| 1 | Notes:-(i) 100 percent nonperishable items of the work shall be deposited by the L1 bidder within 30 days after placing of work order.(ii) The critical path network shall be submitted by L1 bidder immediately after the acceptance of tender and approved by GE.(iii) The bidders must ensure to visit the site, check relevant documents and makes of materials required to be incorporated under the subject from concern Engineer-in-Charge.(iv) Material obtained from demolition/dismantled and the serviceable material (other than reused in the work) shall be the property of the Govt and shall be removed and deposited in the MES Store Yard without any extra cost to Govt.(v) In case of non-availability of any make mentioned under list of Makes, the L1 Bidder shall obtain non-availability / non-manufacturing certificate from the concern OEM / authorised dealers and submitted to Accepting Officer, the L1 bidder may be incorporated Group-I category makes as approved by HQ CE SWC Jaipur / HQ CE BTZ in the works after prior approval of Accepting Officer.(vi) L1 Bidder shall produce E-way bill alongwith test certificate from OEM / manufacturer for costly items / major items of amount above Rs 50,000/- along with RAR’s and Final Bill.(vii) L1 Bidder shall be maintained an album containing Photos of all the material brought at site and each stage wise work progress and kept at site. Same shall be deposited in Engineer-in-Charge office after completion of work. (viii)It shall be ensured by the bidder that main item and fixtures/base material shall be from the same manufacturer. (ix) Sufficient tradesman,Labours needed for subject work shall be deployed by the bidder on daily basis ans as required by Engineer-in-charge. (x)The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder,nothing extra shall be paid to the bidder on this account. (viii) The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder, nothing extra shall be paid to the bidder. |
| 2 | Dismantling existing unserviceable Aluminium conductors, steel reinforced (ACSR conductor) from overhead lines on LT poles, of any type and any size complete all as specified and as directed by Engineer-in-charge |
| 3 | M&L forAluminium conductor, steel reinforced (ACSR)any type of ACSR conductor as per site requirement of size /make as ordered including stringingfor overhead line on LT poles including aluminum binding wire 14 SWG, jumpers, line tapes, conducting jelly etc complete all as specified and as directed by Engineer-in-Charge.(Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compoundingthe weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.) |
| 4 | S&F in replacement shackle type insulators,vitreous porcelain white, brown or green for working pressure 1100 volts grade of 100 mm height and 115 mm dia including galvanized mild steel straps of 31mm x 5mm size,14mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge. |
| 5 | S&F in replacement pin type insulator of size 100mm height, 65 mm diaporcelain, vitreous white, brown or green insulator suitable for 1100 volts grade including one galvanized mild steel spindle, two GI washer and one GI nutcomplete all as specified and directed by Engineer-in-Charge. |
| 6 | M&L forfixing in replacement ofCross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-410-0 or Fe-310-0 grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, suppliedand fixed in repair complete all as specified and as directed by Engineer-in-Charge.(Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only.Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.) |
| 7 | S&F in replacement stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1800mm long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator with over all dimensions 90x140mm and clearence of hole 25.5mm, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.Note : Excavation,earthwork and PCC in foundation shall be measured and paid seperately under respective items of BOQ. |
| 8 | M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of Red Oxide Zinc Chrome Primer, alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paintcomplete all as specified and directed by Engineer-in-Charge |
| 9 | M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete cement Pole (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (5 No. Each Strip 300mm wide) and remaining portion of Pole treated with Two Coats of Exterior Weather Proof Paint also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paintand Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paintcomplete all as specified and directed by Engineer-in-Charge. |
