| 1 | Shifting,Assembly, Erection, Testing and Commissioning of11KV,Indoor type Vacuum Circuit Breakers (VCBs). The VCBs shall be erected on the trenches by providing MS material. The job includes but not limited to the following:1) Conducting primary injection, secondary injection tests and testing of relays mounted on VCB panels. Approx. Size: 820(L) x 2355(W) x 2700(H) mmandWt:1500kgs each. |
| 2 | Disassembly of Wiring Chambers of New VCBs for enabling shifting of the VCBs inside the substations at both T33 and DPH and reassembly of Wiring Chambers of New VCBs inside the substations. The job includes but not limited to:a) Disconnection of entire wiring between wiring chamber and circuit breaker chamber, wiring chamber and CT chamber,b) Dismantling of wiring chambersc) Reassembling of wiring chambersd) Reconnection of the wiring between wiring chamber and circuit breaker chamber, wiring chamber and CT chamber |
| 3 | Dismantling of existing VM-12 & BVM VCBs. The job includes but not limited to:a) Removal of covers,b) Disconnection of all the power and control cablesc) Removal of earth connectiond) Dismantling and removal from existing locatione) Shifting of the VCBs to scrap yard or suitable location as per the instruction of site engineer |
| 4 | Disconnection of cables, Dismantling and shifting and reerection of existing Neutral Grounding Resistor Panel and Reconnection of cables. The job includes but not limited to:a) Removal of covers,b) Disconnection of all the power and control cablesc) Removal of earth connectiond) Dismantling and removal from existing locatione) Shifting of the NGR Panel to location and erection as instructedby site engineerf) Reconnection of cables |
| 5 | Disconnection of cables, Dismantling and shifting of 30V DC battery charger along with battery assembly to scrap yard or as per the instruction of site engineer |
| 6 | Disconnection of cables, Dismantling and shifting of 110V DC battery charger along with battery assembly to scrap yard or as per the instruction of site engineer |
| 7 | Shifting and laying of the following HT power cables (UE). The job includes Dressing & Tagging, Fixing of free issued trefoil clamps for Single Core cable at 1mt interval etc. |
| 8 | 1C X 500 sq.mm, 11kV(UE), XLPE Aluminum cable |
| 9 | 3C X 95 sq.mm, 11KV, XLPE Aluminium cable |
| 10 | Removal of existing cable connections from transformers |
| 11 | 3C X 95 sq.mm, 11KV, XLPE Aluminium cable |
| 12 | 3C X 120 sq.mm, 11KV, XLPE Aluminium cable |
| 13 | 1C X 500 sq.mm, 11KV, XLPE Aluminium cable |
| 14 | Shifting and execution of end terminations for the following cables. The job includes, but not limited to, making holes of sufficient size in the gland plates, adjusting the cables in the trench, relaying and adjustment of cable for suitable length for facilitating entry into VCBs/Transformer and providing mechanical support for the cables, sealing of cable entries with wall putty, tagging of cables. Supply of wall putty for plugging holes in the cable entry and cable tags are in contractor\"s scope. The tools required for the work are in contractors\"s scope. |
| 15 | 1C X 500 sq.mm, 11kV(UE), XLPE Aluminum cable |
| 16 | 3C X 95 sq.mm, 11KV, XLPE Aluminium cable |
| 17 | Shifting and execution of straight through joints for the following cables. The job includes preparation of cable at both ends, executing the joint and tagging of the cable joint. |
| 18 | 1C X 500 sq.mm, 11kV(UE), XLPE Aluminum cable |
| 19 | 3C X 95 sq.mm, 11KV, XLPE Aluminium cable |
| 20 | Shifting and Laying of Earth pits for Equipment body earthing with 48mm dia GI pipe .The work includes excavation of earth pit for the above earth pits and pouring of chemical compound in the earth pit after installation of electrode. Placing markers on earth pit. Measuring earth resistance value and marking the same on the earth pit with durable paint or any other method. |
| 21 | Shifting, Fabrication and Erection of BHEL free issued structural steel for equipment/cable tray support . |
| 22 | Shifting & Earthing of Equipment from nearest Earth riser with 50x6mm/ 25x3mm GI flat |
| 23 | Shifting & Erection of cable tray upto 600mm width of ladder / perforated type. The job includes fabrication of cable tray bends wherever required. |
| 24 | Supply and laying of Electrical Insulated Rubber Floor Mats, size: 1000x2000x2.5 mm, 11KV, Class B for placing in front of HT & LT Switch Gear Panels conforming to IS:15652/1969. Insulation Resistance: 10,000MOHMS (minimum). Breakdown Test: 50kV (minimum) as per IS: 2584/1963. |
| 25 | Shifting and laying of the following LT cable. The job includes shifting of cable drum from stores, laying and dressing of the cable |
