| 1 | Supply & install, testing & commissioning in repairs LT APFC panel -75 KVAR compartmental out door type, Lockable fabricationmade by 3.15 mm thick sheet CRCA approved machine pressed, dust and vermin, weather proof design framed on angle iron (40mm x 40mm x 6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, including with 4 \" Exhaust Fan along with air vents, Capacitor on/off indicators and Auto & manual Selector switch for all Capacitors and cable entry with glands with all control wiring and thimbles etc, foundation /grouting on & including PCC work as per site requirement with the following :-(a) Copper bus bar250 Amp Cap- 1 Set ( Set of 4 strips), (b) MCCB 200 Amp 415V TPNwith spreader links, 36 KA-1 No, (c) 25 KVAR Capacitor Heavy Duty- 2 Nos, (d) Capacitor duty contactor MO C25 or equivalent - 2 Nos, (e) MCB 63 Amp, TP ,10 KA-2 Nos, (f) 10 KVAR Capacitor Heavy Duty- 1 Nos (g) Capacitor duty contactor MO C10 or equivalent- 1 Nos, (h) MCB 20 Amp, TP ,10 KA-1 Nos, (j)5 KVAR Capacitor Heavy Duty- 2 Nos, (k) Capacitor duty contactor MO C5 or equivalent - 2 Nos, (l) MCB 16 Amp, TP ,10 KA-2 Nos, (m) 2 KVAR Capacitor Heavy Duty- 2 Nos, (n) Capacitor duty contactor MO C2 or equivalent - 2 Nos, (o) MCB 10 Amp, TP ,10 KA-2 Nos,(p) 1 KVAR Capacitor Heavy Duty- 1 Nos, (q) Capacitor duty contactor MO C1 orequivalent - 1 Nos, (r) MCB 6 Amp, TP ,10 KA-1 Nos(s) Indicating fuse/lamp LED type R,Y,B - 03 Nos, (t)VAF meter 3 Phase-01 No, (u) Control MCB SPN 6 Amps -03 Nos, (v) CT Coil 200/5 Amps -03 Nos and 250/5 Amp -01 Nos, (w) APFC Relay 8 stages - 01 Nos |
| 2 | Supply & install, testing & commissioning in repairs LT APFC panel -100 KVAR compartmental out door type, Lockable fabricationmade by 3.15 mm thick sheet CRCA approved machine pressed, dust and vermin, weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, including with 4 \" Exhaust Fan along with air vents, Capacitor on/off indicators and Auto & Manual Selector switch for all Capacitors and cable entry with glands with all control wiring and thimbles etc, foundation /grouting on & including PCC work as per site requirement with the following :-(a) Copper bus bar250 Amp Cap- 1 Set ( Set of 4 strips), (b) MCCB 200 Amp 415V TPNwith spreader links, 36 KA-1 No,(c) 25 KVAR Capacitor Heavy Duty- 2 Nos, (d) Capacitor duty contactor MO C25 or equivalent- 2 Nos, (e) MCB 63 Amp, TP ,10 KA-2 Nos, (f) 15 KVAR Capacitor Heavy Duty- 2 Nos(g) Capacitor duty contactor MO C15or equivalent- 2 Nos , (h) MCB 32 Amp, TP ,10 KA-2 Nos,(j) 10 KVAR Capacitor Heavy Duty- 1 Nos, (k) Capacitor duty contactor MO C10 or equivalent - 1 Nos, (l) MCB 20 Amp, TP ,10 KA-1 Nos, (m) 5 KVAR Capacitor Heavy Duty- 1 Nos, (n) Capacitor duty contactor MO C5 or equivalent - 1 Nos, (o) MCB 16 Amp, TP ,10 KA-1 Nos , (m) 2 KVAR Capacitor Heavy Duty- 2 Nos, (n) Capacitor duty contactor MO C2 or equivalent - 2 Nos, (o) MCB 10 Amp, TP ,10 KA-2 Nos,(p) 1 KVAR Capacitor Heavy Duty- 1 Nos, (q) Capacitor duty contactor MO C1 or equivalent - 1 Nos (r) MCB 6 Amp, TP ,10 KA-1 Nos, (s)indicating fuse LED type R,Y,B - 03 Nos, (t) VAF meter 3 Phase-01 Nos,(u)Control MCB SPN 6 Amps -03 Nos, (v) CT Coil 200/5 Amps -03 Nos and 250/5 Amp -01 Nos, (w) APFC Relay 12 stages - 01 Nos |
