| 1 | Excavation in trenches n. exc 1.5 m wide for foundations, laying cables/ pipes etc. not exceeding 1.5 m deep and getting out in SOFT/LOOSE soil complete, all as specified |
| 2 | Excavation in trenches n. exc 1.5 m wide for foundations, laying cables/ pipes etc.exceeding 1.5 m deepbut not exceeding 3.0 m deepnd getting out in SOFT/LOOSE soil complete, all as specified |
| 3 | Returning filling in including spreading, levelling, watering and well ramming in layers notexceeding 25cm thick complete, all as specified. |
| 4 | Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete, all as specified. |
| 5 | Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified.NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment. |
| 6 | Brick protection with old size sub class \"B\" bricks laid flat across the route of underground cable all as specified and directed |
| 7 | Plain cement concrete (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly complete all as specified. |
| 8 | Plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly complete all as specified. |
| 9 | Plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregateas in coping to poles poles,bases of out door panel boards etc., including ncessary form workwith fair finishing surface of concrete complete, all as specified. |
| 10 | Plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregateas in coping to poles poles,bases of out door panel boards etc., including ncessary form workwith fair finishing surface of concrete complete, all as specified. |
| 11 | Cutting the existing road / PCC surface straight by manual, depth and width not less than 1 meter below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 type B-1 using 20mm graded stone aggregatecomplete, all as specified. |
| 12 | Road / drain crossing by adopting trench lesstunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock including HDPE/GI pipe medium duty duty of size 80mm dia in any length including jointing materials to carry LT UG cables of size upt 95 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as speceified and as directed. |
| 13 | GI pipe light grade with all fittings fixed as termination postal ,fixed to poles/ walls/ under floors/ under road etc including taking down existing pipecomplete all as specified of following size: - |
| 14 | 40mmbore |
| 15 | 50mm bore |
| 16 | PVC insulated & sheathed stranded FRLSH copper conductor twin core cable 1100 Volts of size 1.5 sq. mm ( nominal area)conforming to IS 694for making connection from junction box to light fittings including taking down existing cable complete all as specified. |
| 17 | PVC insulated unsheathed/ sheathed cable with stranded Aluminium Conductor 1100 Volts grade, flat twin core service cable conforming to IS:694/1990 with latest amendments ISI including disconnecting/ taking out existing service cable complete all as specified offollowing size: - |
| 18 | 2.5 Sqmm |
| 19 | 4 Sqmm |
| 20 | Supply, laying, jointing & testing of LT XLPE insulated cable screened,bedded, galvanised steel strip or wire armourd cable(heavy duty) 1100 volt gradewith aluminium conductor conforming to IS-7098 (Part-I -1988)laid in trenches/ ducts/ through pipes/ in floors / underroads/ hard standing /along poles and testing including taking down existing cablecomplete all as specified of sectional area: - |
| 21 | 10 Sq.mm, 2 core |
| 22 | 10 Sq.mm, 4 core |
| 23 | 16 Sq.mm,4 core |
| 24 | 25 Sq.mm,4 core |
| 25 | Taking out and relaying of LT cable after carrying out necessary repair such as joining with Epoxy joint and laid with sand cushioning and brick protection and making connection by using Lugs as as specified and directed by Engg-in-Charge of following size:-Note - Earth work, sand cushioning, brick protection, LT Joints shall be measured and paid seperately unde respective item of BoQ |
| 26 | 10 to 50 Sq.mm, 2 to 4 core |
| 27 | 70 to 150 Sq.mm, 3.5 core |
| 28 | Cable joining kit (straight through heat shrinkable) for 1100 V (Earthed) grade cablecomplete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable including taking down unserviceable termination complete all as specified offollowing size: - |
| 29 | 10 to 50 Sq.mm, 2 to 4 core |
| 30 | 70 to 95 Sq.mm, 3.5 core |
| 31 | Cable joining kit (outdoor end termination heat shrinkable) for 1100 V (Earthed) grade cablecomplete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable including taking down unserviceable termination complete all as specified offollowing size: - |
| 32 | 16 to 50 Sq.mm, 3.5 core |
| 33 | 70 to 95 Sq.mm, 3.5 core |
| 34 | Steel tubular 9 metre long swaged pole type 410 SP-31 complete with cast iron base plate of size 300mm x 300mm x 6mm, final taper plug, bolts, nuts & screwsand painting the pole with two coats of aluminum paint over a coat of primer including black and yellow strips 30cm each upto 1.5 metre from top of PCC foundation block and numbering of poles in 80mm high white letter using synthetic enamel paint over baseetc including taking down old existing pole complete all as specified.Note - Excavation, earth work, PCC in foundation and coping shall be measured and paid seperately under relevant item of this schedule. |
