall as specified and directed . (Recharging of gas will be measured and paid separately). |
| 139 | Supply & Fix new deep fridgecompressor for storage capacity of 500 ltrs deep freezer including testingall as specified and directed . (Recharging of gas will be measured and paid separately). |
| 140 | Supply & Fix Relay for deep freezer of any size/capacity complete all as specified and directed |
| 141 | Supply & Fix Overload for compressor of deep freezer of any size/capacity complete all as specified and directed |
| 142 | Supply & Fix Thermostat for deep freezer complete al as specified and directed |
| 143 | Supply & Fix 4\" condenser fan motor 240 volt complete all as specified and directed |
| 144 | Material and Labour for making holes of required diaonwalls any type and thick for connectingcopper pipes of indoor and outdoorof Split AC 15/2.0 Tonby core cutting drill machineas per site requirement and making good the disturbed surfaces duly painted matching with the existing one complete all as specified and directed. |
| 145 | Supply only PVC Flexible pipe 80 mm dia complete with all fittings all as specified . |
| 146 | S & F PVC Cable trays with cover of size 75mm X 75mmon walls / ceilings as per site requirement for properfixing of Copper pipe with insulation alongwith fittings and fixtures arrangementcomplete all as specified and directed. |
| 147 | Note: Schedule of credit (SCHEDULE OF CREDIT)amount of Rs ________ mentioned on Page No ____ shall be deducted from the total quoted amount of BOQ. |