| 3 | Supply & install, testing & commissioning in repairs LT APFC panel -125 KVAR compartmental out door type, Lockable fabricationmade by 3.15 mm thick sheet CRCA approved machine pressed, dust and vermin, weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, including with 4 \" Exhaust Fan along with air vents, Capacitor on/off indicators and Auto & Manual Selector switch for all Capacitors and cable entry with glands with all control wiring and thimbles etc, foundation /grouting on & including PCC work as per site requirement with the following :-(a) Copper bus bar300 Amp Cap- 1 Set ( Set of 4 strips), (b) MCCB 250 Amp 415V TPNwith spreader links, 36 KA-1 No , (c) 50 KVAR Capacitor Heavy Duty- 1 Nos, (d) Capacitor duty contactor MO C50 or equivalent - 1 Nos, (e) MCB 100 Amp, TP ,10 KA-1 Nos (f) 25 KVAR Capacitor Heavy Duty- 2 Nos (g) Capacitor duty contactor MO C25 or equivalent - 2 Nos, (h) MCB 63 Amp, TP ,10 KA-2 Nos, (j) 10 KVAR Capacitor Heavy Duty- 1 Nos, (k) Capacitor duty contactor MO C10or equivalent-1 Nos, (l) MCB 20 Amp, TP ,10 KA-1 Nos, (m) 5 KVAR Capacitor Heavy Duty- 1 Nos, (n) Capacitor duty contactor MO C5 or equivalent - 1 Nos, (o) MCB 16 Amp, TP ,10 KA-1 Nos, (p) 2 KVAR Capacitor Heavy Duty- 3 Nos (q) Capacitor duty contactor MO C2 or equivalent - 3 Nos, (r) MCB 10 Amp, TP ,10 KA-3 Nos,(s) 1 KVAR Capacitor Heavy Duty- 4 Nos, (t) Capacitor duty contactor MO C1 or equivalent - 4 Nos, (u) MCB 6 Amp, TP ,10 KA-4 Nos, (v)indicating fuse/lamp LED type R,Y,B - 03 Nos, (w) VAF meter 3 Phase-01 Nos, (x)Control MCB SPN 6 Amps -01 Nos, (y) CT Coil 250/5 Amp -04 Nos, (z) APFC Relay 12 stages - 01 Nos |
| 4 | Supply & install, testing & commissioning in repairs LT APFC panel -175 KVAR compartmental out door type, Lockable fabricationmade by 3.15 mm thick sheet CRCA approved machine pressed, dust and vermin, weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, including with 4 \" Exhaust Fan along with air vents, Capacitor on/off indicators and Auto & Manual Selector switch for all Capacitors and cable entry with glands with all control wiring and thimbles etc, foundation /grouting on & including PCC work as per site requirement with the following :-(a)Copper bus bar400 Amp Cap- 1 Set ( Set of 4 strips), (b) MCCB 315 Amp 415V TPNwith spreader links, 36 KA-1 No, (c) 50 KVAR Capacitor Heavy Duty- 1 No, (d) Capacitor duty contactor MO C50 - 1 Nos(e) MCB 63 Amp, TP ,10 KA-1 No, (f) 25 KVAR Capacitor Heavy Duty- 2 Nos, (g) Capacitor duty contactor MO C25 - 2 Nos, (h) MCB 40 Amp, TP ,10 KA-2 Nos, (j) 15 KVAR Capacitor Heavy Duty- 2 Nos (k) Capacitor duty contactor MO C 15 -2Nos, (l) MCB 32 Amp, TP ,10 KA-2 Nos, (m) 10 KVAR Capacitor Heavy Duty- 3 Nos, (n) Capacitor duty contactor MO C10 - 3 Nos, (o) MCB 20 Amp, TP ,10 KA-3 Nos, (p) 5 KVAR Capacitor Heavy Duty- 2 Nos, (q) Capacitor duty contactor MO C5 - 2 Nos, (r) MCB 16 Amp, TP ,10 KA-2 Nos, (s) 2 KVAR Capacitor Heavy Duty- 2 Nos, (t) Capacitor duty contactor MO C2 - 3 Nos,(u) MCB 10 Amp, TP ,10 KA-2 Nos, (v) 1 KVAR Capacitor Heavy Duty- 1 Nos, (w) Capacitor duty contactor MO C1 - 1 Nos, (x) MCB 6 Amp, TP ,10 KA-1 Nos, (y)indicating fuse LED type R,Y,B - 03 Nos (z) VAF meter 3 Phase-01 Nos, (aa)Control MCB SPN 6 Amps -01 Nos, (ab) CT Coil 250/5 Amp -04 Nos (ac) APFC Relay 16 Stages - 01 No |
| 5 | Material and labour for Servicing/repair LT APFC panel board by disconnection of power supply from panel, necessary welding to door hinges and fixing the sliding bolt for proper locking arrangement andmaking good all electric connection and ensuring the serviciabilityof LT APFC panel of any size incl replacement of rubber gasket and spray painting complete panel with synthetic enamel paint over a coat of red oxide incl preparation of old surface complete all as specified and directed by Engr-in-charge.Note : 1. charges for replacement of minor part viz nut bolts, thimble,insulation tape, Conrol wiringetc are included in this item.2. Major part viz MCCB, Ammeter, Voltmeter,relay,contactor , capacitor , MCBs etc will be measured and paid separately. |
| 6 | S&F in repair digital voltmeter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. |
| 7 | S&F in repair digital Ampere meter 0-200 Amps of size 96x96mm complete all as specified and directed by Engr in Charge. |
