| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 2 | Wiring for light/power plug with 2x4 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed PVC conduite along with 1 no 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as required..2x2.5 sq.mm +1x2.5 sq.mm earth wire |
| 4 | Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as required..2x6 sq.mm +1x6 sq.mm earth wire |
| 5 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 2.5 sq. Mm |
| 7 | Supplying and drawing following sizes of FRLSPVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3x 4 sq. Mm |
| 8 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25MM |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 A switch |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 A socket outlet |
| 12 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 13 | Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc.as required.6Module (200mmX75mm) |
| 14 | Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc.as required.8Module (125mmX125) |
| 15 | Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc.as required.12 Module (200mmX150mm) |
| 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 17 | Installation of exhaust fan in the existing opening, includingmaking good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).8 way , Double door |
| 19 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).12 way , Double door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 21 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 22 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal/ coke and saltas required. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 24 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. Mm |
| 25 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. Mm (clamped with 1mm thick saddle) |
| 26 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). CRCA Sheet Body (Thickness ≥ 0.50 mm)18- 22 watt |
| 27 | LED Street light fixture, powder coated pressure die cast aluminum body (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LEDfixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80 , under voltage and over voltage protection,EMIEMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).72 watt |
| 28 | Online UPS - Input supply: Single Phase, Output Supply : Single Phase Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accoseries are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc.3KVA |
| 29 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 30 | Supply, Installation, Testing and Commissioning of Window type Air.Non Inverter Type,1.5 TR with fixed speed 5 Star BEE rating. conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll / rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc as required complete in all respect as specified of following capacity. Sound level of up to 50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 31 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R- 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only1.5 TR with 5 Star BEE Rating |
| 32 | S/I/T/C of 4 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 33 | Supply of 12\"\" (300mm)sweep 1400 rpm exhaust fan heavy duty complete with shutters blades etc as reqd |
| 34 | S/I/T/C of stand for split AC |
| 35 | S/I/T/C of copper pipe for split AC |
| 36 | S/I/T/C of Drain Pipe |
| 37 | S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner |
| 38 | S&F of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as reqd. |
| 39 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as reqd. |
| 40 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable1.1KV grade Conforming to IS 7098/1988 of following Sizes (a)2X6 SQmm |
| 41 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 42 | SITC of single/ three phase monoblock pump set complete with all accessories workable on 240/415 volts, 50 Hz ac supply (a) 1 HP (0.75 KW) single phase pump set, head from 12-30 metre suction and delivery 25×25 mm. |
| 43 | S/I/T/C of 2MP fixed lensDOME IP Camera with following specifications:-Image Sensor: 1/32MP CMOS or better**Minimum Illumination: 0.08 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate:1-25 fps or better **Lens: 2.8 FixedVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (1920x1080) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 25mOperating Temperature: -20 to 55 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL. |
| 44 | S/I/T/C of 4MP fixed lens Bullet IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOS Minimum Illumination: 0..05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate:20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 30mOperating Temperature: -20 to 55 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL. |
| 45 | SITC of 16 channel NVR with the following specifications:Camera resolution:upto8MPInterface: 1 HDMI, 1VGA minimumCompression :H.265or betterNetwork Throughput :80Mbps or better**USB Port: 2 USB port (USB2.0)minimumHard disk interface: 1 SATA port suitable for 6TB eachProtocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNSOperating temp: -10 to 55 deg CentSafety standard: UL |
| 46 | SITC of 8 TB surveillance HDD |
| 47 | SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch |
| 48 | S/I/T/C of full HD LED Monitor,32inchescomplying to with following specifications:Resolution : Full HD : 1920 x 1080 or betterBacklight : LEDBrightness : 300 NITS min.Contrasts :1200:1 or betterPower supply : 230v + / - 10%, 50 Hzat sitewith connections andalong with all accessories completeas required. |
| 49 | SITC of pigtails 1 meter with spilicing and testing |
| 50 | SITC of LIU Boxes complete with all accessories etc as required of 12 port |
| 51 | Supply Installation testing Commissioning of following wall/ standing M.S powder coated rack with glass front door, fan, steel rear door,power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd.17 U |
| 52 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable |
| 53 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 2 run of cable |
| 54 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 3 run of cable |
| 55 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switch gears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) |