| 26 | 3.5C X 300 sq.mm Aluminium, 1.1KV, LT PVC insulated, armoured Aluminum cable |
| 27 | 4C X 16 sq.mm Aluminium, 1.1KV, LT PVC insulated, armoured Aluminum cable |
| 28 | 3C/4C X 1.5/2.5 sq.mm Copper armored cable |
| 29 | 12C X 1.5 sq.mm Copper armoured cable |
| 30 | Termination of the following LT cable. The job includes preparation of cable, making holes in the gland plate of VCB/transformer marshalling box/30VDC Battery Charger, Supply of double compression glands for the armoured copper cable, supply of cable lugs, execution of terminations and closure of covers and/or plugging of gaps in the cable entry gland plate. Copper/Aluminum lug, double compression glands are in the scope of contractor |
| 31 | 3.5C X 300 sq.mm 1.1KV, Aluminum, PVC insulated armoured cable |
| 32 | 4C X 16 sq.mm Aluminium, 1.1KV, LT PVC insulated, armoured Aluminum cable |
| 33 | 3C/4C X 1.5/2.5 sq.mm Copper armored cable |
| 34 | 12C X 1.5 sq.mm Copper armoured cable |
| 35 | Shifting, Erection, Testingand Commissioning of 30V DC, 100AH Lead Acid (VRLA) battery bank and charger for VCB & LT ACB panel operation. The job includes assembly of battery cells. |
| 36 | Shifting, Erection, Testingand Commissioning of 110V DC Lead Acid (VRLA) battery bank and charger for VCB & LT ACB panel operation. The job includes assembly of battery cells. |
| 37 | Supply, Shifting, Installing, Testing and commissioning of LED Double Tube Lights fittings along with lamps of capacity 22W each. Supply of downrods and 3C X 1.5 sq.mm cable is in the scope of the contractor.Make: Havells/Philips/Crompton Greaves/Bajaj/GEModel: REGALBATTENT8UPTO2X22WDSBSWH/equivalent model of other makes mentioned above.The job also includes supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 90 cm length, painting and wiring the down rods and connections with 3CX 1.5 sq. mm FRLS PVC insulated, copper conductor and earthing etc. as required. |
| 38 | Supply, Shifting, assembly, fixing, testing and commissioning 1400mm sweep BLDC ceiling fans as per the following specifications.*) Input power ≤ 32W*) Sweep diameter - 1400mm*) No. of blades - 3 nos*) Color - White*) BEE star rating - 5-star*) Fan Motor with PCB Controller - 1 no*) 1 no Downrod of length - 260mm*) 1 no remote*) 2 nos AAA batteries *) 1 no Shackle kit*) 1 no twisted wire*) 1 no warranty card for two yearsThe job includes supply and fixing of Anchor fastner with fan hook / Providing MS Fan hook with grouting and cement plastering and supply of 3C X 1.5 sq.mm copper cable for connecting from ceiling rose to the fan.Make of fan: Orient/Havells/Bajaj/Crompton Greaves/StandardModel: Topaz Gold of M/s Orient or equivalent model of other makes. |
| 39 | Shifting, installation, testing and commissioning of BHEL free-issued Periphery LED lighting. 42mm GI pipe will be issued free of cost by BHEL. The job includes bending of the GI Pipe, fixing of the pipe at a suitable location by any suitable means as instructed by site engineer. |
| 40 | Supply and fixing of 3pin, 250 V. 10 Amps power socket cum switch with indication Roma type code 21113 and 21033 of Anchor make. Fixed on suitable modular type concealed box top cover.Testing & commissioning. |
| 41 | Supply and fixing of 10 Amps 250 V. SP switches for control of light fitting and fans with Roma Type code: 21011 of Anchor make. Fixed on a suitable modular type concealed box with suitable top cover. Testing & commissioning. |
| 42 | Supply and execution of concealed PVC/Surface MS Pipe or HDPE Pipe wiring with 1.5 sq. mm 660 / 1100. V. Grad PVC insulated copper wire multi strand of make Finolex/Rediant/Finecab/Havells/L&T. In PVC pipe/MS Pipe of suitable dia (As per IS: 743 for wiring points ) with 14 G/1.5sq.mm green colour copper wire for earth continuity. Each light / fan point should be connected to three plate ceiling rose code 39072 of Roma modular type of Anchor make / connector suspended duly with couduit / PVC pipe etc.Each ciruit should not have more than 7 points 700 watts. |
| 43 | Supply and fixing of 3pin, 250 V, 10/25 Amps power socket cum switch with indication Roma type code 34374 and 22014 of Anchor make. Fixed on suitable modular type concealed box top cover.Testing & commissioning. |
| 44 | Supply and installation of wiring with 2.5 sq. mm PVC insulated copper wire multistrand of make Finolex/Rediant/Finecab/Havells/L&T.The wiring point for 20/16 A. power socket including 14 G./2.5sq.mm green colour copper wirefor earth continuity. Independent circuit for each socket from power MCB distribution board (As per IS:732 for wiring point) Testing and commissioning. The wiring should not be mixed with lighting pipe wiring and it should be run separately in the room/ shed at a height of 2 feet from ground leavel or as per the site engineers instruction. |
