| Sl. No. | Item Description |
| 1 | Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables, foundation filling of poles or stays and for rerouting of cables complete all as specified and directed. |
| 2 | Returning filling, including spreading, leveling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed. |
| 3 | Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | M&L for Sub class ‘B’ bricks old size laid dry flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed. |
| 5 | M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying stretching and testing the cable complete all as specified and directed.Note:- Punned thickness shall be measured and paid. |
| 6 | M&L for Boring/ drilling manully of holes under road, pavement, hard standing or by trenchless technology using ultra sounding technique and necessary machine/ tools upto 100 dia complete all as specified and directed. |
| 7 | Supply and Lay in replacment cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 16 Sqmm 4 core complete all as specified and directed. |
| 8 | All as per item No. 07 above but of size 25 Sqmm 3.5 core complete all as specified and directed. |
| 9 | All as per item No. 07 above but of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 10 | All as per item No. 07 above but of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 11 | All as per item No. 07 above but of size 70 Sqmm 3.5 core complete all as specified and directed. |
| 12 | All as per item No. 07 above but of size 95 Sqmm 3.5 core complete all as specified and directed. |
| 13 | All as per item No. 07 above but of size 120 Sqmm 3.5 core complete all as specified and directed. |
| 14 | All as per item No. 07 above but of size 185 Sqmm 3.5 core complete all as specified and directed. |
| 15 | All as per item No. 07 above but of size 240 Sqmm 3.5 core complete all as specified and directed. |
| 16 | Supply and fixing of HDPE double wall corrugated (DWC) electric pipes of size 40 mm dia of 6 mtrs length each, manufactured using HDPE polymer having a smooth/plain internal surface & currugated external surface having with greater stiffness withstand soil movement & take higher loads (static & dynamic) incuding connecting rings made of HDPE DWC suitable for 40 mm pipes, to pass through LT cable complete all as specified and directed. Make Astral/SFMC/ KPT |
| 17 | All as per item No 16 above but of size 50 mm dia complete all as specified and directed. |
| 18 | All as per item No 16 above but of size 63 mm dia complete all as specified and directed. |
| 19 | All as per item No 16 above but of size 75 mm dia complete all as specified and directed. |
| 20 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 10 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 21 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 16 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 22 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 25 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 23 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 35 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 24 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 50 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 25 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 70 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 26 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 95 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 27 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 120 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 28 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 150 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 29 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 185 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 30 | Supply and fix in replacmentof aluminium Lugs/ thimble for LT cable 240 Sqmm including removing of insulation of cablefor the size of thimble base, inserting the conductor inside thimble & crimping properly complete all as specified and directed. |