| 10 | Disconnecting over head conductors and insulators any Nos on existing damaged Pre -stressed Concrete CementLT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L forEreting Pre-stressed concrete poles 9 meter long, 102mm x 172mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable onecomplete all as specified and as directed by the Engineer-in-Charge.Note : Earthwork, Cement Concrete, etc. shall be measured and paid under respective Items. |
| 11 | Disconnecting over head conductors and insulators any Nos on existing damaged steel tubularswaged LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L forEretingSteel Tubular Swaged Pole Type 410-SP-31 (9.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of red oxide Primer (Externally from Top of Coping)and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (4 No. Each Strip 300mm wide) andalso including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint,including dismantling of old unserviceable one complete all as specified and as directed.Note : Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items. |
| 12 | Disconnect the electric supply from Main GO/DOand taking down old existing LooseACSR conductor mounted on Steel/PCC pole3 to 5 Conductorand Re-stringing of existing over head line ACSR conductor/GI wire of any size/type including repair of conductor broken due to wind storm/expansion, contraction etc, on existing LT steel and/orPCC pole including replacement of aluminium binding wire of suitable size andrefixing of all old accessoriescarefully without damaging of insulator etccomplete all as specified and directed by Engineer-in-Charge.Note:- Length of each conductor shall be measured as one length. |
| 13 | M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in new / old coping of poles etcincluding weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge |
| 14 | M & L for PCC (1:3:6) typeC-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing completeall as specified and directed by Engineer-in-charge |
| 15 | M & L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation for poles,struts & mass concrete including necessary form work and fair finishing to exposed surfaces completeall as specified and directed by Engineer-in-charge |
| 16 | M&L for Earthing complete with galvanised steel pipe ,40mm bore ,medium grade, 2.5 metre length, burried directly in ground vertically to a depth not less than 2.5 metre below ground level with top edge of not less than 1.25 metre below ground level, , connected to earth lead of GIstrip 32mm x 6mm thickby means of bolts, nuts and washers of the earth wire galvanised iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 40mm upto earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat ironand perforated water pipe 20mm dia GI medium grade of length 2.25 mtop of pipe with funnel & wiremesh, and bottom connected to elctrode by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete including taking down old eathing complete all as specified and directed by Engr-in-charge.Notes :- (i) Cost of GI wire upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item.(iii) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber.(iv) Minimum weight of reinforcement for RCC cover shall be 1 KG. |
| 17 | Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays, joints or layingunderground cable etc.in soft/loose soil,& getting out including taking out old brick or precast cable cover complete all as specified and directed by Engineer-in-Charge. |
| 18 | Description as per Item No. 16 but not exc 3 mtr in depth complete all as specified and directed by Engineer-in-Charge. |
| 19 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge |
| 20 | Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level n. exc 1.50 metre above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supplyand fixingHDPE DWC Pipe dia inner dia 75mm and outer dia 90mm for laying of cable laid in trenches complete all as specifiedand as directed by the Engineer-in-Charge.Note:- excavation and earth work shall be measured and paid for separately. |
| 22 | Supplyand fixingHDPE DWC Pipe dia inner dia 50mm and outer dia 63mm for laying of cable laid in trenches complete all as specifiedand as directed by the Engineer-in-Charge.Note:- excavation and earth work shall be measured and paid for separately. |
| 23 | Supplyand fixingHDPE DWC Pipe dia inner dia 32mm and outer dia 40mm for laying of cable laid in trenches complete all as specifiedand as directed by the Engineer-in-Charge.Note:- excavation and earth work shall be measured and paid for separately. |
| 24 | Taking out oldunderground LT Cable of size 10 sqmm to 240 Sqmm of 3.5 core fromLT Panels trenches/floors /road/wall/ pipe/pole/including taking out loop from trenches upto 1.5 mtrs depth, cutting the faulty end of cable and refixing the cable in original position by using flat aluminium sockets/ thimble/ andinsulating the all nackedwiresof anysize including making connection with MCCB\"s/ Switchescomplete all as directed by Engineer-in-Charge. Note : Exacavation for taking out LT cable from will measured and paid separatly. |
