| 1 | Supply and fix in repair Air termination, single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed. |
| 2 | Supply and fix in repair Air termination, single pointed copper rod 12mm dia and 300mm long complete all as specified and directed. |
| 3 | Supply and fix Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 4 | Supply and fix in repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed. |
| 5 | Supply and fix in repair Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground, complete all as specified and directed. |
| 6 | Earthing complete with galvanised steel earth plate electrode of size 60cm X 60cm X 6.3mm buried directly in ground (earth pit not less than 2.25 metres deep below the normal ground level) with top edge of the plate not less than 1.5m below normal GL connected to GI earth strip 25 mm x 4 mm by means of GI bolts, nuts, check nuts and washers and earth strip protected by 40 mm dia GI pipe medium grade and connected to main distribution board/earthing test point all as shown on electrical plate No.3 of SSR Part I and all as specified including testing on completion.Notes: The unit rate shall also include for excavation, earth work in hard/dense soil, plain cement concrete 1:3:6 mix, Cement Earth pit and pit cover, GI funnel with watering pipe, wire mesh, protection pipe for earth lead upto 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II and also refer Plate No-03.Earth strip and protection pipe beyond 7.5m shall be measured and paid separately. Note :- Earthing will be redone if desired earth result not found during testing of the same at site., complete all as specified and directed. |
| 7 | All as per item No.6 above but by using copper plate 60×60cm ×3.15mm thick electrode and 20 × 3.15mm copper strip as earthing lead complete all as specifed and directed. |
| 8 | M&L earth continuity conductorGI of 25 x 4 mm of GI strip fixed by means of bolts, nuts, check nuts and GI washers complete all as specified and directed. |
| 9 | S&F in repair 90W energy saving and environmental friendly long life LED security street light made up of pressure die cast aluminium housing with high power LED, lens & toughened glass, potted driver and with efficacy of 120lm/W, IP 66 protection including connection with twin twisted unsheathed PVC copper cable of suitable size complete all as specified and directed.Make : Havells Cat No. ENDURASUNDOWNNXTSL90WLEDCWPASYBOPC or an equivalent model in Wipro / Philips |
| 10 | S&F in repair 120W energy saving and environmental friendly long life LED building security street light made up of pressure die cast aluminium housing with high power LED, lens & toughened glass, potted driver and with efficacy of 120lm/W, IP 66 protection including connection with twin twisted unsheathed PVC copper cable of suitable size complete all as specified and directed.Make : Havells Cat No. ENDURASUNDOWNNXTSL120WLEDCWPASYBOPC or an equivalent model in Wipro / Philips |
| 11 | S&F in repair 150W energy saving and environmental friendly long life LED Flood light made up of pressure die cast aluminium housing with high power LED, lens & toughened glass, potted driver and with efficacy of 120lm/W, IP 66 protection including connection with twin twisted unsheathed PVC copper cable of suitable size complete all as specified and directed.Make : Havells Cat No. JETALEGANZAFLS150WLED757P60DTOTG or an equivalent make in Wipro / Philips |
| 12 | Supply and fixing in repair 10W LED based Bollard lights with aluminium pipe housing with glare free PMMA diffuser, IP 65 with height of 645MM complete all as specified and directed.Make : Havells Cat No. MOUNTBL10WLED830PSYMTOPMMAM or an equivalent make in Wipro / Philips |
| 13 | S&F in repair 40W Coral LED Post Top gate light, spun aluminium landscape luminaire, IP 65 suitable for pole dia 76mm complete all as specified and directed at site.Make : Havells Cat No. RUBYGENXPT40WLED730PSYMTOPC or an equivalent make in Wipro / Philips |
| 14 | Supply and lay in trenches/fixed to walls/poles etc and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with aluminium conductor of size2 Core 10 Sqmm including taking out of existing cable all as specified and directed. Note :- Earth work excavation, sand cushioning and brick protection shall be measured and paid separately. |
| 15 | All as per item No:14 above but2 Core 16 Sqmm, complete all as specified and directed. |
