| 1 | Excavation in trenches not exc 1.5m in width and 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25cm complete all as specified and as directed. |
| 3 | Removing excavated material / soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | Supply and layfine sieved excavated dry soilcushioning spreading levelling for cable trenches complete all as specified and directed. (Note: Punned thickness only shall be measured and paid.) |
| 5 | Supply and laying well burnt bricks sub class \"B\" in trenches for cable protection of U/G cable complete all as specified and directed. |
| 6 | Taking out the existing PVC/XLPE, 1100 volts grade,LT UG electric cable of size 6 sqmm x 2 core fromtrenches/ walls (or) passing through pipes/in floor removing the unserviceable fault cable andcarefully stacking the serviceable cable for reusing all as specified and directed by the Engr-in- chargeNote:- Excavation and Earth work shall be measured and paid separately under appropriate items |
| 7 | All as per item No.6abovebut6 sqmm 4 core |
| 8 | All as per item No.6 abovebut10 sqmm 4 core |
| 9 | All as per item No.6abovebut16 sqmm 4 core |
| 10 | All as per item No.6abovebut25 sqmm 4 core |
| 11 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleeves etcandsize 6sqmm 2 corecomplete all as specified and directed by Engr-in Charge . |
| 12 | All as per item No. 11but obtained from item No. 7above but 6 sqmm 4 core |
| 13 | All as per item no.11 but obtained from item no. 8 above but 10 sqmm 4 core |
| 14 | All as per itemno.11but obtained from item no. 9 but 16 sqmm 4 core |
| 15 | All as per item no.11 but obtained from item no. 10 above but 25 sqmm 4 core |
| 16 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 6 sqmm 2 core. |
| 17 | All as per item no. 16above but 6 sqmm 4 core |
| 18 | All as per item no. 16above but 10 sqmm 4 core |
| 19 | All as per item no. 16 above but 16 sqmm 4 core |
| 20 | All as per item no. 16 above but 25 sqmm 4 core |
| 21 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for following size10 to 16 sqmm 2/4core complete all as specified and as directed. |
| 22 | All as per item No 21 abovebut 25 to 50 sqmm 3.5/4core |
| 23 | S & L intrenches /fixed on walls by suitable clamps and jointing complete GI pipe light grade of size 50mm diafor cable protection in repairs complete all as specified and as directed. |
| 24 | S & L intrenches /fixed on walls by suitable clamps and jointing complete GI pipe light grade of size 25mm dia in repairs complete all as specified and as directed. |
| 25 | S & L intrenches /fixed on walls by suitable clamps and jointing complete GI pipe light grade of size 40mm dia in repairs complete all as specified and as directed. |
| 26 | S/F in repairsstreet light Junction box PVC weather proof suitable for accommodating and including heavy duty PVC connector block30 amp capacitythree phase with one number single poleMCB 06 Amps complete including fixing to pole with suitable brackets, bolts/nuts in connecting cable in testing complete all as directed. |
| 27 | M & L for Sub main wiringcomplete with two runs of 1.5 sqmmPVC insulatedunsheathed single core multistrand copper conductorcable of 1100 volts grade drawn through new non metallic rigid PVC casing capping on wall alongwith accessories fixed on walls/floors/ceilingwith one run of 1.5 sqmm PVC insulatedunsheathed copperconductorcable as earth continuity conductor including taking down complete all as specified and directed.Note:- Two runs of PVCinsulatedcable 1.5 sqmm+ one run 1.5 sqmmof earth wire and one run of conduit including accessories shall be measured as one length. |
| 28 | Taking down the existingmounted LED security lights of gate lights/flood lights/ground lights of any size etc in carrying out repairs including checkingluminousreplacement of defective spares parts andchecking all connection to make the fitting serviceable including replacement of connection while from junction box to fittings and rectifying the same after attending repairs complete all as specified and directed Note: Spare parts required for repairing the lights will be measured and paid seperatelyunder relevenat items |
| 29 | Supply only LED Driver 25 watts comnplete all as specified and directed |
| 30 | Supply only LED Driver 45 watts comnplete all as specified and directed |
| 31 | Supply only 1.5 sqmm3 core copper conductormultistrandedcableincluding taking down complete all as specified and directed |
| 32 | Supply only 15 mm PVC pipe with suitable clamp and nuts/boltsincluding taking down complete all as specified and directed |
