| 1 | As Per RUIDP SOR 2023 |
| 2 | Providing and laying RCC Foundation for octagonal/ Conical street light poles. High msat poles as per Drawing attach at table P-4 with following procedure & All as per pre approved by Engineer in charge for additional technical parameters of products/work refer annexure \"A\" attached with this BSR.A) Excavation of pit for foundation Size upto required depth from ground level.B) Dressing of pit and dry stone pitching 200mm thick includingsupply of stones and preparing surface complete.C) Providing and laying in position cement concrete of M-10 grade of 75mm thickness.D) Reinforcement for RCC work with TMT bars including straightening, cutting, hending, placingin position and binding all complete.E) Centring & Shuttering including sturing, propping etc. and removal of from work for footing and pedstal.F)providing & fixing of 2 no. Required size PLB HDPE pipe & Foundation Bolt with template as per OEM recommendations.G) Providing and laying reinforce cement concrete of M-25 grade in footing and pedestal including curing the foundation for 7 days.H) Providing and fixing nosing Angle 40 mm X 40 mmX 6mm with 2 no. 100 mm long, 10mm dia. lugs on each face pole foundation for octagonal pole from 7 Mtr. to 9 mtr |
| 3 | Supply & Laying following size\" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 50 mm dia. |
| 4 | Plate Earthing as per PWD specification for electrical Works as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 5 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached withthis BSR . 8 SWG copper Wire |
| 6 | Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load and site requirement) 4KV impulse withstand voltage, as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductorline load reversibility, label holding facility , IP 20 contact protection and fitted with existing distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A rating including making connections, testing etc. as required. . OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . Single pole MCB 3 A to 5 A rating |
| 7 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.99% purity copper, class 5 stranding in acc. to IEC 60228 for lower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A or C ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4, , in existing surface or recessed PVC/ MS conduit/casing capping including all as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 2 x 1.5 sq.mm |
| 8 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Unarmoured/ Armoured aluminium cable of 1.1 KV grade as per PWD specification for electrical Works in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench , on existing cable trays or on surface etc. including making necessary connection, testing etc. as required of size and as per points (a), (b), (c), mentioned below:-(a) Material :- H4- Grade aluminium conductor of purity >99.6 % & as per IS:1554 P-I / IS :7098 P – I(b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999 for armouring of cables in armoured cable items , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures.(c) OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities for cables . Appropriate type test certificate / OEM test report shall be submitted . All above as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR. Un-armoured 16.0 Sq. mm 4 core |
| 9 | Supplying and making end termination with heavy aluminium lugs Pin / ring type (as per IS 8309 -1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 1.5 Sq.mm |
| 10 | 6.0 Sq.mm |
| 11 | 16.0 Sq.mm |
| 12 | Providing & laying of Double wall corrugated pipe confirming to IS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required( Excavation of Earth to be paid Extra as required. ) of following Outer Dia. / Inner dia as per IS:4984:1995. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 55/50 mm |
| 13 | Labour charges for Excavation of 30cmx75cm size trench in loose soil including refilling of excavated earth,compaction of earth, making good the same complete as required . |
| 14 | Labour charges for Excavation of 30cmx75cm size trench in tar road including refilling of excavated earth,compaction of earth, making good the same with CC or Tar complete as required . |
| 15 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level. In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc. Depth upto 1.5 m |
| 16 | Providing & Fixing of IK 09 recessed/surface mounting heavy duty Flexi/Row TPN sheet steel not less then 1.2 mm thick Distribution board as per PWD specification for electrical Works ISI marked conforming to IS-13032 & IS-8623 /conforming to IEC 61439-B253. Phosphatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link and din bar,masking sheet, including making internal DB terminations with copper lugs and with detachable gland plate, testing etc. as required complete in all respect.OEM shall have submit NABL /CPRI / ERDA accrediated lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .IP-43 Double door 4 Row 56 Module(14 module per row) |
| 17 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 4 pole Power contactors with following AC 1 Rating 63 Amp |
| 18 | Providing & Fixing of Powder coated CRCA sheet on existing angle iron frame by means of nuts and bolts and making holes , etc. All as er pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 2.0 mm thick |
| 19 | Providing & Fixing in position frame made out of M.S. angle (riveted or welded) as per IS: 2062-2011 finished with two coats of red oxide and two coats of enamel paint including cutting, welding, holes etc. of following sizes as required. All drawing as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 25mm x 25mm x 5mm |
| 20 | Providing & Fixing of metal clad industrial plug top & socket unit with pin and sleeve type copper contact on porcelain/ bakelite base insheet steel( CRCA ) powed coated enclosure as per PWD specification for electrical Works conforming to Is 8623 & IEC 61439-3 (without MCB) including , all as per pre approved by Engineer in charge,making connections,, testing etc.as required .OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .20 A Double Pole (single phase Three pin ) |
| 21 | P & F Of Mechanical /digital time switch having following day/week programme and minimum 100 hours reserve and AC 1 rating of 16- 20 amperes including making connection |
| 22 | Providing & Fixing of ISO certified company made 240/415 V porcelain kitkat fuse (/HBC type) as per PWD specification for electrical Works conforming to IS:2086,1983 on existing board/ sheet including making connections with lugs, testing etc. as required . Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 100 A ,415 V |
| 23 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.99% purity copper, class 5 stranding in acc. to IEC 60228 for lower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A or C ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4, , in existing surface or recessed PVC/ MS conduit/casing capping including all as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 1 x 6.0 sq.mm |
| 24 | PART - B ( H SCHEDULE )NON SOR ITEM |
| 25 | Supply and erection of Decorative Cast Iron pole as per approved design of following length with base plate on the cement concrete foundation of M-15 grade (1:1.5:3) with the help of anchor bolts of grade 6.8 (IS 1367 P III). The pole shall be made of Cast Iron as per IS 210:1993, precision machining and filling job to achieve good finish and a fine coat of primer on each element before assembling. After assembling of each element one coat of primer and two coats of P.U. paint are applied. Approved coloured UV resist coating of mat/ glossy/ metallic finish followed after air drying of pole. The pole shall have a weatherproof flush door and locking arrangements, two arm bracket of length of 1000mm complete in all respect. 9.0 Mtr |
| 26 | P/ F IP-65/ IP-66 protected Decorative street light luminaries of warm White 120W LED WW on existing bracket. Fixture made from powder coated single piece pressure die cast aluminum housing with heat dissipation fins on housing with high power LEDs . Diffuser / glass cover for ensuring IP-65 protection for lamp and control gear compartment, system lumen output of 100 lum/watt high power LED. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards. Smart LED luminaire iwth integrated SLC and 0-10V dimmable driver, 140-270V AC. 10kv built-in surge protector. System life of 50000 burning hours with 70 % of initial lumens maintained. Fixture shall be in CE compliance. Please Enable Macros to View BoQ information |