| 25 | Supplying, jointing and testing in replacement heat shrinkable typeindoor / outdoor end termination jointing kit, suitable fordifferent size of cable 35 sq mm to 120 sq mm aluminium conductor1100 Volts including making connectionscomplete all as per following. |
| 26 | All as per item No 24 above but suitable for cable of size 185 sqmm to 300 sqmm. |
| 27 | Supplying, jointing and testing in replacement heat shrinkable typestraight through jointing kit, suitable fordifferent size of cablealuminium conductor1100 Volts including making connectionscomplete all as per following and directed by Engineer-in-Charge. |
| 28 | All as per item No 26 above but suitable for cable of size 16 sq mmto 25 sqmm. |
| 29 | All as per item No 26 above but suitable for cable of size 35 sq mmto 70 sqmm. |
| 30 | All as per item No 26 above but suitable for cable of size 95 sqmm to 120 sqmm. |
| 31 | All as per item No 26 above but suitable for cable of size 185 sqmm to 300 sqmm. |
| 32 | Trimming/pruning of the tree branches comming cross electric power head line LT feeder cleaning the span and making it free from touching the tree branches complete all as specified and as diredted by Engineer-In-Charge.(Note :-(i) All item of LT overhead lines taken together shall be measured as one unit for the payment purpose under this item.(ii) Only such length shall be measured where trees are required to be cut/trimmed as directed by Engineer-In-Charge.(iii) Removing branches from road and diposition at a distance of more than 500 meter)(iv) Ladder wheel shall be arranged by the contractor at his own cost, nothing extra shall be paid on this account. |
| 33 | Supply and fixing 32 mm dia 1.2 metre long GI pipe light grade bracket forfixing street light made to shape at including MS clamps (FI Plate 25X4mm as per site requirement) 02 Nos and nut and bolts duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete as required at site complete all as specified. |
| 34 | S&F in replacement following MCCB , thermal magnetic release in the existing feeder pillar box including any addition / alteration to the panel to accommodate the new MCCB & making connections with 25x3 mm copper strip as required from main bus bars,making necessary welding work, metal work for fixing base plate etc and connectionscomplete all as specified and as directed by Engineer-in-Charge. Make:- Legrand / L&T/ Schneider / Indoasian |
| 35 | All as per item No. 30here-in-before but MCCB 4 Pole, 63 Amps rating, breaking capacity 16 KA, 415 Volt complete all as specified and directed. |
| 36 | All as per item No. 30here-in-before but MCCB 4 Pole,125 Amps rating, breaking capacity 16 KA, 415 Volt complete all as specified and directed. |
| 37 | All as per item No. 30here-in-before but MCCB 4 Pole, 160 Amps rating, breaking capacity 36 KA, 415 Voltcomplete all as specified and directed. |
| 38 | All as per item No. 30 here-in-before but MCCB 4 Pole, 250 Amps rating, breaking capacity 36 KA, 415 Volt complete all as specified and directed. |
| 39 | All as per item No. 30 here-in-before but MCCB 4 Pole, 400 Amps rating, breaking capacity 36 KA, 415 Volt complete all as specified and directed. |
| 40 | All as per item No. 30 here-in-before but MCCB 4 Pole, 630 Amps rating, breaking capacity 50 kA, 415 Volt complete all as specified and directed. |
| 41 | Supply and fixing in replacement weather proof PVC insulated, sheathed three core stranded aluminium conductor cable of size 2.5 Sqmm, 1100 Volts grade conforming to IS:9968 (Part-I) 1988 or IS:694-1990 complete all as specified and directed by Engineer-in-Charge. |
| 42 | Locating the fault in LT cable of any size for any type of fault like open cable short between phases/Neutral ,grounded cable with help of cable fault locator and pin pointing location with the help of audio signal ,excavation at the fault and openning cable to suitable distence and depth for making a cable joint and including complete Earth work all as specified and as directed .(note:-1. The joint kit will bepaid separately. 2:-contractor will have to arranged the cable fault locator or other testing Eqpt /tools as required &same shall be deemed to be includede in the item rate Quoted) |
| 43 | Supplying, laying, jointing, commissioning and testing in replacement XLPEinsulated screened PVC bedded, armoured,heavy duty underground electric cable with stranded aluminium conductor 1100 volts gradeconfirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge. Make :- Havells / Gloster / Finolex / Polycab/RR cables or equivalent make as specified in Appendix \"A\" |
