| 1 | Supply, Installation, Testing & Commissioning of 11/0.433kV, 3-phase, 200KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate. Transformer should have arrangement for vertical Take off Dismentaling of old 100KVA transformer and loading/ unloading to Divisional Store. |
| 2 | Supply, Installation, Testing & commissioning of 9 Mtr. Long Pole (ST-410 SP33) |
| 3 | Supply, Installation, Testing & commissioning of ACSR 0.05 Conductor (50 mm² ACSR Conductor) |
| 4 | Supply, Installation, Testing & commissioning of G I Channel/ Angle/ Flat iron for cross, braces of sizes including clamps and GI Nut Bolts with all accessories |
| 5 | Supply, Installation, Testing & commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 6 | Supply, Installation, Testing & commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 7 | Supply, Installation, Testing & commissioning of 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 8 | Supply, Installation, Testing & commissioning of Gapless Surge Arrestor,9 kV, 10 kA,LA with polymer housing, Stn. Type |
| 9 | Supply, Installation, Testing & commissioning of 300 mm2 Single Phase Cable, 1.1K V Grade, PVC Insulated Al. Stranded Conductor FRLS type |
| 10 | Supply, Installation, Testing & commissioning of LT Fuse set of standard make & quality. |
| 11 | Supply, Installation, Testing & commissioning of Al-Thimbles |
| 12 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover as per REC standards. |
| 13 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm as per REC Standards. |
| 14 | Providing of Painting of Poles Red Oxide as per standards |
| 15 | Providing of Painting of Poles Aluminium Paint as per standards (double coat) |
| 16 | Providing of Cement bottoming of poles 1:2:4 mix as per REC standards 0.48cum /pole |
| 17 | Providing of Danger Plates with Clamps for 9 meter HT Poles as per REC standards. |
| 18 | computerized site plan of work\"s depicting complete details of works along with land marks on 12X18 inch good quality paper sheet |
| 19 | GEO tagged photographs of size not less than 8x6 inches on good quality photopaper (along with soft copy). |
| 20 | Sign Board (3X2) sq. feet supported on angle iron post with cocrete base mentioning name of work /scheme, year (2025-26), implementation agency (Executive Engineer KPDCL Division Pulwama) and name of contractor at the site of substations. Please Enable Macros to View BoQ information |