| 31 | Supply and fix in replacmentof aluminium ferrule for LT cable 10 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 32 | Supply and fix in replacmentof aluminium ferrule for LT cable 16 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 33 | Supply and fix in replacmentof aluminium ferrule for LT cable 25 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 34 | Supply and fix in replacmentof aluminium ferrule for LT cable 35 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 35 | Supply and fix in replacmentof aluminium ferrule for LT cable 50 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 36 | Supply and fix in replacmentof aluminium ferrule for LT cable 70 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 37 | Supply and fix in replacmentof aluminium ferrule for LT cable 95 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 38 | Supply and fix in replacmentof aluminium ferrule for LT cable 120 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 39 | Supply and fix in replacmentof aluminium ferrule for LT cable 150 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 40 | Supply and fix in replacmentof aluminium ferrule for LT cable 185 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 41 | Supply and fix in replacmentof aluminium ferrule for LT cable 240 Sqmm including removing of insulation of cablefor the size of thimble, inserting the conductor both side for joining the LT cable& crimping properly complete all as specified and directed. |
| 42 | Supply & fixing in replacment of double compression glands of brass matel suitable for 10 sqmm LT cable 4 core with weatherproof, duly nickel plated complete all as specified and directed. |
| 43 | Supply & fixing in replacment of double compression glands of brass matel suitable for 16 sqmm LT cable 4 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 44 | Supply & fixing in replacment of double compression glands of brass matel suitable for 25 sqmm LT cable 3.5 core with weatherproof, duly nickel plated complete all as specified and directed. |
| 45 | Supply & fixing in replacment of double compression glands of brass matel suitable for 35 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 46 | Supply & fixing in replacment of double compression glands of brass matel suitable for 50 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 47 | Supply & fixing in replacment of double compression glands of brass matel suitable for 70 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 48 | Supply & fixing in replacment of double compression glands of brass matel suitable for 95 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 49 | Supply & fixing in replacment of double compression glands of brass matel suitable for 120 sqmm LT cable 3.5 core with weatherproof, duly nickel plated complete all as specified and directed. |
| 50 | Supply & fixing in replacment of double compression glands of brass matel suitable for 150 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 51 | Supply & fixing in replacment of double compression glands of brass matel suitable for 185 sqmm LT cable 3.5 core with weatherproof, duly nickel plated complete all as specified and directed. |
| 52 | Supply & fixing in replacment of double compression glands of brass matel suitable for 240 sqmm LT cable 3.5 core with weatherproof,duly nickel plated complete all as specified and directed. |
| 53 | Supply and laying RCC cable route indicator rectangular in shape providing cured shape on top, dimension not less then 250x150 mm at bottom below GL, 200x150 mm above GL & total height not less than 1250 mm fabricated in cement concrete (1:2:4) coloured yellow & mentioning cable size/ voltage & location in black colour, has to be engraved complete all as specified and directed. |
| 54 | S&F in replacment of cable jointing kit for 1100 volt grade cable for outdoor/ indoor termination stright through joint heat shrinkable type complete with jointing material and accessories suitable for XLPE armed aluminium conductor cable of size 25 to 50 sqmm 3.5 core complete all as specified and directed. |
| 55 | All as per item No 54 above but for cable 70-120 sqmm 3.5 core complete all as specified & directed. |
| 56 | All as per item No 54 above but for cable 150-185 sqmm 3.5 core complete all as specified & directed. |
| 57 | All as per item No 54 above but for cable 240-300 sqmm 3.5 core complete all as specified & directed. |
| 58 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 63 Amps with breaking capacity 25 KA complete all as specified and directed. Make:- Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270 |
| 59 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 100 Amps with breaking capacity 25 KA,complete all as specified and directed. Make:- Havels Cat Part No - IHA13DB40100 or L&T/K Cat Part No - CM91712OOKOOG or Indoasian Cat Part No - 830272 |
