| 1 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 400 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 2 | [a] Onload Changeover switch I-O-II open execution, 4 Pole, 200 Amps – 01 No. [To be fixed after incomer][b] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 02 Nos [Mains+DG][d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 04 Nos [Outgoing][e] Three line multifunction meter having LCD display - 01 No[f] Current Transformer and Potential Transformer - 01 Set[g]Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 3 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1500 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 4 | [a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release - 0 No [Outgoing][c] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing][d] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 Nos [Outgoing][e] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing][f] Three line multifunction meter having LCD display - 01 No[g] Current Transformer and Potential Transformer - 01 Set[h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 5 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 6 | [a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing][c] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing][d] Three line multifunction meter having LCD display - 01 No[e] Current Transformer and Potential Transformer - 01 Set[f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 7 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1250 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 8 | [a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing][c] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing][d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing][f] Three line multifunction meter having LCD display - 01 No[g] Current Transformer and Potential Transformer - 01 Set[h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 9 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 10 | [a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 03 Nos [Outgoing][c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing][d] Three line multifunction meter having LCD display - 01 No[e] Current Transformer and Potential Transformer - 01 Set[f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 11 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 630 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 12 | [a] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 07 Nos [Outgoing][c] Three line multifunction meter having LCD display - 01 No[d] Current Transformer and Potential Transformer - 01 Set[e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 13 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 450 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- |
| 14 | [a] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing][c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing][d] Three line multifunction meter having LCD display - 01 No[e] Current Transformer and Potential Transformer - 01 Set[f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 15 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 16 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 16 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 25 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 17 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 35 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 18 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 70 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 19 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 120 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 20 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 150 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 21 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 185 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 22 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 240 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 23 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 300 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. |
| 24 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 400 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.[Note for item Nos. 8 to 14 above: Quoted rate is deemed to be inclusive for providing Brass glands at terminals and MS cable route indicators at 50m intervals as directed by the Engineer-in-Charge] |
| 25 | Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in soft/ loose soil complete all as specified and as directed. |
| 26 | Removing excavated material /soil to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed |
| 27 | Returning filling in, including spreading, levelling,watering and well ramming in layers not exc 25cm thickness as in soil complete all as specified and directed. |
| 28 | M & L for laying sub class \"B\" bricks of old size 230mm x 115mm x 75mm for cable protection laid across alignment of cable in trenches complete all as specified and directed. |
| 29 | M&L for Sand filling in trenches using dry river sand as cushioning to under ground cable including spreading, levelling and consolidation complete all as specified and directed.[Note: Punned thickness of sand shall only be measured.] |
| 30 | S & F in repairs PVC insulated 3 core 1.5 Sqmm stranded copper conductor cable for connecting junction box to street light fitting including testing and commissioning complete all as directed |
| 31 | M & L for laying 40mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 32 | M & L for laying 50mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 33 | M & L for laying 80mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 34 | S & F Nature Switch smart timer based Automatic Street light control panel. The panel should be suitable for taking three phase load of 25 KW. The Nature Switch Smart timer should be maintenance free in design and settings accessible through Mobile App [with bluetooth connectivity] and the mobile app should allow the users to customise the ON & OFF timings based on Natural Light (sensor), local sunset / sunrise (Astro) and time. The mobile app should also have facility to set input Voltage range. The smart timer along with suitable power contactor(s) and incoming - outgoing MCBs should be enclosed in a pole / wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonatre enclosure (with hinged Lid) conforming to IP66 protection class 2. The circuit should also have provision for the following:-[a] Manual Operation (i.e sensor bypass option)(b) In 3 Phase model, controlling current phase selection option (at least from two phases)(c) Three phase load of 25 KW (Navdeep-66-25kw3P) with 3 Nos incoming-outgoing MCBs of 63 Amps and 3 Nos contactors (2 pole / 3 Pole) of 40 Amps and copper circuit wiring of 16 Sqmm |
| 35 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 200 Amps rating (04 Nos) for 3 phase 4 wire system of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:-[a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 06 Nos [Outgoing][c] Current Transformer with Ammeter - 01 No[d] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 36 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 200 Amps rating (04 Nos) for 3 phase 4 wire system of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:-[a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 06 Nos [Outgoing][c] MCCB, 63 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 01 No [Outgoing][d] Current Transformer with Ammeter - 01 No[e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 37 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 200 Amps rating (04 Nos) for 3 phase 4 wire system of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:-[a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer][b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 04 Nos [Outgoing][c] MCCB, 63 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 01 No [Outgoing][d] Current Transformer with Ammeter - 01 No[e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) |
| 38 | Dismantling cross arms of MS channel or angle sections, etc complete all as directed |
| 39 | Dismantling insulators any type and size complete all as directed |
| 40 | Taking out old unserviceable of any size complete all as directed |
| 41 | Dismantling of ACSR or AAC conductors of any type complete all as directed |
| 42 | S & F Street light fitting LED type of minimum 90 Watt, pressure die cast aluminium housing LED street light luminaires with IP66 with accessories including bracket made of 40mm bore GI medium grade pipe of 1.5m long bent to shape fixed with Two Nos of MS clamps of suitable size, bolts, nuts and washers duly painted with two coats of aluminium paint over a coat of red ixide zinc chrome primer on steel surfaces including taking down old fittings alongwith brackets complete all as specified and as directed by the Engineer-in-Charge. |
| 43 | S & F FRP Moulded / Polycarbonate cable looping box of minimum size 250x250x115mm complete with electrolytic aluminium bus bar of suitable size and capacity for 3 phase and neutral fixed on ebonite insulator and one MCB 6 Amps complete all as directed |
| 44 | Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to galvanised earth strip 25x4mm [Earth Lead] and GI pipe 40 mm dia light Grade for earthing lead protection to the extent of maximum 7.5m, earth plate electrode surrounded by 150mm thick packed layers of charcoal and common salt filled in alternate layers, connected to the plate by means of GI bolts & nuts complete all as per Electrical plate No. 3 of SSR Part – I, connected to earthing test point including testing on completion including PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm angle iron, MS funnel with 20 mm bore medium grade GI Watering pipe, wire mesh, earth work excavation, returning filling, removal of surplus soil etc. including removing old unserviceable earthing set complete all as specified and as directed. |
| 45 | M & L for preparation of old painted surfaces of street light poles of 9m height by complete scrapping with sand paper, cleaning and applying 2 coats of aluminium paint over a coat of red oxide primer including numbering of poles in circle mentioning area and pole number including providing Five strips of Yellow Black (YBYBY) strips (each strip of 25cm) on the pole from coping and white water based paint on the coping of the pole complete all as directed |
| 46 | M & L for boring holes horizontally under road, pavements, hard standing by trenchless technology using sounding technique and necessary machine including inserting and providing 150mm dia HDPE pipe suitable for 0.4 mpa working pressure complete all as directed. |