| 16 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depthfor foundation, laying of poles / cable in trenches and getting out in hard/densesoil complete all as specified and as directed . |
| 17 | Returning, filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick complete all as directed by Engineer-in-Charge. |
| 18 | Removal of surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above from the starting point complete all as specified and directed. |
| 19 | Supply and spread approved dry river sand / M sandforcushioning of cable laid in trenches including watering and consolidation, complete all as specified and directed.Note:- Punned thickness of sand cushioning shall only measured for payment purpose. |
| 20 | M&L for brick, sub class \"B\", old size, laid in trenches as cable protection covers, complete allas specified and directed. |
| 21 | S&F Hot press moulded SMC Junction box of size 240 mm x 130 mm x 95 mmwith right openable hinged doorwith two number aluminium bus bars mounted on porcelain insulator including clamps of MS flat iron 25 x 3 mm with bolts and nuts including taking down old juction box, complete all as specified and directed.Make : Sintex Cat No. GSJB-2817 or equivalent make. |
| 22 | S & F ofnature switch pole mounted encloser consisting of NATURE SWITCH-02, power contactor for load switching, MCB, and terminal blocks. The enclosurecomplete with mounting brackets, cable glands, openable door with lock and key. The enclosure is made of UV stabilized, FR grade special moulding compound to provide a rust proof, electric shock proof, termite proof, outdoor mountable electrically insulating body capable of enduring solar radiation in the outdoor. Selectable options are available for duration based switching OFFsuitable for single phase operation of 02 KW load, 230 Volts, 50 Hz, AC , with all connected accessories, including taking down existing timer switch of any description, complete all asspecified and directed. |
| 23 | S&F Steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts, screwsas specified type 410 SP-31 (9.00 metre long)including two coats of bituminous paint internally and externally for the portion embedded in concrete and two coats of aluminium paint over one coat of red oxide primer to external/ exposed surfaces, including taking down existing pole of any description, complete all as specified and directed. Note: (i) Rate quoted by the contractor shall deemed to includes excavation and earth work, 150mm thick PCC (1:3:6) type C2 (using 40mm graded stone aggregate) below ploe and filled in trench aleound the pole including coping up to 20cm above ground using PCC (1:2:4) type B1 with rquired formwork complete.(iii) Rate quoted by the contractor shall alsodeemed to include fortaking down carefully the exisitng unserviceablepole, serviceable street light fitting and ACSR conductor including connecting accessories and refixing the same after replacing the new pole with all necessary accessories complete all as specified and directed. |
| 24 | S&Fbracket made out of 40 mm dia GI pipe, light grade, 1.5m long, bend to shape including clamps, nuts and bolts etc and required electrical connections including taking out old unserviceable brackets of any descriptionallas specified and directed . |
| 25 | S&Fbracket made out of 50 mm dia GI pipe, light grade, 1.5m long, bend to shape including clamps, nuts and bolts etc and required electrical connections including taking out old unserviceable brackets of any descriptionallas specified and directed . |
| 26 | S&F PVC insulated and FR PVC round sheathed, copper conductor, flexible industrial cable, 1100Volts, 1.5 Sqmm 2 core for connection from junction box to streetl ight fitting complete all as specified and directed. |
| 27 | M&L for cleaning thoroughly the street light poles/LT distribution poles of any height and any description (Maximum 9 Mtr long ) with necessary cleaning agent including complete removal of existing paint by scrapping etc carefully and applying two coat of synthetic aluminium paint over a coat red oxide primer complete all as specified and directed . |
| 28 | Cutting & trimming of tree branches any girth and sizetouching to overhead lines and clearing the distance 1.5 mtr both sides of overhead line with in a gap of span 35 mtrs each and removing the samecleaning the site all as specified and directed. |
