| 1 | Design, Fabrication, supplying and erection of 9 Mtrs long hot dip galvanized, Octagonal pole with BSEN 10025 GRADE S355JO steel plate for shaft, IS 2062 for base plate with door opening arrangements, including suitable boards, Bakelite sheet and MCB’s as per IS specifications suitable to withstand the wind speed of 47 m/s for 9 Mtr pole in single section and single joint welded as per IS 9595/IS10178AWS having dimensions bottom 155mm dia, top 70mm dia with 3mm thick suitable base plate 260x260x16mm, PCD 250 and foundation bolts M24x750mm long 4nos “J” type along with template and the pole shall be hot dip galvanised in single dipping with not less than 65micron as per ASTM-A123 and 153 etc. (excluding foundation) as per drawing appended. a) 9m - Top 70mm and Bottom 155mm dia. (As per Technical Specifications) |
| 2 | Supplying and fixing of Hot dip Galvanized M.S. Bracket suitable for outdoor Luminaries and mounted on octagonal pole using necessary bolts, nuts etc., complete.a) Single Arm Bracket with 1500mm Standard 40/50mm dia. (As per Technical Specifications) |
| 3 | Supplying and fixing of Hot dip Galvanized M.S. Bracket suitable for outdoor Luminaries and mounted on octagonal pole using necessary bolts, nuts etc., complete.a) Double Arm Bracket with 1500mm Standard 40/50mm dia. (As per Technical Specifications) |
| 4 | Supply and fixing of hot dip Galvanized MS circular bracket of ID 750mm, fabricated with 40mm dia pipe, head frame & supports, mounting plates suitable for mounting 4 Nos. outdoor LED flood light luminaries on 9 mtr octagonal pole using necessary bolts, nuts etc. Complete. All the hardware shall be GI/stainless steel only |
| 5 | Supply of LED Streetlight luminaire-200W with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti-glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output Rated life Burning Hrs 50000 hr @Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT >5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor > 0.9 with mains, Surge Protection-Min 5KV along with Over voltage / Overload, short circuit / miss- wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50 / 60Hz application. Compliance to IS10322/IEC60598, LM79&LM80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools.LED Light fixture with 200W System Power consumption. LED Efficiency > 1301m/w, nominal CRI > 75. Luminaire manufacturer should be accredited by NABL / CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark / name shall be Engraved / Embossing on the die cast housing / Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer |
| 6 | Supply of LED flood light luminaire - 200W with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti-glare clear diffuser with Injection moulded polycarbonate / clear glass material, delivering superior light output Rated life Burning Hrs 50000hr @ Lumen Maintenance of 70%, CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor > 0.9 with mains, Surge Protection – Min 5KV along with Overvoltage / Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia. of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V, 50/60 Hz application. Compliance to IS10322 / IEC60598, LM 79 & LM80 Adherence with RoHS.UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with 200W System Power consumption. LED Efficiency > 130 1m/w, nominal CRI > 75.Luminaire manufacturer should have in- house facility accredited by NABL / CPRI & any Government certified agency & Design & Development facility certified by ISO9001: 2008. Housing with supplier word mark / name shall be Engraved / Embossing on the die cast housing / Body part Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer |
| 7 | Providing foundation for 9 mtrs Octagonal pole including Earth Excavation and making of RCC foundation drawing using M 20 concrete, steel reinforcement, shuttering complete as per pole suppliers approved foundation drawing or depending upon site condition. (All supply materials included in this item) |
| 8 | Replacement of existing LED street light/floodlight fittings & fixing new fittings |
| 9 | Supply and drawing Flexible Multicore cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS:8130-1984 and (virgin) PVC insulation sheathed suitable for working voltage up to 1100 volts as per IS-694:1990. a) 3C x 2.5 sq.mm |
