| 1 | Schedule-A (EM Work) |
| 2 | Supply, installation, testing and commissioning of high wall split type inverter air conditioner of capacity 1.5 TR, BEE 5-star rated, complete with indoor and outdoor units, copper tube condenser coil, cordless remote control, duly mounted on MS powder-coated outdoor unit stand, suitable for single-phase electric supply, including all necessary accessories, connections, and making good to the disturbed surfaces, complete all as specified and as directed. |
| 3 | Supply, installation, testing and commissioning of high wall split type inverter air conditioner of capacity 2.0 TR, BEE 5-star rated, complete with indoor and outdoor units, copper tube condenser coil, cordless remote control, duly mounted on MS powder-coated outdoor unit stand, suitable for single-phase electric supply, including all necessary accessories, connections, and making good to the disturbed surfaces, complete all as specified and as directed |
| 4 | Supply and fixing of voltage stabilizer for automatic operation, single-phase, naturally air-cooled, indoor type, suitable for input voltage variation from 170V to 250V, delivering stabilized output voltage of 230V ±2.5%, of capacity 5 KVA, complete all as specified and as directed |
| 5 | Supply and fixing of voltage stabilizer for automatic operation, single-phase, naturally air-cooled, indoor type, suitable for input voltage variation from 170V to 250V, delivering stabilized output voltage of 230V ±2.5%, of capacity 4 KVA, complete all as specified and as directed. |
| 6 | S&F nylon braided PVC pipe of size 20mm dia outer suitable for split Ac drain including fixing accessories such asclaps screws rawl plugs etc complete all as specified and directed. |
| 7 | M&L for suction discharge copper tubing of size 1/2 inch and 1/4 inch dia and 0.5mm thickness from indoor unit to outdoor unit of split AC 2 TR capacity including soldering and brazing complete all as specified and directed. Note- Suction and discharge copper tubing together will be measured as one unit of running meter. |
| 8 | All as per above item but copper tubing size 5/8 inch and 3/8 inch dia and 0.5 mm thickness. |
| 9 | M&L for insulating the suction and discharge copper tubing from indoor unit to outdoor unit of split AC of capacity 2TR with neoprene foam sleeves including sealing by applying adhesive tape for brown or white colour to avoid minimum contact with atmosphere complete all as specified and as directed. |
| 10 | Taking down ofexisting old unserviceable submain wiringcomplete all as specified and as directed. |
| 11 | Taking down ofexisting old unserviceableSingle pole and neutral enclosure of any ratingcomplete all as specified and as directed. |
| 12 | Taking down of old unserviceable distribution board complete all as specified and as directed. |
| 13 | S&F submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 20mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 2.5 Sqmm single core HR Grade and one run of 2.5 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB/ AC plug points complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 14 | S&F submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 6 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB/ AC plug points complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 15 | S&F Single pole and neutral enclosure with a two pin and earth including plug and socket complete set with one single pole MCB of 20 Amps,complete all as specified and directed. |
| 16 | Supply and fix in replacement of factory made epoxy polyster powder coated VTPN distribution boardTriple pole MCB4 way 415V fabricated from minimum 1.6 mm thick CRCA sheet with double door (IP-43 protection) fixed flush to wall and standard DIN rail, earth bar and cable ties for cable management, provision for 160 Amps MCCB as one incommerand 12 outgoings single pole MCB with 2 Neutral bar, 2 Earthbar, Fully insulated busbar rated capacity above 160Amp, shrouded Neutral bars and cable ties for cable management complete all as specified and confirming to IEC 61439-3,Reversible door IP 43 & IP 54. Make: Legrand /Siemens/Schneider. Note: Cutting on wall and taking out old one and then flushing new DB and making all the connection as before and any accessories required to fix the DB including making good the disturbed surface is deemed to be included in quoted rate. |
| 17 | Supply & Fixing MCCB 160 Amps4 Pole, 415 V, fixed thermal & fixed magnetic setting electromechanical type with Ics=75 % of Icu , with breaking capacity 16 KA conforming to IS: 13947-II complete all as specified and as directed. |
| 18 | Supply and fix in replacement of factory made epoxy polyster powder coated distribution board double doorSP&N 8 way 240V fabricated from minimum 1.6 mm thick CRCA sheet with double door (IP-43 protection) fixed flush to wall and standard DIN rail, earth bar and cable ties for cable management, suitable for one incomingand 6 outgoings complete all as specified and confirming to IS: 8623 (Make: Legrand /Siemens). Note: Cutting on wall and taking out old one and then flushing new DB and making all the connection as before and any accessories required to fix the DB including making good the disturbed surface is deemed to be included in quoted rate. Make: Legrand /Siemens/Schneider. |
| 19 | S&F in repalcement of MCB SP 6-32 Amps ,10 KA 230 Volts ,50 HZ complete all as specified and as directed by Engineer -in -charge .Make : Make: Legrand /Siemens/Schneider. |
| 20 | Supply and fixing SPN 63 amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) oftwo pole complete with connection testing and commissioning. |
| 21 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 40 AMP, in the MCB DB Complete with connection testing and commissioning. |
| 22 | Supply , Laying , testing and commissioning in replacement of XLPE insulated and PVC Sheathed , galvanized steel strip or wire armoured , heavy duty electric cable with multi stranded aluminium conductor, 1100 volts grade of size 95 sqmm 3.5 core complete all as specified & directed by Engineer - In - Charge. |
| 23 | Excavation in treanches in soft loose /soil not exc 1.5m wide and not exc 1.5m deep and getting out for taking out and laying cables foudation etc.Brick PCC cables protection cover shall be retrieved and kept in safe costody for reuse). |
| 24 | Returning filling in including spreading leveling waterning and well remmaning in layers not exc 25cm thick all as directed . |
| 25 | Removing of surplus spoil to a distnce not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point. |
| 26 | M&L for dry clean sand filling in trenches below and around under ground cable cushioning complete all as specified and directed. Note :-Thickness of sand cushioning shall be measured after punning. |
| 27 | M&L for brick protection with sub class \"B\" Designation 75 old bricks laid dry flat 23cm in width over sand cushioning in trenches as perpendicular to the direction of underground cable complete all as specified and as directed. |
| 28 | S&F in repair GI pipe light grade 50mm bore in trenches/wall/poles for protection of cable complete all as specified and as directed. |
| 29 | Labour and required toolsfor carrying out horizontal boring below roads/PCC hard standing/Drain suitable up to 50mm dia GI pipeall as specified as directed for inserting GI pipe of the following sze with a depth upto 1.5m & length of road upto 12m of the follwing size of bore. |
| 30 | M&L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed. |
| 31 | Note:- The amount of Rs 15447/- against Schedule of Crediton Srl Page 137 shall be deducted from the total amount quoted against Sch \"A\" |