| 35 | Cross arm bracing support, clampand back plate from structural steel section including nuts & bolts washer, welding, bending, cold or hot drilling holes for bolts in any shape or size as indicated or as directed and including of one coat primer, one under coat and one finishing coat of aluminium paint for maing clamp to be used for fixing of flood light/ street light on pole complete, all as specified. |
| 36 | Dismantling LT steel tubular pole of any heigh by taking out form PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40 mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I - 2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engg-in-Charge |
| 37 | Automatic Street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is <30 Lux and for switching off> 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor alongwith suitable power contactor incoming outoging MCBs SP and an automanual (sensor bypass selection option should be enclosed in a pole/ wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 8 KW with circuit wiring min 10Sqmm copper wire 63 Amps contactor ans suitable MCBs at both positions at incoming and outgoing of breaking capacity 10KA complete including necessary clamp (2 sets) /anchor bolt (4 Nos)for fixing on pole/ wall including taking down existing switch complete all as directed. |
| 38 | Automatic Street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is <30 Lux and for switching off> 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor alongwith suitable power contactor incoming outoging MCBs SP and an automanual (sensor bypass selection option should be enclosed in a pole/ wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 12 KW with circuit wiring min 10Sqmm 3nos contactor each of 40-50 amps, incoming outgoing MCB (3 Nos) rating 40 amps of breaking capacity 10KA complete including necessary clamp (2 sets) /anchor bolt (4 Nos)for fixing on pole/ wall including taking down existing switch complete all as directed. |
| 39 | Painting the existing LT steel pole of 9.0 mtr Long incluidng cross arms, clamps, street light junction box etc with 1 coats of aluminium paint including throughly cleaning the existing surface, writing of pole numbers in yellow circule 15cm with black paint on poles. Painting the pole upto 1.5 Mtr height with alternate bands 30 cm height (3Nos black and 2 Nos Yellow) from ground level complete all as specified and directed |
| 40 | Security light bracket made of 40 mm bore GI light grade pipe 1.5 metre long bend to shape including necessary weldingand fixed to pole with suitable size of flat iron clamps, nuts, bolts and washers etc. IN REPLACEMENT, complete all as specified . |
| 41 | Hot press moulded SMC junction/terminal box of size with internal dimensions of 300x200x105 mm with hinged door, incl provision of 2 way connector 415 Volts made out of ploycarbonate or bakelite and 1 No MCB of 6Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/glands, fixed on ple by means of clamps made out of MS Flat iron of size 25mm x3mm 2 Set including dismantling of old unserviceable all as speceified and as directed. |
| 42 | LED street light 70/72 watt, outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W IP 66 protection and impact resistance of IK08, IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE UL 72W IP66 LXN G1or equivalent make mentioned in Appendix \"B\". |
| 43 | LED street light90 watt outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W, IP 66 protection IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE UL 90W IP66 LXN G1 or equivalent make mentioned in Appendix \"B\".. |
| 44 | LED street light100 watt outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W, IP 66 protection IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE UL 100W IP66 LXN G1 or equivalent make mentioned in Appendix \"B\". |
| 45 | LED street light120 watt outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W, IP 66 protection IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE UL 120W IP66 LXN G1 or equivalent make mentioned in Appendix \"B\". |
| 46 | LED street light150 watt outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W, IP 66 protection IN REPLACEMENT and making connections, complete.MAKE:Surya Cat part no. SLE UL 150W IP66 PLX G1 or equivalent make mentioned in Appendix \"B\". |
| 47 | LED street light200 watt outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 120 LM/W, IP 66 protection IN REPLACEMENT and making connections, complete.MAKE:Surya Cat part no. SLE UL 200W IP66 PLX G1 or equivalent make mentioned in Appendix \"B\". |