| 8 | Supply and fixing in replacement of heavy duty 50 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 9 | Supply and fixing in replacement of heavy duty 25 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 10 | Supply and fixing in replacement of heavy duty 15 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 11 | Supply and fixing in replacement of heavy duty 10 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 12 | Supply and fixing in replacement of heavy duty 5 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 13 | Supply and fixing in replacement of heavy duty 2 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 14 | Supply and fixing in replacement of heavy duty 1 KVAR Capacitor cylindrical typefixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 15 | Supply and fixing in replacement of50 KVAR Capacitor MOC50 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 16 | Supply and fixing in replacement of25 KVAR Capacitor MOC 25 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 17 | Supply and fixing in replacement of15 KVAR Capacitor MOC15 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 18 | Supply and fixing in replacement of10 KVAR Capacitor MOC10 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 19 | Supply and fixing in replacement of5 KVAR Capacitor MOC10 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 20 | Supply and fixing in replacement of2 KVAR Capacitor MOC2/3 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 21 | Supply and fixing in replacement of1 KVAR Capacitor MOC2/3 heavy duty contactor fixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 22 | Supply and fixing in replacement of MCB TP 100 Amp\"C\" Curve, 10 KA Breaking Capacityfixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 23 | Supply and fixing in replacement of MCB TP 63 Amp\"C\" Curve, 10 KA Breaking Capacityfixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 24 | Supply and fixing in replacement of MCB TP 32 Amp\"C\" Curve, 10 KA Breaking Capacityfixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 25 | Supply and fixing in replacement of MCB TP 20 Amp\"C\" Curve, 10 KA Breaking Capacityfixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 26 | Supply and fixing in replacement of MCB TP 16 Amp\"C\" Curve, 10 KA Breaking Capacityfixed in existing APFC Panel complete all as specified and directed by Engr-In-Charge. |
| 27 | S&F in replacement MCCB 4 Pole, 160 Amps, 36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. |
| 28 | S&F in replacement MCCB 4 Pole, 63 Amps, 16 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. |
| 29 | S&F in replacement MCCB 4 Pole, 250 Amps, 36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. |
| 30 | S&F in replacement MCCB 4 Pole, 400 Amps, 36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. |
| 31 | S&F in replacement MCCB 4 Pole, 200 Amps, 36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. |
| 32 | Supply and fixing in replacement of APFC Relay16 Stages in existing APFC panel suitable for connection/disconnection of capacitors in the system by sensing current and voltage. The relays shall be operable with 3 phase 415-440 volt, 50 Hz AC power supply suitable with existing APFC panel and existing CTs. The relay shall have following functions/features (a) Display parameters :- PF, Volt, current, kVAr, kVA, HZ, temperature (b) Power factor control range :- 0.3 lag to 0.3 lead (c) IP-20 protection (d) Operating temperature :- 20 degree celsius to 60 degree celsius (e) Humidity : 0 to 90% (f) Automatic detection of CT polarity (g) capacitor health check function complete all as specified and directed by Engr-In-Charge. |