| 60 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 125 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havels Cat Part No -IHA13DB40125 or L&T/K Cat Part No -CM90642OOLO or Indoasian Cat Part No - 830273 |
| 61 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 160 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havels Cat Part No - IHA13DB40160 or L&T/K Cat Part No - CM90642OOMO or Indoasian Cat Part No - 830295 |
| 62 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 200 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havells Cat Part No - IHLLSEB40200 orL&T/K Cat Part No -CM90642OONOor Indoasian Cat Part No -830296. |
| 63 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 250 Amps with breaking capacity 36 KA, complete all as specified and directed. Make:- Havells Cat Part No -IHLLSEB40250 orL&T/K Cat Part No - CM92109OOP1OGor Indoasian Cat Part No -830336. |
| 64 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 400 Amps with breaking capacity 36 KA, complete all as specified and directed. Make:- Havells Cat Part No - IHLLSEB40400 orL&T/K Cat Part No - CM98403OOROOG or Indoasian Cat Part No -830396. |
| 65 | S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 630 Amps with breaking capacity 36 KA, complete all as specified and directed. Make:- Havells Cat Part No -IHLLSEB40630 orL&T/K Cat Part No - CM94106OOT1OG or Indoasian Cat Part No -830398. |
| 66 | S&F in repairMCCB3 pole 415V, Adjustable thermal and fixed magnetic type of capacity 100 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havels Cat Part No - IHA13DB30100 or L&T/K Cat Part No - CM91612OOKOOG or Indoasian Cat Part No - 840038 |
| 67 | S&F in repairMCCB3 pole 415V, Adjustable thermal and fixed magnetic type of capacity 160 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havels Cat Part No - IHA13DB30160 or L&T/K Cat Part No - CM90642OOMO or Indoasian Cat Part No - 840100 |
| 68 | S&F in repairMCCB3 pole 415V, Adjustable thermal and fixed magnetic type of capacity 200 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havells Cat Part No -IHLLSEB30200 orL&T/K Cat Part No -CM90638OONOor Indoasian Cat Part No -840101. |
| 69 | S&F in repairMCCB3 pole 415V, Adjustable thermal and fixed magnetic type of capacity 250 Amps with breaking capacity 25 KA, complete all as specified and directed. Make:- Havells Cat Part No - IHLLSEB30250 orL&T/K Cat Part No - CM90638OOPOor Indoasian Cat Part No -840102. |
| 70 | Supply and fixing in replacement MCB TPN 40 amps 415 V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 71 | Supply and fixing in replacement MCB TPN 63 amps 415 V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 72 | Supply and fixing in replacementMCB SPN 32-40 amps 230V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 73 | Supply and fixing in replacementMCB SPN 63 amps 230V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 74 | Supply and fixing in replacement MCB SP 6-16 amps 230V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 75 | Supply and fixing in replacement MCB SP 20-32 amps 230V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 76 | Supply and fixing in replacement MCB TP 40 amps 415 V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 77 | Supply and fixing in replacement MCB TP63 amps 415 V \"C\" curve with rupturing capacity 10 KA complete all as specified and directed. |
| 78 | Supply and fixing in replacment of sheet metal enclosures for MCCBs of capacity 63 amps 4 pole suitable for MCCB of item No 58 above complete all as specified and directed. |
| 79 | Supply and fixing in replacment of sheet metal enclosures for MCCBs of capacity 100 amps 4 pole suitable for MCCB of item No 59 above complete all as specified and directed. |
| 80 | Supply and fixing in replacment of sheet metal enclosures for MCCBs of capacity 160 amps 4 pole suitable for MCCB of item No 61 above complete all as specified and directed. |
| 81 | Supply and fixing in replacment of sheet metal enclosures for MCCBs of capacity 200 amps 4 pole suitable for MCCB of item No 62 above complete all as specified and directed. Note for item no 78 to 80 make of MCCBs enclosure must be of same make MCCB provided in Ser item No 58, 59, 61& 62. |
| 82 | Supply and fixing in replacement of off load change over switch in sheet metal enclosure 4 poles, 400 Amp rated, 440 volts, 50 Hzs, confirming to IEC 60947-3, IS/IEC 60947-3alongwith extendable handle with making all connection and fixing accessories on surface of wall/panel operating handle etc complete all as specified and directed. |