| 29 | S&F PVC conduit suitable for 20mm on pole(steel pole/ concrete pole) from juction box to street light fitting for PVC wire complete all as specified and directed. |
| 30 | S&F PVC flexible conduit (size 20mm ) on pole from juction box to PVC conduit& PVC conduit to streetlight fitting complete all as specified and directed. |
| 31 | Supply & Laying 40mm bore GI tubing, light grade, with all fittigs of following sizes for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as specified and directed. |
| 32 | S&F Driver circuit board 48W with necessary wiring including taking down exisitng driver circuit board from street light pole of any make, complete all as specified and directed. |
| 33 | S&F Driver circuit board 60W Model with necessary wiring including taking down exisitng driver circuit board from street light pole of any make, complete all as specified and directed. |
| 34 | S&F Driver circuit board 90 W to 120 W with necessary wiring including taking down exisitng driver circuit board from street light pole of any make, complete all as specified and directed. |
| 35 | Supply, fabricating, installation, testing and commissioning of back-lit signage including embedding the signage baord firmly with the wall/ MS Angle frame/as per approved Art work and nomenclature as given below :- (a)Box with frame :- 25 x 25 mm square pipe (18 G) frame with cross supports @ spacing not exceeding 1.0 m on the box length including 20 mm x 20 mm MS Square pipe (18 G) stifferenrs duly white enamel painted in 2 coats over a coat of zinc oxide iron primer, depth of box should not be less than 165 mm.(b)Side, Top, Back and bottom Panels :- Made out of 24 gauge chemically treated GI Sheets duly precoated / powder coated with white MATT finish coating on both inner and outer surface. Top panel to have 24 guage precoated drip cap (fixed with pop rivet or machine moulded to shape) of 25 mm on front and side to prevent damages due to rain etc.The bottom panel should be provided with access door fixed with ss screws and suitable housing for LED drivers.(c)LED Module :-LED 12V Module beam angle >=150 degrees with IP rating >= 64, 0.72 W/70 Lumens per module of 3 LEDs with 7000 to 8000 K colour temperature, Make : Tridonic/ Osram / Cree / GE(d)LED configuration :- 29 LED Modules per Sq mt (Equal division on spacing based on height of box) and one module every 0.20 m on running length of box.(e)LED power supply :-Input 230 V AC, power supply should be CPCC (Constant power constant current) of 30W/60W/120 W each.(f)Graphics :-Graphics shall be computer plotter cut with translucent cast vinyl matching the colour specification of the installation |
| 36 | Material and labor for LED signage visible from both side of size not less than 300 x 200 mm made out of sandwiched transparent acrylic sheet (minimum 6 mm thick) and necessary computerized laser cutting for letters/ signs illuminated with LED light 8 watt, 12 volt of approved color along with necessary driver and twin core PVC insulated and sheathed multistrande copper conductor 1.5 sq mm up to 1.0 miter for connection including fixing arrangement to wall or ceiling including taking down of old signage all as specified and as directed.[Note: - The letters or symbols or signs will be engraved as per direction and a sample printed on plain paper as per actual size should be got approved from and all as specified and directed . |
| 37 | All as per Item No 36 here-in-before but of size not less than 600 x 200 mm with LED light 12 watt, 12 volt all as specified anddirected. |
| 38 | Material and labour for fabrication of MS angle iron, joist, channel Square hallow Pipe frame work for LED sign boards of gates, Pump Houses, Electrical Installatiions etc at any indicated situation all as specified anddirected. |
| 39 | Material and labour for aluminum anodized equal angle of size not less than 22 x 38 x 1.5 mm thick fixed to corners of front side of glow sign boards for fixing of Vinyl sheet / acrylic sheet or existing sheets of any description including fixing with GI machine screw complete all as specified and directed.Make : JINDAL/NIZAN/SAIL/TATA |
| 40 | Material and labor for replacement of plain galvanized iron sheet 0.32 mm thick zinc coated both side and making glow sign board including necessary turning up for corners etc and necessary decoration as per site requirement andall as specified and directed .Make : JINDAL/NIZAN/SAIL/TATA |