| 33 | All as per srl item No 32 above, but 12 stages complete all as specified and as directed. |
| 34 | All as per srl item No 32 above, but 08 stages complete all as specified and as directed. |
| 35 | S&F in replacement current tranformer (CT) suitable for existing LT APFC panel having 200/5 Amps ratio, 10 VA burden, and class 1.0 complete all as specified and directed by Engineer in charge |
| 36 | Supply & install, testing and commissioning of factory made,CPRI approved factory made LT panel outdoor KIOSK type with double doors of suitable size provided with locking arrangements dust, weather and vermin proof 1100 volt grade, 50 Hz AC made out by 3.15 mm thick CRCA sheet steel, fully compartmentalised, with IP-65 protection all as per conforming to IS: 2417 of 1962 complete with and 50x50x5 mm thick angle iron for frame and legs, 04 Nos. legs 750 mm long 450 mm grouted in PCC blocks of type B-1 (1:2:4) with 300 mm ground clearance,for 415 volts, 3 phase, 4 wire AC supply complete all as directed with and including the following :-(a) MCCB 4 pole 415 Volt, 630 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 35 KA - 01 No (incoming), (b) MCCB 4 pole 415 Volt, 250 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 25 KA - 04 No (outgoing), (c) MCCB 4 pole 415 Volt, 125 Amps, Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 16 KA - 02 No (Outgoing),(e)Digital street light Timer Switch with contactor 40A - 01 Nos,[g] Digital Voltmeter 96 sqmm 0 - 500V with selector switch - 01 No,[h] Digital Ammeter 96 sqmm 0 - 200 Amp with CTs and selector switch - 01 No, [j] Aluminium strip bus bars with colour code PVC insulation 800 Amps capacity - 01 Set, [k] Indicators RYB - 01 Set, [l] Earthing terminals and cable glands, (m) Internal wiring of panel board with solid coductor copper cable single core of sutable size and incl 03 Nos bakelite control fuses, [n] Danger notice plate for LT with conventional skull and bones duly rivetted/pasted to the panel board door. |
| 37 | Supply & install, testing and commissioning of factory made,CPRI approved factory made LT panel outdoor KIOSK type with double doors of suitable size provided with locking arrangements dust, weather and vermin proof 1100 volt grade, 50 Hz AC made out by 3.15 mm thick CRCA sheet steel, fully compartmentalised, with IP-65 protection all as per conforming to IS: 2417 of 1962 complete with and 50x50x5 mm thick angle iron for frame and legs, 04 Nos. legs 750 mm long 450 mm grouted in PCC blocks of type B-1 (1:2:4) with 300 mm ground clearance,for 415 volts, 3 phase, 4 wire AC supply complete all as directed with and including the following :-(a) MCCB 4 pole 415 Volt, 400 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 35 KA - 01 No (incoming), (b) MCCB 4 pole 415 Volt, 200 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 25 KA - 02 No (outgoing),(c) MCCB 4 pole 415 Volt, 125 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 10 KA - 02 No (Outgoing),(c) MCCB 4 pole 415 Volt, 63 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 25 KA - 04 No (Outgoing), (e) Digital street light Timer Switch with contactor 40A - 01 Nos, [g] Digital Voltmeter 96 sqmm 0 - 500V with selector switch - 01 No, [h] Digital Ammeter 96 sqmm 0 - 200 Amp with CTs and selector switch - 01 No, [j] Aluminium strip bus bars with colour code PVC insulation 800 Amps capacity - 01 Set, [k] Indicators RYB - 01 Set, [l] Earthing terminals and cable glands, (m) Internal wiring of panel board with solid coductor copper cable single core of sutable size and incl 03 Nos bakelite control fuses,[n] Danger notice plate for LT with conventional skull and bones duly rivetted/pasted to the panel board door. |