| 10 | Supply of 1.1 KV LT Aluminium UG cable XLPE insulated. PVC extruded inner sheath armoured UG LT cable as per IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14Ohms/Kms as per IS-3975. a) 4C x 16 sq.mm (As per Technical Specifications) |
| 11 | Supply of 1.1 KVXLPE insulated, PVC extruded inner sheath armoured UG LT cable as per IS-1554 (Part-I) or IS-7098 (Part-1), Armouring strip thickness and resistivity as per IS-3975.a) 3.5C x 50 sq.mm (As per Technical Specifications) |
| 12 | Labour charges for laying of 1.1 KV class XLPE LT UG cable in existing trench / GI pipe / stoneware pipe / on pole/ on concrete wall as required. a) 4C x 16 sq.mm |
| 13 | Labour charges for laying of 1.1 KV class XLPE LT UG cable in existing trench / GI pipe / stoneware pipe / on pole/ on concrete wall as required. a) 3.5C x 50 sq.mm |
| 14 | Earth work excavation for cable trench of 0.5 to 0.75 Mtr. Width and Depth upto 1 Mtr. Including trial pits, depositing on bank upto a lead of 50mtr. Supplying and Displaying necessary Danger boards and Lighting, refilling the trench to the required ground level and consolidating etc., complete. a) In Hard soil |
| 15 | Supplying and laying Double walled corrugated DWC HDPE pipe as per IS 14930 part ll with necessary connecting sockets, couplings, Tees, bends, End caps of same materials in existing trench / duct / pole / on wall / on black stone wall with SS saddles / on poles / structure drawing the cable with supply and fixing DWC pipe with Aluminium clamps and stainless steel screws as required for drawing the cable as complete job.a) 63mm OD / 50mm ID |
| 16 | Supplying and making end termination with glands, lugs of LT cable. a) 4C x 16 Sq.mm |
| 17 | Supplying and making end termination with glands, lugs of LT cable. a) 3.5C x 50 Sq.mm |
| 18 | Supply and fixing of spiral Earth Electrodes as per standard technical specifications as per MESCOM |
| 19 | Releasing and shifting of MESCOM RCC poles from site to 33KV MUSS |
| 20 | Providing and filling sand in excavated trench to cover already laid UG cable to a depth of 150mm around the cable |
| 21 | Supply & laying of RCC semi cut pipe (C-CUT) in existing trench over the cable. Size: 150mm dia., 25mm thick |
| 22 | Providing / stone masonry foundation for control panel and the dimension of the foundation 800(W)x1000(H)x400(D) mm and the gap between the pillars is 350mm for cable connection to the control panel. The foundation starts 300mmbelow the ground after making 100 mm stone soling and curing etc. The panel should be stand on the 4 stainless steel bolts (12mmx6”) each bolt with four nuts & washers at 50mm height from the foundation and complete |
| 23 | Supply of SS-304 grade stainless steel (IP-54) enclosure of size 600(W)x760(H)x210(D)mm with rain canopy single door type with cam lock door sealing gasket and gland plate with required openings etc. Material 2mm thick and mounting plate 2.5mm thick comprising the following components with control wiring 10sq.mm copper wire for lighting circuit. Work including supply and fixing of the components 1 No. 125 Amps MCCB 4 pole 35KA as Incomer and 3 Nos 63 Amps MCCB for out goings, 50amps CBT connectors 16 Nos. 1 No. MNX 50amps contactor 3 pole with 1 No. timer 24 hours & 1 No. Auto manual selector to bypass the Contactor |
| 24 | Charges for trimming of tree branches wherever street light poles erected under the tree |
| 25 | Supply of 30M High Mast shaft in three sections suitable for 50 m/sec wind speed, as per IS:875 part-III, with head frame, winch mounting bracket, luminaries carriage suitable to install 10 No’s 500W LED Flood light luminaries in symmetrical arrangement. As per Technical Specifications |
| 26 | Supply of raising, lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightning finial. As per Technical Specifications |
| 27 | Supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template. A per Technical Specifications |
| 28 | Supply of LED type double dome aviation obstruction light.As per Technical Specifications |