| 48 | LED flood light 120 watt suitable for 11 metre hight high mast , outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 110 LM/W IP 66 protection IN REPLACEMENT and making connections, complete.MAKE:Surya Cat part no. SLE FL 120W IP66 LMS NEO-N or equivalent make mentioned in Appendix \"B\". |
| 49 | LED flood light150 watt suitable for 11 metre hight high mast , outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 110 LM/W IP 66 protection IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE FL 150W IP66 LMS NEO- N or equivalent make mentioned in Appendix \"B\". |
| 50 | LED flood light200 watt suitable for 11 metre hight high mast , outdoor type pressure die cast aluminium housing, heat resistant toughtened glass with frame and lamp with minimum efficiency 110 LM/W IP 66 protection IN REPLACEMENT and making connections, complete.MAKE: Surya Cat part no. SLE FL 200W IP66 LMS NEO-N or equivalent make mentioned in Appendix \"B\". |
| 51 | LED Post top light fitting in spherical shape Lantern made up of die-cast aluminium housing with glare free optically designed PC diffuser , LED 40 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with direiver and lamp, IN REPLACEMENT, all as specified and directed.MAKE: Surya Cat part no. ETPP SLE PT 40W or equivalent make mentioned in Appendix \"B\". |
| 52 | LED 10W bollard in IP 66 to ensure sustainable performance in all sections and aesthetics, lumen output should not be less than 90 lumens per watt with & including PCC type B-1 (1:2:4) base of size not less than 300 mm dia and 500 mm depth (minimum) & necessary earthwork, IN REPLACEMENT, all as specified and directed.MAKE:Surya Cat part no..GLZ SLE BL 10W 1000 NX E or equivalent in makes mentioned in Appendix \"B\" here-in-after |
| 53 | MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, \"C\" curve type of rating6 to 32 Amp, IN REPLACEMENT,complete all as specified and directed. |
| 54 | MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, \"C\" curve type of rating 6 to 32Amp, IN REPLACEMENT,complete all as specified and directed. |
| 55 | MCB suitable for 415 volt AC supply, TPN with over load and short circuit protection and rupturing capacity not less than 6 kA, \"C\" curve type of rating 10-63 Amp, IN REPLACEMENT,complete all as specified and directed. |
| 56 | Lantren of dia 60cm for fixing of flood light, cap type to be fixed on the top of 9 m SP-31 / 11 m SP-55 steel pole made of MS pipe medium grade dia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50x6 mm 8 nos including two coat of aluminium painting over a coat of red oxide primer complete all as directed. |
| 57 | Dismantling of damage / broken coping of PCC /Steel pole of any size and removing the the debries from site complete all as specified and directed. |
| 58 | LT Feeder pillar Box factory made CPRI approved panel, weather, dust & vermin proof outdoor cubical compartmental type, double door, front and back side openable, with providing rubber/PVC gasket of suitable size all sides of door, with copper busbar wrapped with pvc tape/sleeves with maintained the colour code and copper strip busbar of suitable rating to MCCB input andMCCB output of suitable length, made out of 3.15 mm thick mild steel CRCA sheet with 50x50x6mm size angle iron supporting frame including applying two cats of Powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing/incoming including PCC foundation in cement concrete 1:3:6 using 20mm graded stone aggregate, including taking down existingLT panel complete all as directed and specified installation, commissioning and testing and comprising of the following fitment accessories:-(a) Aluminium bas bar 200 amps - 04 nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutralb) MCCB 100 Amps , 415 Volt, 16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar as INCOMING - 01 NosNote - All internal connection between MCCB and Bus Bar shall be connected by aluminium strip of suitable size and capacity.(ii) All MCCB to be connected with both side spreader link. |
| 59 | Earthing to panel with galvanised steel plate electrode 600 mm x 600 mm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal groung level) with top edge of earth lead wire 4.0 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES Schedule pt-I 2009, protected by 15 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mmbore GI light grade pipe for watering and including funnel, wire mesh, RCC cover, reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steel handle 12 mm dia, using round bar, PGI funnel with wire mess & frame, PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, all as specified & shown in electrical plate No. 3 of MES Schedule Part – I.IN REPLACEMENT, complete all as specified. Note:- (i)PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate.(iii) Earth resstance shall be less than 3 ohm. In case the test results are not found less than 3 ohm, complete earthing shall be redone by the contractor without any extra cost to Govt. |