| 45 | Supply and Installation of MCB DB with TPN 415V,consisting of 10 to 20A -- 6nos MCBs on each phase i.e., a total of 18 Nos of MCBs , sheet enclosed, dust & vermin proof. Model 8GB32202RC06 of SIEMENS/Equivalent model of L&T/ABB/STANDARD/LEGRAND/HAGER MAKE along with controlling 63A TPN MCB. It is to be fixed on a neatly fabricated steel frame and mounted on to walls or as required for lighting distribution. The scope of supply also includes the following:*) DIN rail mounted Multifunctional Energy Meters 100A Direct, make: Elmeasure, model no: LG 2510D (Category code: LG2510D11A00)/make: Selec,(Category code: EM4M-3P-C-100A)The job includes painting of steel frames, labelling / writing the connection chart inside the door with WHITE duco paint as required, double earthing, testing & commissioning. |
| 46 | Supply and laying of the following PVC Pipes and suitable no. of bends and junction boxes for electrical and telephone wiring. The job includes chipping of wall and concealing the pipe in the wall and plastering after fixing the pipemake of pipes: Sudhakar PVC pipes/Anchor/Ashirvaada) 25mm (1\") dia PVC pipes 1.5mm thick, Make: Sudhakar Pipes/Anchor/Precision |
| 47 | Excavation and Road cutting |
| 48 | In soil, excavation of 1000mm deep and 500mm width trench, supply & spreading of sand, supply & laying of bricks & shabad stone as per IS:1255 1983 and back filling after laying the cable with marking plates. Existing HT cables are lying in the route. Hence, Contractor has to take additional safety precautions. If any existing cable happens to be damaged during the above excavation, the responsibility lies with the contractor for repair/restoration of cable at free of cost to BHEL. |
| 49 | Cutting of Road, RCC & Hard rock (500mm width, 300mm depth). Backfilling the excavated area without looseness in soil |
| 50 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge for facilitating cable entry |
| 51 | Supply and fixing of Polyethylene Earth Pit Chamber covers |
| 52 | Providing and laying in position specified grade, Reinforced cement concrete excluding the cost of shuttering, finishing and reinforcement. All material and equipment are in the scope of contractor. Cement: OPC 43 or OPC 53 grade are permitted.a) all works up to Plinth level with 1:1 ½:3(1 cement: 1 ½ coarse sand: 3 graded stone aggregate of20 mm nominal size)) |
| 53 | Shifting, Testing, Erection and Commissioning of LT ACB Panel of size: 1300mm X 900mm X 1000mm. Approximate weight of the panel: 800Kgs |
| 54 | Shifting, Erection, Testing and Commissioning of BHEL free-issued Feeder Panel. Approximate size: 1500mm X 400mm X 600mm and weight: 120 kgs |
| 55 | Engaging earth dozer/ JCB / chain wheel mounted dozer / 10-14 T Hydra Crane / Telescoping type Crane with basket / Sky lift with basket to work, for dozing, levelling, lifting, handling equipment, working at all heights etc., as directed by Engineer-In-Charge. Rate includes Operator, fuel, helpers, slingers etc., including all incidentals for handling the work. |
| 56 | Disconnection of cables, removal of cables and dismantling of the following:a) 16m high mast light with eight lampsb) Feeder pillar for the above high mastThe job includes, but not limited to, complete disassembly of the high mast, removal of lamp posts, removal of high mast from foundation. |
| 57 | Shifting, assembly, erection, testing and commissioning of 10 m high 90W street light poles. The job includes shifting of poles from stores, excavation of earth for suitable depth (up to 1m), assembly of street lights, fixing of power distribution boxes, fixing of street light to street light arm, fixing of street light arm to street light pole, installation of street light pole assembly, testing and commissioning. |
| 58 | Shifting, Assembly, Erection, Testing and Commissioning of 16/20Mt height Polygonal Highmast Lighting System with 8nos 400W HPSV luminaires. The job includes the following: 1) Assembly of luminaires which are are to be fixed on 710mm dia carriage. 2) Assembly of the highmastin two sections of top 5470/9520mm and bottom 10980/10980mm length. 3) Assembly and installation of the luminaire carriage which is operated through double drum winch with 2HP integral motor, 5Cx4sq.mm trailing copper cable and stainless steel wire rope, control panel etc.4) Testing and commissioning |
| 59 | Supply of the following items for cables:a) Cable Insulation Stripping knife, make: Jainson, model: Panther max |