| 33 | Taking down the exsiting garden/bldg security light fittings of any type /description and depositing where directed complete all as specified and directed by Engr-in-Charge |
| 34 | S&Ffor 25 W new generation energy saving environmental friendly long life versatile pressure die castaluminium IP-66streetlightwith high power LED as light source complete all as specified and as directed. Make Bajaj (Cat No. NEXO 30L WH PO PC SD) orits techno commercial equivalent in Havells /Philips /Crompton |
| 35 | S&Ffor 45 W new generation energy saving environmental friendly long life versatile pressure die castaluminium IP-66 streetlightwith high power LED as light source complete all as specified and as directed.MakeBajaj (Cat No. NEXO 54L WH PO PC SD) orits techno commercial equivalent in Havells /Philips /Crompton |
| 36 | S&F garden light 8 W, new generation energy saving environmental friendly long life aesthetically designed aluminium landscape luminairefor diffused lighting with high power LED as light source completeall as specified and as directed .Make Havells cat No BAMBOOBL8WLED830SSYMTOPCM(1.0m) orits techno commercial equivalent in CG/Philips /Bajaj |
| 37 | S&F garden light 8 W,new generation energy saving environmental friendly long life aesthetically designed aluminium landscape luminairefor diffused lighting with high power LED as light source completeall as specified and as directed.Make : Havells cat No BAMBOOBLS8WLED830PSYMTOPCM(.60m) orits techno commercial equivalent in CG/Philips /Bajaj |
| 38 | Supply, fix, test and commissioning LEDPost top lanternluminaires outdoor type 45 Watts new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP66 roadway luminaire with high power LEDs as light source and electronic driver suitable for operation on AC single phase 220-240 Volts, 50 HZ supply, including provision of two single core 1.5sqmm copper conductor PVC insulated, 1100 Volts, cable not less than 8 meter length etc, connecting from junction boxes to poles completeall as directed . Make:Havells (Cat No. RUBYPT45WLED757PSYMTOPC)orits techno commercial equivalent in CG/Philips /Bajaj |
| 39 | Supply, fix, test and commissioning LEDPost top laternluminaries outdoor type 25 Watts new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP66 roadway luminaire with high power LEDs as light source and electronic driver suitable for operation on AC single phase 220-240 Volts, 50 HZ supply, including provision of two single core 1.5sqmm copper conductor PVC insulated, 1100 Volts, cable not less than 8 meter long etc, connectiing from junction boxes to poles completeall as directed. Make:Havells (Cat No. RUBYPT25WLED757SSYMTOPC) orits techno commercial equivalent in CG/Philips /Bajaj |
| 40 | S&F in repair ceiling rose , polycarbonate, isolated bodywith 2 to 3 terminalscomplete all as specified and directed. |
| 41 | Supply and fixforbracket for single street lightfittingwith GI pipe medium grade 40 mm dia 1.5 m long bent to shape and double clamped with fabricated MS clamps as directed and fixedto outside wall with bolts and nuts including paintingand taking down old unserviceable complete all as specified and directed by Engr-in Charge |
| 42 | Supply & Layandconnectingup Weather proof cablewith aluminium conductor 1100V grade of size10sqmm 2 corecomplete all as specified and directed by Engr-in Charge . |
| 43 | Earthing complete with galvanisedsteel earth plate electrode of size60cm x 60cm x6.3 mm thick buried directly in ground( earth pit not less than 2.25 m deep below the normal ground level) with top edge of the plate not less than 1.5m below normal GL connected to GI earth strip of size 25x4 mm by means ofbolts, nuts, check nuts washers of GI or steel all asshown in electrical plate No-5 of SSR Part I connected to machinery/equipments installed power house/sub station all as specified including testing on completion complete all as specified and as directed. Note: The unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete in addition to item No 1(a) to (e) of preamble ( Notes) Under sub heading earthing specified on SI page NO-451 of SSR Part-II 2020. |
| 44 | S & F MCB distribution board made ofCRCA sheet, powder coatedpaint conforming to IS 13032, single door fixed in switch boards/wall at various places of capacity 240 volt 2 way MCB DB, SPNconforming to IP 38 protectionincluding taking down complete all as specified and directed. |
| 45 | S&F MCB of Single pole of rating 6 to 32 Amps B curve 10 KA 240 Volts including taking downcomplete after taking proper disconnecting of electric supply properly andmaking good surfacecomplete all as specified and directed. |