| 44 | All as per item No 35 above but cable of cross secitonal area 240 sq mm 3.5 core. |
| 45 | All as per item No 35 above but cable of cross sectional area 185sq mm 3.5 core. |
| 46 | All as per item No 35 above but cable of cross sectional area 120 sq mm 3.5 core. |
| 47 | All as per item No 35 above but cable of cross sectional area 95 sq mm 3.5 core. |
| 48 | All as per item No 35 above but cable of cross sectional area 70 sq mm 3.5 core. |
| 49 | All as per item No 35 above but cable of cross sectional area 35 sq mm 3.5 core. |
| 50 | All as per item No 35 above but cable of cross sectional area 25 sq mm 4core. |
| 51 | All as per item No 35above but cable of cross sectional area 16 sq mm 4 core. |
| 52 | All as per item No 35 above but cable of cross sectional area 16 sq mm 2 core. |
| 53 | All as per Item No 35 above but Cable of Cross Sectional Area 10 sq mm 2 Core |
| 54 | Suppyling, installing, testing and commissioning factory made outdoor type bus bar chamber having MCCB 4 Pole, 415 Volts, 160 Amps of suitable size for operation on 415 volts, 3 phase, 4 wire, 50 Hz, outer shell made out of 3.15mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 250 Amps aluminium bus bar fixed Horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 160Amps MCCB including provision for taking out incoming and outgoing cables detachable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces groutedin PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and as directed by Engineer-in-charge. |
| 55 | S&F as in repaircable junction box of size not less then 300x200x105mm, made of high quality thermo plastic polystyrene, weather proof, dust, jet water proof, chemical, acid corrosion, impact, insulated & shock proof IP 66 / 67 for outdoor Installation with internallly embedded gasket (PUR) including the box fitted with connector 8 way 40 Amps 01 No including Emlex stud type TB 4 Nos incoming / outcoming cable at controlled with MCB SP 6 Amps 01 No & enclosed along pole with MS flat iron clamp of suitable size complete all as specified and directed by Engineer-in-ChargeNote :- Cost of flat iron clamp is deemed to include in unit rate of this items. Make Sintex cat Part No GSJB-3020/Hensel/indokop or equivalent Technocommercial as mentioned in Appx \"A\". |
| 56 | Supply and fixing in replacement electronic MPPCB for street light(Make as per site requirement) 220/240 V suitable for existing LED light fitting , 45 Watts ,60WATT /complete all as specified and directed by Engineer-in-Charge. |
| 57 | Taking down LED security/street light fitting such as 30/45/60/72/90 watt etc for find out faults including cleaning of glass with castic soda solution and refixing the same in existing position after carrying out necessary repair / replacement of unserviceable parts complete all as specified and directed by Engineer-in-Charge.Notes :- (i) The accessories / spare parts which are required to be replaced shall be measured and paid in respective item.(ii) Ladder wheel shall be arranged by the Contractor.(iii) Detection and rectification of fault in over head/under ground line shall be done by the contractor. |
| 58 | Inspection/checking/tightening of connections for LED Security/Street light fitting such as 30/45/60/72/90 watts etc for tighting the connection with replacement of twin core multi strand 2.5 Sqmm aluminium wire complete all as specified and directed by Engineer-in-Charge. |
| 59 | M&L for preparation of existing painted surfaces of Panel Board / Feeder Pillar box(indoor / outdoor type), area not exceeding 10 square metre each and applying one coat of synthetic enamel paint after preparation of surfaces on external and internal surfaces of approved tint by using spray machineinclusive of writing SM / MES No / name of feeders etc.(not exceeding of height 5 cm each) including welding of broken panel door, tightening electric connection of switch gears and cleaning of vegetation all around the panels up to one meter from all sides complete all as specified and as directed by Engineer-in-charge. |
| 60 | Supply only and testing LED Street light fitting of 45 Watt including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 60 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including provision of connection for street light from pole box with 2.5 Sqmm PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked complete all as specifiedand directed by Engineer-in- charge. |
| 61 | Taking down 150-200 watt flood light fitting for finding out faults and refixing the same in existing position after carrying out necessary repair and wiring with 4 sqmm 3 core copper PVC cable, tightning of loose connection and cleaning of glass complete all as specified and directed by Engineer-in-Charge.Notes :- (i) Ladder wheel shall be arranged by the Contractor.(ii) Detection and rectification of fault in over head/under ground line shall be done by the contractor. |