| 83 | Supply and fixing in replacement of off load change over switch in sheet metal enclosure 4 poles, 200 Amp rated, 440 volts, 50 Hzs, confirming to IEC 60947-3, IS/IEC 60947-3alongwith extendable handle with making all connection and fixing accessories on surface of wall/panel operating handle etc complete all as specified and directed. |
| 84 | Supply , installation, testing and commissioning of power factor improvement panel of capacity 125 KVAR size of panel 1175 mm x 800 mm x 540 mm, fully type test according to IEC 61921 including interconnection with LT panel with appropriate size of electric cable for Main panel,factory made, weather proof , dust and vermin proof (IP 65) suitable forHumidity: up to 95%,Average daily temperature: +35°C max, Ambient temperature: -5°C to 45°C, 1100 V/660 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 14 SWG MS sheet welded on 40 x 40 x 3 mm angle iron frame / base of appropriate size and having four Nos angle ironlegs made out of 40 x 40 x 6mm 60 cm long angle iron below frame with front door and back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles , all as specified and directed by Engr-in-Charge and all other electric incoming and outgoing connections with PVC insulated multi stranded flexible copperNYVIN cable of suitable size and PVC flexible conduit medium quality as required , comprising of the following:- |
| 85 | (a) Insulated Bus bar of aluminium of 250 Amps capacity for three phase, fixed on insulators, Busbar should be PVC sleeved with Red, Yellow & Blue Colour, Bus bar support should be of SMC/DMC, Rated Impulse Withstand Voltage 8KV -01 Set(b) Incommer MCCB 250 Amp, three pole, short circuit breaking capacity 25 KA Icu at 415 V (KA rms) Ics =100% ,IEC 60947-2 Adjustable thermal and fixed magnetic setting ,frame LS type,Front Face,Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.Make:- Schneider/ Siemens / ABB/L&T/Havells -1 No.(c) Capacitor 125 KVAR (01 X 50 KVAR + 02 X 25 KVAR + 01 X 10 KVAR + 02 X 5 KVAR + 01 X 3 KVAR + 01 X 2 KVAR), square type capacitor heavy duty rated, capacitor bankof rated 440 volt , 3 phase, Maximum over current: 1.8 In,Overpressure protection,Discharge resistance 50 V - 1 min, Capacitance Tolerance -5%, +10%,Maximum permissible over current(with thermal protection included)1.43 In ,Maximum permissible over voltage 1.1 x Un, 8 h every 24 h,of rated 440 volt with detuned Reactor of de-tuning factor (P) 7% and suitable output of 125 KVAR at 440 volt suitable output , Overheating protection by thermostatconfirming toIS-13340-1993/, 13341-1992 & IEC -60831-1+2. .Make:- Schneider/ Siemens / ABB/L&T/Havells(d) Intelligent Power factor controller relay 8 steps, seven segment LED Display, Augiliary power factor, Algotitham, Dual password protection 4 digit display, Alarm Indication on Display switching time programmable IS to 1809, 90V - 550V 50/60Hz 1A/5A with RS485 Make:- Schneider/ Siemens / ABB/L&T/Havells-01 No(e) SPMCB 6 to 32 Amps C-Curve with rupturing capacity 10 KA Control Circuit, .Make:- Schneider/ Siemens / ABB/L&T/Havells(f) CT 250/5A , 10 V.A,CL:1.0,Resin Cast ,CT Secondary wire Size should be 2.5 Sq mm.Make : Kalpa /AE/ L&T/Kappa -03 Nos |
| 86 | (g)Accessories for 125 KVAR capacitor Bank :-(i)Capacitor Duty Contactor (01 X 50 KVAR + 02 X 25 KVAR + 01 X 10 KVAR + 02 X 5 KVAR + 01 X 3 KVAR + 01 X 2 KVAR) 440 volt with damping resistors which limit inrush Current, 440 volt ,3ph,50 Hz, Coil-220 Vac, .Make:- Schneider/ Siemens / ABB/L&T/Havells(ii) MCB TPN 10 Amp, with rupturing capacity 10 KA, 240 Volt(iii) MCB TPN 16 to 25 Amp, with rupturing capacity 10 KA, 240 Volt(iv)Digital Voltmeter of size 96x96mm (0-500V) with built in selector switch.(v)Digital Ammeter of size 96x96mm (0-400A) with built in selector switch. (vi)Indication lamp 22.5mm dia LED type 240volts AC to show three phase availability-01Set.(h) Ventilating fans of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending upon the temperature of the Panel. 230 V AC, 2650 rpm,160 Cu.m/h, Flying leads - 04 Nos (j) All accessories prewired with suitable size copper conductor cable insulated with fibre glass insulation to with stand high temperature, housed in cubical panel (CPRI approved) made out of 3.15 mm thick MS sheet factory made as per IEC 62208 duly powder coated front and rear door open able with locking arrangement complete with,IK 10 protection against mechanical Shocks as per IEC 62262 foundation as required or recommended by manufacturer. Make of APFC Panel Note: APFC Panel shall be manufacturedby original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf and the panels so manufactured will not be accepted. |