| 29 | Construction of shallow foundation with M25 grade concrete for the high mast considering the safe soil bearing capacity at site as 10 T/sq.mtr at 2-meter depth with all materials and labour. As per Technical Specifications |
| 30 | Erection of the high mast with the help of suitable tools and plants, wiring of luminaries with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5sq.mm, lugs, MCB and all labour as a complete job |
| 31 | Supply, installation, testing & commissioning of 500 W LED Flood light fittings complete with driver and necessary accessories as required to maintain average 25 Lux for keeping minimum uniformity. Bidder to submit illumination design with location of the Mast. Housing material of the flood light should be Matt Grey powder coated pressure Die-cast aluminium housing, with heat resistant tempered glass cover. System wattage of the luminaire should be within500W and system lumen output should not be less than 120 lm/w. And total luminous flux shall be 60000 lm (+/- 10%). The fixture should be available with choice of beam angles of NB A3 -25˚. Fixture should be suitable for a input voltage range of 120 V to 277 V AC with input power supply of 230 V AC ± 10 %. Lifetime should be at least 50,000 burning hours. Ingress protection class of IP 66 and impact resistance of IK 08. Bidder to submit LM79-80 report of the luminaire from NABL / Govt. Approved test house along with BISS certificate as required. As per Technical Specification |
| 32 | Supply of High Mast control panel of SS-300 Grade Stainless steel Enclosure of size 600(W) x 760(H) x 210(D) mm with rain canopy, single door type with cam lock door sealing gasket and gland plate with required openings etc. Material 2mm thick and mounting plate 2.5mm thick comprising the following components with control wiring 10 Sq.mm copper wire for lighting circuit and 2.5 Sq.mm copper wire for motor circuit and termination with suitable lugs complete Etc. As per technical specifications |
| 33 | Design & construction of RCC barricade wall around the high mast by using M 20 concrete with 10 mm vertical rod at a gap of 200 mm double layer and 3 rows of 8 mm horizontal rod by keeping 200 mm inner radius from centre of high mast foundation as per the specifications. As per Technical Specifications |
| 34 | Providing RCC / Stone masonry foundation for the High Mast control panel and the dimension of the foundation is 800(W) x1000(H) x400(D) mm and gap between the pillars is 350 mm for cable connection to the control panel. The foundation starts 300mm below the ground after making 100mm stone soling and height of the foundation 500mm above the High Mast foundation level and curing etc. and the panel should be stand on the four Stainless steel bolts (12mm x 6”) and each bolt with four nuts & washers at 50mm height from the Foundation and complete |
| 35 | Installation and commissioning of the Stainless-steel high mast control panel by terminating the required cables such as Incomer, lighting and motor. Work also including supply and fixing of required materials Such as glands lugs etc. complete |
| 36 | Supply and laying Reinforced Cement Concrete pipe light duty NP2 for culverts, roadway utilities and crossings as per IS458:2003 in Single row including pointing ends and fixing collars with cement mortar 1:2 including cost of all materials, labour, curing complete as per specification. a) 300 mm dia. |
| 37 | Supplying, fixing and wiring earth electrode for panel using 40 mm dia, 2.90 mm thick GI pipe 2.5 Mtr long with funnel with mesh and suitable size reducer fixed on the top of the Electrode. The funnel should be enclosed in a CC chamber of 400x400x400 mm with cast iron cover. The electrode shall have staggered holes of 12mm dia and the electrode covered 150 mm all-round with alternate layers of salt and char coal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts |
| 38 | Supplying and running GI strip for grounding connections, using necessary fixing materials as required.a) 25 x 6 mm GI strip |
| 39 | Supplying and installing cable route marker made up of RCC Block of size 100cm (H) x 50cm (W) x 6cm (D) indicating Embossed text as “NMP LT Cable” with yellow paint a red colour letters and fixing with cement concrete |