| 38 | Supply & install, testing and commissioning of factory made,CPRI approved factory made LT panel outdoor KIOSK type with double doors of suitable size provided with locking arrangements dust, weather and vermin proof 1100 volt grade, 50 Hz AC made out by 3.15 mm thick CRCA sheet steel, fully compartmentalised, with IP-65 protection all as per conforming to IS: 2417 of 1962 complete with and 50x50x5 mm thick angle iron for frame and legs, 04 Nos. legs 750 mm long 450 mm grouted in PCC blocks of type B-1 (1:2:4) with 300 mm ground clearance,for 415 volts, 3 phase, 4 wire AC supply complete all as directed with and including the following :-(a) MCCB 4 pole 415 Volt, 400 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 35 KA - 01 No (incoming), (b) MCCB 4 pole 415 Volt, 250 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 25 KA - 03 No (outgoing), (c) MCCB 4 pole 415 Volt, 125 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 10 KA - 02 No (Outgoing),(e)Digital street light Timer Switch with contactor 40A - 01 Nos, [g] Digital Voltmeter 96 sqmm 0 - 500V with selector switch - 01 No, [h] Digital Ammeter 96 sqmm 0 - 200 Amp with CTs and selector switch - 01 No, [j] Aluminium strip bus bars with colour code PVC insulation 800 Amps capacity - 01 Set, [k] Indicators RYB - 01 Set, [l] Earthing terminals and cable glands,(m) Internal wiring of panel board with solid coductor copper cable single core of sutable size and incl 03 Nos bakelite control fuses, [n] Danger notice plate for LT with conventional skull and bones duly rivetted/pasted to the panel board door. |
| 39 | Supply & install, testing and commissioning of factory made,CPRI approved factory made LT panel outdoor KIOSK type with double doors of suitable size provided with locking arrangements dust, weather and vermin proof 1100 volt grade, 50 Hz AC made out by 3.15 mm thick CRCA sheet steel, fully compartmentalised, with IP-65 protection all as per conforming to IS: 2417 of 1962 complete with and 50x50x5 mm thick angle iron for frame and legs, 04 Nos. legs 750 mm long 450 mm grouted in PCC blocks of type B-1 (1:2:4) with 300 mm ground clearance,for 415 volts, 3 phase, 4 wire AC supply complete all as directed with and including the following :-(a) MCCB 4 pole 415 Volt, 63 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 25 KA - 01 No (incoming), (b) MCCB 4 pole 415 Volt, 40 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 16 KA - 02 No (outgoing), (c) MCB 4 pole 415 Volt, 32 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 10 KA - 02 No (Outgoing), (c) MCB 3 pole 415 Volt, 32 Amps ,Adjustable thermal and magnetic release manual drawout typesetting rupture capacity 10 KA - 04 No (Outgoing), [g] Digital Voltmeter 96 sqmm 0 - 500V with selector switch - 01 No, [h] Digital Ammeter 96 sqmm 0 - 200 Amp with CTs and selector switch - 01 No, [j] Aluminium strip bus bars with colour code PVC insulation 100 Amps capacity - 01 Set, [k] Indicators RYB - 01 Set, [l] Earthing terminals and cable glands, (m) Internal wiring of panel board with solid coductor copper cable single core of sutable size and incl 03 Nos bakelite control fuses, [n] Danger notice plate for LT with conventional skull and bones duly rivetted/pasted to the panel board door. |
| 40 | Supply & Fixingin replacement of MCCB 630 Amps, 4 pole, 415 Volts , 36KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 41 | Supply & Fixingin replacement of MCCB 400 Amps, 4 pole, 415 Volts , 36KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 42 | Supply & Fixing in replacement of MCCB 250 Amps, 4 pole, 415 Volts , 25KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 43 | Supply & Fixing in replacement of MCCB 200 Amps, 4 pole, 415 Volts , 25KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 44 | Supply & Fixing in replacement of MCCB 160 Amps, 4 pole, 415 Volts , 25KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 45 | Supply & Fixing in replacement of MCCB 100 Amps, 4 pole, 415 Volts , 25KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 46 | S & F in replacement Digital Voltmeter 0-500 volts of size 96 x 96 mm complete all as specified and directed by Engr-in-charge. |