| 62 | Supply only electronic driver (Make as per site requirement) 220/240 V suitable for existing LED light any typefittingWatts complete all as specified and directed by Engineer-in-Charge. Make Wipro/Philips/Cromptonor equivalent Technocommercial makes as mentioned in Appx \"A\" |
| 63 | Supply only 10 KV surge protector suitable for anytype ofLED fitting & make complete all as specified and directed by Engineer-in-Charge. |
| 64 | S&F in replacement LED flood light of 160 watt with high pressure die cast housing with lens with lument output 6000K complete (including LED, drive and internally prewired) with on board 5 KV surge protection with 10 KV external SPD. The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP 66 protection as per IS 10322-1982 (part-I) with latest amanedments and input voltage range 140-300V AC, frequency 50-60 Hz, P.F should be more than 0.9. The efficiency of LED luminaries system shall be more than 100 lumens per watt and FRLSH cable PVC insulated stranded copper conductor, 1100 volts grade, 2.5 sqmm x 3 core of ISI marked for light to ceiling rose complete including arrangement of mounting for street light as required at site complete all as specified and directed by Engineer-in-charge. |
| 65 | S&F in replacement electronic MCPCB for flood light 120 watt to 180 watt (make as per site requirement) complete all as specified and as directed by Engineer in charge. |
| 66 | Supply only in replacement electronic driver 220/240 volts suitable for existing LED flood light fitting 150-200 watts complete all as specified and directed by Engineer-in-Charge.Make :- Wipro / Philips / Syska / Crompton / Surya or equivalent in makes mentioned in Appendix \"A\" here-in-after. |
| 67 | S&F in replacement three phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights with three number two pole power contractors 40 Amps (Type - MU40-2P, Cs90119) with coil voltage 220 / 240 V and incoming MCBs single pole - 03 Nos, outgoing MCBs single pole - 03 Nos of rating 32 Amps & circuit wiring with single core multi stranded of size 10 Sqmm. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. The sensor along with suitable power contactor (S), Incoming -outgoing MCB\"s should be enclosed in a Rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure with hinged lid confirming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass option). The enclosure sould be mounted on 40mm x 40mm x 5mm angle iron structure and the structure height minimum 600mm and must be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer in charge. KAKATIYA ENERGY SYSTEM PVT LTDcat aprt No. Swadeep 02EC5KW3P or Equivalent make as specified in Appx \"A\". |
| 68 | S&F as in replacementthree phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lightscompitable with exisitng timer box. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours.complete all as specified and directed by Engineer in charge.Make :- Nature switch shall be same make of exisitng timer box i.e. KAKATIYA ENERGY SYSTEM PVT LTDcat aprt No. Swadeep 02EC5KW3P or Equivalent make as specified in Appx \"A\". |
| 69 | S&F as in repair LED Bollard 08 Watt IP65 cone series acts as imposing street furniture . The elegant yet minimailistic design acts a silent observer and giving light, diffuser at the upper portion adds fucctional Value into landscape environmental with all accessories complete all as specified and as direcetd.Make :- Havells Cat Part No.CONEBLS8WLED830PSYMTOPC/Wipro/Crompton or Equivalent technocommercial cat part as specified in Appendix \"A\" |
| 70 | Taking down unserviceable ACB of capacity 630/800 Amps from the LT panel and disconnecting for repair/ replacement of following parts:-(a) Decarbonizing of busbar and all defective parts- 01 Job(b) Replacement of control wiring -01 Job© Replacement of heat shrinkable insulation of busbar with colour coding - 01 Job(d) Replacement of Male and Female Contactor(e) Toggle Switch(f) Repairing to triping mechanism including replacement of all defective parts - 01 job(g) Assembling the ACb complete and refixing the same in the LT panel and testing after completion of work , complete all as specified and as directed.Note :-Old unserviceable material retrieved from above mentioned all items shall be deposited in store yard of subdivision by the contractor at his own arrangement. Noting extra shall be paid on this account.If bidder fail to submit the old item than suitable recovery as per double the Market Rate of old item shall be deducted from the final bill and suitable action shall be taken against the bidder as deemed fit. |