| 1 | Supply ,laying and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with stranded aluminium conductors, 1100 volts grade of of size 35 Sqmm 3.5 core laid in trenches/on walls with saddles or clamps/cable tray/HDPE pipe/cable duct etc complete all as specified and directed |
| 2 | All as per item No01 here-in-before but cable of size 16 Sqmm 4 core complete all as specified and directed |
| 3 | Excavation in trenches soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out excavated soil/sand/ unseviceable LT Cable for laying of cable complete all as specified and directed. |
| 4 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in hard /loose soil complete all as specified and directed |
| 5 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed |
| 6 | Supply and laying of 40 mm bore High density polyethylene pipes(HDPE) PN 10 including necessary accessories such as bends,tee,couplers etc to belaid in trenches/wall/road crossing for cable protection of suitable length as per site requirement complete all as specified and directed |
| 7 | Cutting existing road/hardstand/concrete blocks/slabs/brick work or stone masonry of any type by using crow bar chisel up to adepth of 45 cm for laying GI pipe including making good the surface by returning filling watering ramming in layers cold mix bitumen over 200 mm thick hard core of broken bricks/stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed |
| 8 | Material and labour for GI tubing medium grade (ISI marked) with all fitting/acessories for protection of cable on pole/wall and under road crossing including clamps, nut bolt etc complete all as specified and directedofsize 40mm dia(make: prakash surya/jindal/TATA) |
| 9 | Supply and fix, cable jointing kit for straight throughheat shrinkable typejointwith jointing material andall connected accessories suitable forXLPE armoured aluminium conductorcable 1100voltsgrade of size 3.5/4 core 16 sqmm complete all as specified and directed |
| 10 | All as per item No 9here-in-before but of size 3.5/4 core 35 sqmm complete all as specified and directed |
| 11 | Supply and fixing MCCB 4 pole, 63 Amps,415V, 16KA on the existing LT panels/enclosure all as per site requirment complete all as specified and directed |
| 12 | Supply and fixing on MCCB enclosure \"L\" frame, 4 pole, for fixing of MCCBs on wall/LT panel etc complete all as specified and directed |
| 13 | Material and labour for earthing completewith galvanized iron or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to galvanized iron strip 32x6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-Iand specified includingprovision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation andearth work & connecting the earthing to an earthing test point /transformer nuetral/body/ Lt panel etc. and testing on completion, complete all as specified and directed |
| 14 | Material and labour for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.as required of 32x6mm galvanised iron strip complete all as specified and directed |
| 15 | Supply and fixingof thermoplastic socket distribution board of make Hensel or equivalent in other approved makes,environment friendly,recyclable,UV resistent,halogen & silicon free anti acid & anti corrosive,ingress protection of enclosure is IP 65 in avccordance with IEC60529,(Since the IP rating of switch gear is IP54,total IP rating of the system shall be considered as IP54) for better safety the polycarbonate enclosure is fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 Part 3,UL subject 94 for flammability V-2,tested at glow wire test for 960 deg Cent and complete marking on the board for identification and comprising of the following:-Incomer32A 4P MCCB - 01 NoOutgoing6/16 Amps Domestic socket with switch - 06 NosWall mounting type of size 750x550x350 mm |
| 16 | Design,fabrication,supply and installation of cubicle type, totally enclosed, double door, outdoor type (CPRI Approved vendor IP 65) floor mounted,fully stainless steel of SAE 316 grade built forced cooling feeder pillar fabricated in compartmentalised design made out of 2.0 mm thick stainless steel sheet of 316 grade suitable for operation on 415 volts,3 phase,3 wire,50 Hz AC supply , 200 Amps,TPN aluminium bus bars of high conductivity,DMC/SMC bus bar supports with bottom base channel,including necessary foundation,stickering of feeder names, with the following incomers & outgoings complete all as specified and directed |
| 17 | i) Aluminium bus bar TPN 200 Amp of suitable length and section covered with coloured heat shrinkable anti track insulation tape finished thickness not more than 1mm and fixed on epoxy base post insulator of both dia and height not less than 40mm- 01 Set. ii) MCCB, 4P, 125 Amp, Ics 27 kA, 415V, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No (Incomer).iii) MCCB, 4P, 40Amp, Ics 16 kA, 415V, 50 Hz with adjustable thermal and fixed magnetic release-06 Nosiv) MCB, SPN, 32 Amp, Ics 10 kA, 230V, 50 Hz, \"C\" Curve type- 02 Nos v) Indicator lamp RYB- 1 Set. vi) Multifunction meter digital compatible to measure voltage, current, PF, frequency with 3 lines display LCD in 96x96 sqmm flush mounted case, accuracy class 1.0- 01 No.vii) Control wiring with suitable size copper conductor stranded wire/cable.viii) Danger notice plate riveted on the outer body 440 volt. |
| 18 | Supply and install GI 300 mm perforated cable tray of sheet thickness 1.6mm and dimensions of 300x50 mm fixing the cable tray along the walls and running the cables through the tray including all accessories such as nuts,bolts,clamps for fixing the tray on the walls complete all as specified and directed |
| 19 | Material and labour for dismantling floor,hearth or wall tiling including cement mortar bedding (but not backing) removing servicable tiles to store and rubbish off the premises complete all as specified and directed |
| 20 | Providing and laying 80 mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved color,design & pattern as in footpath,parks,lawns,drive ways or light traffic parking etc of required strength,thickness & size/shape made by table vibratory method using PU mould,laid in required color & pattern over and including 50 mm thick compacted bed of coarse sand,compacting and proper embedding/laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,filling the joints with fine sand and cutting of paver block as required size and pattern,finishing and sweeping extra sand complete all as directed. |