| 87 | Supply, install, testing and commissioning LT cubical Panel of outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangementboth in front and rear side(independent door for each item on front side) mounted on 4 Nos angle iron 50x50x6 mm, 60 cm long embedded in PCC 1:3:6 type C2 with aluminium bus bar ofrating 1.5 times of incomer MCCB rated capacity, IP 65 protection, provision of holes at the bottom of panelto pass through cable with cable gland for incomming and outgoing cables with lugs and connections, sealed completely to avoid foreign particals entry into the panel,etc required nuts ,bolts and washer incl provision of lugs for cable terminationof 16 to 240 sqmm cable with MCCBs & control wiring with suitable size PVC copper conductor cable etc. Including provision of following accessories/eqpt incl cable gland etc and suitable for fixing of under mentioned items:- |
| 88 | Incoming(a) MCCB Adjustable thermal and fixed magnetic 4Pole 160 A 25 KA -No.01Make Havels Cat Part No - IHA13DB40160 or L&T/K Cat Part No - CM90642OOMO or Indoasian Cat Part No - 830295(b) Digital Voltmeter 0 to 500 Volt -01 No(c) Digital Ammeter 0 to 400 Amps with CTs and selector switch - 01 set(d) LED Phase Indication lamp (RYB) -01 Set(e) Cable gland double compression type weratherproof for 120 Sqmm 01 Nos Outgoing(a) MCCB Adjustable thermal and fixed magnetic 4Pole 63 A 25 KA -No.02 Make Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270(b) MCB TPN 10 to 32 amps - 4 Nos (01 No Spare)(c) Cable gland double compression type weatherproof for 95 Sqmm 3.5 core 01 Nos (d) Cable gland double compression type weatherproof for 70 Sqmm 3.5 core 01 Nos (e) Cable gland double compression type weatherproof for 50 Sqmm 3.5 core01 Nos (f) Cable gland double compression type weatherproof for 35 Sqmm 3.5 core 01 Nos(g) Cable gland double compression type weatherproof for 25 Sqmm 3.5 core 01 Nos (h) Cable gland double compression type weatherproof for 16 Sqmm 3.5 core 01 Nos |
| 89 | Supply, install, testing and commissioning LT cubical Panel of outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangementboth in front and rear side(independent door for each item on front side) mounted on 4 Nos angle iron 50x50x6 mm, 60 cm long embedded in PCC 1:3:6 type C2 with aluminium bus bar ofrating 1.5 times of incomer MCCB rated capacity, IP 65 protection, provision of holes at the bottom of panelto pass through cable with cable gland for incomming and outgoing cables with lugs and connections, sealed completely to avoid foreign particals entry into the panel,etc required nuts ,bolts and washer incl provision of lugs for cable terminationof 16 to 240 sqmm cable with MCCBs & control wiring with suitable size PVC copper conductor cable etc. Including provision of following accessories/eqpt incl cable gland etc and suitable for fixing of under mentioned items:- |
| 90 | Incoming (a) MCCB Adjustable thermal and fixed magnetic 4Pole 63 A 25 KA -No.01Make Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270(b) Digital Voltmeter 0 to 500 Volt -01 No(c) Digital Ammeter 0 to 400 Amps with CTs and selector switch - 01 set(d) LED Phase Indication lamp (RYB) -01 Set(e) Cable gland double compression type weratherproof for 95 Sqmm 01 Nos Outgoing(a) MCCB Adjustable thermal and fixed magnetic 4Pole 63 A 25 KA -No.01Make Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270(b) MCB TPN 10 to 32 amps - 2 Nos (01 No Spare)(c) Cable gland double compression type weatherproof for 95 Sqmm 3.5 core 01 Nos (d) Cable gland double compression type weatherproof for 25 Sqmm 3.5 core 01 Nos (e) Cable gland double compression type weatherproof for 16 Sqmm 3.5 core 01 Nos |
| 91 | Supply, install, testing and commissioning LT cubical Panel of outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangementboth in front and rear side(independent door for each item on front side) mounted on 4 Nos angle iron 50x50x6 mm, 60 cm long embedded in PCC 1:3:6 type C2 with aluminium bus bar ofrating 1.5 times of incomer MCCB rated capacity, IP 65 protection, provision of holes at the bottom of panelto pass through cable with cable gland for incomming and outgoing cables with lugs and connections, sealed completely to avoid foreign particals entry into the panel,etc required nuts ,bolts and washer incl provision of lugs for cable terminationof 16 to 240 sqmm cable in MCCBs 63 to 630 amps & control wiring with suitable size PVC copper conductor cable etc. Including provision of following accessories/eqpt incl cable gland etc and suitable for fixing of under mentioned items:- |
