| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. (a) Group C |
| 2 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 15/16 amp switch |
| 3 | b) 3 pin 5/6 amp socket outlet |
| 4 | c) 6 pin 15/16 amp socket outlet |
| 5 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 6 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. (a) 3 Module (100mmX75mm) |
| 7 | c) 6 Module (200mmX75mm) |
| 8 | d) 8 Module (125mm X 125mm) |
| 9 | e) 12 Module (200mm X 150mm) |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessedPVC conduit as required. |
| 11 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 12 | 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire |
| 13 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 14 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 15 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 12 way (4 + 36), Double door |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door |
| 17 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 18 | Supply of 15\"(380 mm)sweep 1400 rpm heavy duty Exaust Fan complete with ring, blade etc as required. ISI marked. |
| 19 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 20 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 21 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing &Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) 18-22 watt |
| 22 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, freq 50/60 hz, Operating temprange -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). CRCA Sheet Body (Thickness ≥ 0.50 mm) 36 Watt |
| 23 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) |
| 24 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubical panel board including drilling holes in cubical panel, making connections etc. as required 125 A, 16kA, TPMCCB |
| 25 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 400 Amp, 35 kA, TPMCCB |
| 26 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 Amp, 25 kA, TPMCCB |
| 27 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 150 Amp, 16 kA, TPMCCB |
| 28 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width x 50 mm depth x 1.6 mm thickness |
| 29 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 30 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*35 sqmm |
| 31 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*50 sqmm |
| 32 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*70 sqmm |
| 33 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*95 sqmm |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required(a) Above 35 sq. mm upto 95 sq. mm |
| 35 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required(a) Above 35 sq. mm upto 95 sq. mm (clamped with 25x3 MS flat clamp) |
| 36 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5x70 sq. mm(38mm) |
| 37 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5x95 sq. mm(45 mm) |
| 38 | HI - WALL SPLIT SYSTEMS Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU),copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R- 407 Green Refrigerant, wireless Remote control, suitable for workingbetween 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be ableto deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only 2.0 TR with 5 Star BEE Rating |
| 39 | S/I/T/C of 5 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 40 | S/I/T/C of copper pipe for split AC |
| 41 | S/I/T/C of Drain Pipe |
| 42 | S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner |
| 43 | S/I/T/C of stand for split AC |
| 44 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |