| 1 | Supplying & Laying of following sizePVC insulated PVC sheathed1.1KV grade armored Aluminium cable for extending of Power supply from Panel to DG set/BTS DB as required. |
| 2 | 4 x 16 Sqmm |
| 3 | 4 x 25 Sqmm |
| 4 | Supplying & Laying ofsingle core 25 Sq.mm weather proof Aluminium power cable of 1.1 KV grade in In Existing PVC/ MS conduit / in open as required. |
| 5 | Supplying & laying10 SWG GI wire for support of OH service cable as required. |
| 6 | Supplying and laying of the following size PVC insulated FR copper conductor cable including terminations in the existing PVC pipe as reqd. ( M/s. Polycab/ equivalent make) |
| 7 | 10 Sqmm |
| 8 | 16 Sqmm |
| 9 | Supplying & fixing of the following size PVC pipe on surface of wall / floorfor covering of Electrical cables as reqd. |
| 10 | a) 40 mm dia Rigid PVC pipe |
| 11 | b) 25mm dia Rigid PVC Pipe |
| 12 | Supplying & fixing of3 chamber Outdoor Panel( min size : 75cm (H) x 75 cm (W)x 30 cm (D)) made up of 16 G MS sheet for housing1Ph/3Ph Energy Meter ( direct type)-1NO, 100A Fuse cutout-3nos with Neutral link and 63A ON Load Changeover switch -1No on existing MS angle iron frame , painting complete as required. (Panel specification : a) Panel shall be Made up of 16G MS sheet b) All 3 chambers shall be individually separated, shallhaveIndividual doors with locking arrangement. c) Meter chamber shall have opening with Glass provision for meter reading from outside d) change over Switch chamber shall be double door. e) All chambers shall have suitable holes & rubber seals for cable entry. f) Panel shall be powder coated. g) suitable size hylam sheet & DIN rail shall be provided inside panel chambers wherever necessary for fixing Meter/ fusecutouts/ MCBs etc,h) Panel drawing shall be approved by competent authority ) |
| 13 | Supply and making ofMS stand made up of 40mm x 40mm x 5mm MS Angle for fixing above OD meter panelabove 1.5 mtrs height (upto 2mtr) above ground level including welding, making holes, cement concrete foundation, transportation etc complete as required. |
| 14 | Supplying & fixing ofoutdoor PVC Enclosure(min 400mm x300mm ) with hinged doorfor housing1 No2/4 way enclosure with 63A FP/DP MCBand 15A Power socketon surface of wall/ MS grill as required |
| 15 | Supplying & fixing of following MCBs in existing MCB DB/ in panel complete as required |
| 16 | 2 Way/ 4 way enclosure |
| 17 | 63A 4 PoleMCB ( C-series) |
| 18 | 63A DP MCB ( C-series) |
| 19 | Supply and fixing of 63A 4 pole on load change over Switch ( without Enclosure ) suitable for operating on 415V, 3 Phase, 50Hz AC supply in existing MS Panel complete as required. |
| 20 | Transportation of Telephone pole from nearest TE/ BTS and Errection at site by digging the soilfor laying of Over head service cable from EB Pole to building/BTS site complete as required. |
| 21 | Supply and fixing of 15A Power socket with switch of modular type on surface of wall/in in existing panel/in PVC enclosure along with interconnections etc as required. |
| 22 | Supplying and fixing ofOD power distribution box ( inside BTS room for power distibution to multiple operators) (approx 50cm x 50cm x 15cm) (double door) made up of 16G MS box for housing 63A FP MCBs-4 nos along with 4 Nos AL Bus bars (20mm x 3mm x 300mm each on 2 nos insulators) on surface of wall / on Iron Mesh with suitable supporting clamps complete as required. |
| 23 | Supply and fixing of 63A TPN Switch with suitable enclosure and 3nos 63A HRC fuse links suitable for 415V, 50 Hz, AC Supply on surface of wall / MS grill complete as required. |
| 24 | Supplying & fixing of following electrical items on surface of wall/ in existing Power panel complete as required |
| 25 | 100A Fuse Cut Outs |
| 26 | 100A Neutral Link/Busbar link |
| 27 | Providing of 25mm x5mm GI strip on surface of wall or in recess for extention of earthing as required. |
| 28 | Removing of DISCOM energy meter from existing meter panel during provision of new meter/fuse panel and fixing the same in meter panel by co-ordination with DISCOM authorties as required |
| 29 | Supplying & fixing additional GI sheet roof of suitable size for OD meter-fuse box made up of 25x5 GI strip supports & 24G L-shaped GI sheet to the existing Iron frame as required. |
| 30 | Extra labour charges for excavation of soil to pull outthe Electrical cable near energy Meter /Fuse Box/ DG set forre-using the existing cable and making cable connectcions into the switch/ MCB/ Fuse carrier etc., complete as required. |
| 31 | Supplying & making Aluminium cable jointing with suitable size Aluminium Ferrulefor 16 Sq.mm / 25 Sq.mm/35 Sq.mm Aluminium cable including crimping, making proper insulation after jointing complete as required. |