| 92 | Incoming(a) MCCB Adjustable thermal and fixed magnetic 4Pole 400 A 36 KA -No.01Make Havels Cat Part No -IHLLSEC40400 or L&T/K Cat Part No - CM98403OOROOG or Indoasian Cat Part No - 830396(b) Digital Voltmeter 0 to 500 Volt -01 No(c) Digital Ammeter 0 to 400 Amps with CTs and selector switch - 01 set(d) LED Phase Indication lamp (RYB) -01 Set(e) Cable Gland double compression type for 240 Sqmm 3.5 core 01 Nos Outgoing(a) MCCB Adjustable thermal and fixed magnetic 4Pole 160 A 25 KA -No.02(one spare) Make Havels Cat Part No - IHA13DB40160 or L&T/K Cat Part No - CM90642OOMO or Indoasian Cat Part No - 830295(b) MCCB Adjustable thermal and fixed magnetic 4Pole 100 A 25 KA -No.02 Make Havels Cat Part No - IHA13DB40100 or L&T/K Cat Part No - CM91712OOKOOG or Indoasian Cat Part No - 830272(c) MCCB Adjustable thermal and fixed magnetic 4Pole 63 A 25 KA -No.01. Make Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270(d) Cable Gland double compression type for 120 Sqmm 3.5 core02 Nos(e) Cable Gland double compression type for70 Sqmm 3.5 core 01 Nos (f) Cable Gland double compression type for50 Sqmm 3.5 core 01 Nos |
| 93 | Supply, install, testing and commissioning LT cubical Panel of outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangementboth in front and rear side(independent door for each item on front side) mounted on 4 Nos angle iron 50x50x6 mm, 60 cm long embedded in PCC 1:3:6 type C2 with aluminium bus bar ofrating 1.5 times of incomer MCCB rated capacity, IP 65 protection, provision of holes at the bottom of panelto pass through cable with cable gland for incomming and outgoing cables with lugs and connections, sealed completely to avoid foreign particals entry into the panel,etc required nuts ,bolts and washer incl provision of lugs for cable terminationof 16 to 240 sqmm cable in MCCBs 63 to 630 amps & control wiring with suitable size PVC copper conductor cable etc. Including provision of following accessories/eqpt incl cable gland etc and suitable for fixing of under mentioned items:- |
| 94 | Incoming(a) MCCB Adjustable thermal and fixed magnetic 4Pole 200 A 25 KA -No.01Make Havels Cat Part No - IHLANDC40200 or L&T/K Cat Part No - CM90642OONO or Indoasian Cat Part No - 830296(b) Digital Voltmeter 0 to 500 Volt -01 No(c) Digital Ammeter 0 to 400 Amps with CTs and selector switch - 01 set(d) LED Phase Indication lamp (RYB) -01 Set(e) Cable Gland double compression type for 95 Sqmm 3.5 core 01 Nos Outgoing(a) MCCB Adjustable thermal and fixed magnetic 4Pole 100 A 25 KA -No.01 Make Havels Cat Part No - IHA13DB40100 or L&T/K Cat Part No - CM91712OOKOOG or Indoasian Cat Part No - 830272(b) MCCB Adjustable thermal and fixed magnetic 4Pole 63 A 25 KA -No.02. Make Havels Cat Part No - IHLASF0063 or L&T/K Cat Part No - CM91712OOJOOG or Indoasian Cat Part No - 830270(c) Cable Gland double compression type for70 Sqmm 3.5 core 01 Nos (d) Cable Gland double compression type for50 Sqmm 3.5 core 02 Nos |
| 95 | Supply andinstallation, connecting eclectically & commissioning in replacement of LT feeder pillar box outdoor type of suitable size,factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of suitable size,duly painted with two coats of synthetic enamel paint over and including a coat of red oxide with 300 amps rated aluminium bus bar suitable for 3 phase 4wire supply system duly drilled holes and makingall cable connection with proper thimbles mounted on epoxy based post insulators and one MCCB 200 Amps 4 pole 415 Volt, 35/36 kA of make : Legrand/ Schneider/Havells/L&T complete all as required at site. |
| 96 | Detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured and paid seperately. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required. |
| 97 | M&L for Earthing in replacement / renewal with galvanised steel earth plate electrode 600x600x6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised strip of size 32 x 6 mm earth continuity coductor by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR-I 2009, connected to main switch board all as specified. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20 mm dia GI Pipe medium grade, funnel with wire mesh and lugs, complete all as specified and directed. |