| 47 | S & F in replacement Digital Ammeter 0-200 Amp of size 96 x 96 mm complete all as specified and directed by Engr-in-charge. |
| 48 | Material and labour for repair LT panel board by necessary welding to door hinges and fixing the sliding bolt for proper locking arrangement andmaking good all electric connection of LT panel of any size incl replacement of rubber gasket and spray painting complete panel with synthetic enamel paint over a coat of red oxide incl preparation of old surface complete all as specified and directed by Engr-in-charge.Note : 1. charges for replacement of minor part viz nut bolts, thimble etc are included in this item.2. Major part viz MCCB, Ammeter, Voltmeter etc will be measured and paid separately. |
| 49 | Supply,Laying and testingin replacement ofPVC LT Cable of size 185 Sqmm, 3.5 core, 1100 Volt grade heavy duty with PVC insulated standard aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip and over all PVC Sheathed stranded conductor conforming to IS- 7098 (Part-I) with latest amendments laid in trenches/fixed to wall/pole/laid in floor including necessary connections and suitable size of thimbling complete all as specified and as directed by Engineer-in-charge. |
| 50 | All as per srl item No 49 above, but for size 300 sqmm complete all as specified and as directed. |
| 51 | All as per srl item No 49 above, but for size 400 sqmm complete all as specified and as directed. |
| 52 | Supply & Fixing in replacement of MCCB 63 Amps, 4 pole, 415 Volts , 25KA, Ics=100% Icu Adjustable Thermal (0.8 to 1 x In) and Fixed Magnetic Release, complete all as specified and directed by the Engineer in Charge. |
| 53 | Materialand labour for Earthingcompletewithgalvanised steel earthplate electrodeof size600mm x 600mm x 6mmburieddirectly inground (earth pitnotlessthan 2.25mtrdeep belowground level)withtopedge of the plate notless than 1.5metre below normal ground level, connected to and including GI strip 32 X 6 mm(uptothe bodyof equipment) by means ofGI bolts/nuts/washers/check nuts of galvanised iron all as shown in electrical plate No.3 of SSR Part-I, Connected to equipment all as specified and testing on completion including provision of earth lead protection by 40mmbore GIlightgrade pipe and watering pipe shall be 20mmbore GI Med grade including funnel and wire mesh. Earth plateshallbesurroundedbyalternate layerofcharcoalorcokeand common salt15cmthickallaround bottom, RCCcover in 1:2:4type B1using 20mm graded crushed stone aggregate and reinfircement with8mmdia @ 100c/c/bothbays & frame, PCC (1:3:6)type C2 (using 20 mm graded crushed stone aggregate) asinearthingpitincludingnecessary excavation & earth work complete all as specfied and directed by Engr-In-ChargeNote:- Rates quoted by the tenderer shall be deemed to be included for following provisions.(i) Excavation and earth work in any type of soil including removal of surplus soil upto 100 Mtrs(ii) PCC 1:3:6 Type C-1 mix using 20 mm graded stone aggregate in pipe and 40 mm thick precast RCC 1:2:4 Type B1 using 20 mm graded stone aggregate with 8 mm dia round bars @ 75 mm c/c both ways(iii) Main earthing lead from earth electrode to equipment upto 7.5 Mtr(iv) Funnel with watering pipe GI Med Grade 20 MM Dia (ISI Marked) and lugs, charcoal and salt as required(v) GI Protection Pipe of size 40 mm dia light grade 7.5 Mtrs |