| 21 | Material and labour chequered cement concrete tiles 20cmx20cmx25cm thick,set,jointed and pointed in neat cement slurry with grey cement and no pigment in floors complete all as specified and directed |
| 22 | Supply and fixing of cable trays perforated with cover of Hot dip galvanised sheet offollowing sizes onexternal/internal walls parallel/perpendicular with all accessories including anchor fastener, couplers, threded rod, rungs, horizontal bend, vertical bend inside and outside, tee,Hot dip GI strips, center reducer, right and left hand reducer, cross andnecessary brackets,studs, nuts, bolts of hot dip galvanised steel of suitable size and length etc. including painted with anti corosion paint and taking down old one all as per site requirement:- |
| 23 | Cable trays size 250 mm x 50 mm x 1.6 mm (width x depth x thick) |
| 24 | Cable trays size 200 mm x 50 mm x 1.5 mm (width x depth x thick) |
| 25 | Cable trays size 150 mm x 50 mm x 1.5 mm (width x depth x thick) |
| 26 | Cable trays size 100 mm x 50 mm x 1.2 mm (width x depth x thick) |
| 27 | Cable trays size 80 mm x 25 mm x 1.1 mm (width x depth x thick) |
| 28 | Supply and Fixing on walls/ on ceilings of heavy duty PVC casing capping with all accessories like joints, caps, corners, etc of following sizes:- |
| 29 | PVC casing cappingsize 50mmx50mm |
| 30 | PVC casing cappingsize 32mmx16mm |
| 31 | PVC casing cappingsize 25mmx12mm |
| 32 | Supply and fixing of PVC conduit medium grade of size 40 mm dia for mechanical protection of cablesand clamping the conduit properly on wall/perimeter wall/floor etc with necessary clamps, nuts, bolts and washers,junction boxes and allignin proper sequencecomplete all as specified and directed and as per site requirement. Note:- Minor spares such as drilling machine,clamps ,nuts and bolts arealso deemed to be included in the abovequoted rates. |
| 33 | Supply and fixing of PVC conduit medium grade of size 32 mm dia for mechanical protection of cablesand clamping the conduit properly on wall/perimeter wall/floor etc with necessary clamps, nuts, bolts and washers,junction boxes and allignin proper sequencecomplete all as specified and directed and as per site requirement. Note:- Minor spares such as drilling machine,clamps ,nuts and bolts arealso deemed to be included in the abovequoted rates. |
| 34 | Supply and fixing of PVC conduit medium grade of size 25 mm dia for mechanical protection of cablesand clamping the conduit properly on wall/perimeter wall/floor etc with necessary clamps, nuts, bolts and washers,junction boxes and allignin proper sequencecomplete all as specified and directed and as per site requirement. Note:- Minor spares such as drilling machine,clamps ,nuts and bolts arealso deemed to be included in the abovequoted rates. |
| 35 | Supply and Fixing of cable cap of size 25-40 mm complete all as specified and directed. |
| 36 | Material and labour for 65 mm bore High density polyethylene pipes (HDPE) PN 10 laid in trenches/Wall/drain for suitable length as per sire requirement complete all as specified and directed |
| 37 | Material and labour for 50 mm bore High density polyethylene pipes (HDPE) PN 10 laid in trenches/Wall/drain for suitable length as per sire requirement complete all as specified and directed |
| 38 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 4 core 25 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables, complete all as specified and directed |
| 39 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 50 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables complete all as specified and directed |
| 40 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 70 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables complete all as specified and directed |
| 41 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 95 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables complete all as specified and directed |
| 42 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 120 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables complete all as specified and directed |
| 43 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 150 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables, complete all as specified and directed |
| 44 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 185 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables, complete all as specified and directed |
| 45 | Supply,laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 240 sqmm in trench/duct/floor/wall provision of saddle and lugs,joints etc including taking down of old UG cables complete all as specified and directed |
| 46 | Supply and fixing cable straight through jointing kit for 1.1 KV (earthed) grade cable,heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured conductor cable of size 25 to 50 sqmm, complete all as specified and as directed |
| 47 | Supply and fixing cable straight through jointing kit for 1.1 KV (earthed) grade cable,heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured conductor cable of size 70 to 150 sqmm,complete all as specified and as directed |
| 48 | Supply and fixing cable straight through jointing kit for 1.1 KV (earthed) grade cable,heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured conductor cable of size 185 to 240 sqmm,all as specified and as directed |
| 49 | Supply and laying un-reinforced precast concrete cable cover of class LV, type - 1, flat , size 250 mm X 150 mm X 40 mm laid in trenches for protectionofcable complete all as specified and directed . |
| 50 | Material and labour for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on or under road crossing including clamps,nut bolt etc all as specified and directed of size 80mm dia complete all as specified and directed . |
| 51 | Material and labour for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on or under road crossing including clamps,nut bolt etc complete all as specified and directed of size 50mm dia |
| 52 | Material and labour for riddled soil filling in trenches for coushining of LT cables .Punning after filling complete as specified and as directedNote:-The punned thickness of riddled soil shall be measured and paid. The riddled soil of thichkness 15 cm before cable laying and 8cm after laying of cable shall be done and punned to thickness of min 18 cm”. |