| 98 | Removal of unwanted vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit and surface excavation not esceeding 15 cm depth leveling the ground and removing the excavated material to a distance exceeding 50 M complete all as specified and directed.Note - (1) Tools including Cutting, Digging, grass/ bush cutting machine including fuel & oil has to be provided by contractor with mechine operator & labour. |
| 99 | M&L Painting to existing steel four pole structure of 09 mtr height including mild steel work like cross arms, clamps, pipe channel, bracing etc after cleaning and prepration of surfaces painting externally above painting depth with one coat of aluminum paint over and including a coat of aluminum primer including preparation of existing surfaces and marking pole numbers in 15 cm dia with approved colour in circular and making 03 Numbers & 02 Numbers of bands & strips with 30 cm wide fluorescent paint from bottom of pole to 1.5 mtr height of pole complete all as specified and as directed.Note : Cutting of bushes & tree branches upto 3 Mtrs height of pole shall be deemed included in quoted unit rate. |
| 100 | M&L for recharging to existed earthing in any type upto stranded value using required chemical such as Nacl/ MgSo4 / other approvad chemical incl reveting / welding/ boltingto earth lead incl testing etc by Tech rep with riveting bolting replacing to nut bolt and washer etcto GI earthing strip for making earth continuity from transformer / panels to earthing pit complete all as site required and directed.Note:- Contractor should be submit the bldg wise earthing test result of resistance value with user signature to departmentin duplicate will be submitted to engr-in-charge. |
| 101 | Supply and fixing glow sign board (box type) of size 1500 mm x 600 mm x 150 mm cladding PGI sheet 18 gauge fixed on aluminium angle of size 25 mm x 25 mm x 3 mm on top/bottom both side and transparant acrylic both side and transfrant acrylic sheet 3.00 mm thick in front in which writing with arial black and provision of 3 Nos LED fitting 20 watt for illuminate the board suitable fixing/haning arrangement complete all as specified and directed. |
| 102 | S&F in replacment of in position retro reflective sign board size not less than 2.5 ft to 2 ft cut to sizes/ shape made out of 3 mm thick high density aluminium sheet fixed on wall with aluminium frame work with all weather effected duly riveted with vinyal sheet based of blue colour base by hot process including letter/ nummer as directed fitted on wall with proper arrangment complete all as specfied and directed. Note : The matter which is to be written shall be decided by Engr-In-charge. |
| 103 | Supply and fixing acrylic sheet board 5 mm thickness size 1000 mm x 600 mm on which lay out of installation equipment (computerised Sketch)ofelectric supply. Distribution of Cable detail marked with different colour including all fixing accessories complete all as specified and directed. |
| 104 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart, one twin core cable flat or circular of size 10 Sqmm stranded conductor complete all as specified and directed. (Make - Havells/Plaza/Finolex/Kalinga) |
| 105 | All as per item No 98 above but size 16 sqmm complete all as specified and directed. |
| 106 | M&L for repair & welding of LT feeder pillar box / APFC panel front / rear door and locking arrangement with lock & key including minor parts such as hinges, screw, nuts & bolts, gaskets etc including paint patch work making good as per existing colour andcomplete all as specified and directed. |
| 107 | Supply and fix bus bar chambers 300 mm longiron clad with 4 Nos 200 Amp rated copper strips complete fixed flush wall and making good the disturbed wall surfaces all as a requiredat site complete all as specified and directed. |
| 108 | Supply and fix bus bar chambers 300 mm longiron clad with 4 Nos 100 Amp rated copper strips complete fixed flush wall and making good the disturbed wall surfaces all as a requiredat site complete all as specified and directed. |
| 109 | Material & Labour in replacement of copper wire for control circuitin capacitor bank of size2 core 2.5 sqmm 1100 volts grade complete all as specified and directed. |
| 110 | Dismantling steel poles struts,and supply & erection of 9.00 mtrs high galvanized octagonal pole with bottom 155 mm A/F, top 70mm A/F made up of 3mm thick HT plate along with 250mm x 250mm x 16mm base plate and foundation bolts 04 Nos of M24 X 750 long \"J\" type EN 8 grade foundation bolts along with template, galvanised uniformally inside and outside by means of hot dip mothed, steel material grade must be as per BS-EN10025/IS 2026 and having silicon content not more than 0.6% complete all as specified and directed.Note :- Conditions for octagonal poles & its manufacturing(a) Manufacturer must have hot dip galvanisation facility in their plant with minimum 13 mtrs long galvanizing tank.(b) Raw material (steel) grade must be as per BS-En10025/IS 2062 and having silicon content not more than 0.6% & bidder has to submit raw material test certificate from OEM.(c) Manufacturer must have CNC controlled plasma sheet cutting and bending machine & fully automated submerged arc welding machine at OEM for perfect single longitudinal weiding of shaft.(d) Should be of make in india & have to submit registration certificate.(e) Pole manufacturer must have organised factory with ISO 9001, ISO 14001 and ISO 45001 certified.(f) Structural calculation of pole must be as per IS -875 Part-III |
| 111 | Supply and fix of 1 mtr long hot dip galvanized siongle arm standard bracket made up of 40 NB dia GI pipe suitable to mount on pole having top 70 mm A/F complete all as specified and directed. |
| 112 | Supply and fixing of 1 mtr long hot dip galvanized double arm standard bracket made up of 40 NB dia GI pipe suitable to mount on pole having top 70 mm A/F complete all as specified and directed. |
| 113 | Supply and fix electric stud connector 4 way (RYB&N) with proper colour coding & threaded nobs to tight the cable thimbles, fixed over a hylem sheet or any other elecrically insulated plates with provision of fixing arrangment for MCB SPN 2 way fixed inside GI octoganal pole, including providing good termination to AL cable and copper wire with timbles complete all as specified and directed. |
| 114 | Supply and fix, laying flexible 2.5 sqmm 3 core round copper cable for service connection of street lights within a GI pole inculding termination with thimbles complete all as specified and directed. |
| 115 | M&L for cement concrete 1:4:8 type C-2 (using 40 mm grade stone aggregates) in foundation, filling and mass concrete including sub base of floors complete all as specified & directed. |
| 116 | M&L forReinforced cement concrete nominal mix (using B1 1:2:4 20 mm graded stone aggregates) as in columns, pillars, posts & stuts complete all as specified & directed. |
| 117 | M&L form work to sides of concrete foundation, footings, bases of columns, sides & soffits of foundation and plinth beams and similar work for rough finished flat surfaces of concrete complete all as specified and directed. |
| 118 | Mild steel TMT bars 8 mm dia and over as reinforcement for concrete, cut to length, bent to shape required, including cranking, bending spiraly for hooing for column hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clip complete all as specified & directed. |
| 119 | Mild steel TMT bars 10 mm dia and over as reinforcement for concrete, cut to length, bent to shape required, including cranking, bending spiraly for hooing for column hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clip complete all as specified & directed. |
| 120 | Mild steel TMT bars 12 mm dia and over as reinforcement for concrete, cut to length, bent to shape required, including cranking, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia complete all as specified & directed. |
| 121 | Supply and Fix terminal box made out of PVC Sintex box (GSJB-2817) with hinged door and locking arrangements of size 240x130x95 mm including four way connector, fixed on pole with necessary clamps complete all as specified and directed. |
| 122 | M&L in replacement street light bracket made out from GI Pipe 40 mm bore, light grade 1.20 meter long bent to required shape and fixing to pole, walls etc including fixing of clamp, nut, bolt etc complete all as specified and directed. |
| 123 | Supply and fixing of reflective tape of width not less then 30 cm with strong adhesive on one side to stick on electric poles five layers of zebra in two colours yellow & black layers from the top of the copping of pole, used for high night visibility, complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail