| 1 | Supply, Laying, testing & commissioning XLPE insulated, PVC sheathed heavy duty LT 1100 Volts grade armoured UG cable 3.5 Core 120 Sqmm with stranded aluminium conductor in trenches/ fixed to walls/ poles etc. including taking out of existing cable complete all as specified and directed. |
| 2 | Supply, Laying, testing & commissioning XLPE insulated, PVC sheathed heavy duty LT 1100 Volts grade armoured UG cable 3.5 Core 150 Sqmm with stranded aluminium conductor in trenches/ fixed to walls/ poles etc. including taking out of existing cable complete all as specified and directed. |
| 3 | Supply, Laying, testing & commissioning XLPE insulated, PVC sheathed heavy duty LT 1100 Volts grade armoured UG cable 3.5 Core 240 Sqmm with stranded aluminium conductor in trenches/ fixed to walls/ poles etc. including taking out of existing cable complete all as specified and directed.Note for item 3 to 11 Earth work & excavation, sand cushioning and brick protection shall be measured and paid separately. |
| 4 | Supply & Laying 100 mm bore GI tubing, light grade, with all fittings of following sizes for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as specified and directed. |
| 5 | Supply & Laying 80 mm bore GI tubing, light grade, with all fittings of following sizes for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as specified and directed. |
| 6 | S & F cable end termination jointing kit heat shrinkable type for 1.1 KV (earthed) grade cable for outdoor with jointing material and accessories suitable for 3.5 core of size 95 sqmm to 150 Sqmm complete including taking out old unserviceable end termination jointing kit complete all as specified and directed. |
| 7 | S & F cable end termination jointing kit heat shrinkable type for 1.1 KV (earthed) grade cable for outdoor with jointing material and accessories suitable for 3.5 core of size 185 sqmm to 240 Sqmm complete including taking out old unserviceable end termination jointing kit complete all as specified and directed. |
| 8 | Cutting & trimming of tree branches any girth and sizetouching to overhead lines and cleaning the distance 1.5 mtr both sides of overhead line with in a gap of span 40 mtrs each and removing the samecleaning the site all as specified and directed. |
| 9 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deepfor foundation, laying of poles, cables in trenches and getting out in hard/dense soil complete all as directed and specified. |
| 10 | Returning, filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick complete all as all as specified and directed. |
| 11 | Removal of surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a lvevel not exceeding 1.5 mtrs above from the starting point complete all as all as specified and directed. |
| 12 | Supply and spread approved dry river sand for cushioning of cable including watering and consolidation, laid in trenches complete all as specified and directed. Note:- Punned thickness shall be measured for payment purpose |
| 13 | M&L brick protection with common burnt bricks sub class ‘B’ of size 230 x 113 x 75mm for cable protection complete all as specified and directed. |
| 14 | M & L for cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of cable/pipe all as directed and making good the road/hard standing by using all old/new materials and with PCC (1:2:4) etc, required to match with the existing surface complete all as specified and directed. |
| 15 | M&L for cleaning thoroughly LT distribution steel poles of any height and any description (Maximum 9 Mtr long) with necessary cleaning agent including scrapping of old corroded paint dirt/ rust carefully and applying two coats aluminium paintincluding marking of pole numbers and colour washing of pole coping completeall as specified and directed . |
| 16 | Removing Existing unserviceable Analog voltmeter with electrical connections and supply, install and testing new analog voltmeter 0-500V complete all as specified and directed. |
| 17 | Removing Existing unserviceable Analog ammeter with electrical connections and supply, install and testing new analog ammeter 0-250A/100A with necessary wires & CTs complete all as specified and directed. |
| 18 | Supply, install, test and commission CPRI APPROVED factory fabricated, outdoor type, LT FEEDER PILLAR BOX made out of 3.15mm thick CRCA sheet of size 1M x 0.75M x 0.35M with projected globe roof for rainwater protection dust and vermin proof, double door with both side opening including neoprene rubber gasket, suitable for 440 Volt 3 Phase 4 Wire System, including danger plate, earthing strip point and ventilation louvers at rear side, bottom detachable gland plate complete with suitable size zinc cromium plated nuts, bolts and washers etc. and embeded with 50x50x6mm MS angle iron frame, 600mm above the normal ground level complete with internal connection with suitable size of cable, cable lugs and cable glands, PCC foundation in cement concrete 1:3:6 (20mm graded stone aggregate) complete all as specified and comprising of the following :-(a)Aluminium busbar 200 amps - 04 Nos, supported on suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral.(b)MCCB 100 amps, 415 volt, 16 KA breaking capacity 4 pole electromagnetic release duly connected to busbar as incoming - 01 No. |
| 19 | S&F in repair test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed including 3 nos 8mm dia 25mm long hexagonal headed screws complete all as specified and directed. |
| 20 | S&F in repair galvanised iron strip of size 25x4mm complete all as specified and directed. |
| 21 | M&L for repair of existing LT panel outddor/indoor type by properly fixing loose/dislocated MS doors complete with provision of hinges and welding at locations as necessary, provision of tower bolt as per as existing size including painting of internal and external surfaces with one coat of synthetic enamel paint of approved colour after preparation of old painted surfaces complete as required for smooth operation of panel and as directed by the Engr-in-charge (Size of Panel board n.exc 2.25x1.2x0.6 m)NOTE: Cost of MS sheet, Tower bolt, sliiding bolt as required shall be included in the unit rate quoted by the Contractor. |
| 22 | M&L Earthing complete with galvanized steel with plate electrode 60 cm x 60 cm x 6.3mm thick buried directly in ground (earth kit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanized steel strip 32 x 6 mm by means of bolts, nutsand washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part-I connected toearth test point including necessary earth work and excavation, PCC 1:3:6 type C1 using 20mm graded stone aggregate for earth chamber with RCC cover 50mm thick 1:2:4 mix type B1, using 8mm dia TMT bars reinforcement@ 140mm c/c both ways, watering funnel with GI pipe 15mm dia medium gradeand protection pipe GI 40 mm dia light grade all as specified and directed. |
| 23 | Disconnecting existing panel and its connections and supply, install, testing and commissioning CPRI APPROVED factory fabricated powder coated, outdoor type, LT FEEDER PANEL of 600 Amps made out of 3.15mm thick CRCA sheet of suitable size with projected globe roof for rainwater protection dust and vermin proof, double door (including locking arrangement) with both side opening including neoprene rubber gasket, suitable for 440 Volt 3 Phase 4 Wire System, including danger plate, earthing strip point and ventilation louvers at rear side, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc. with panel control copper wiring, accessories fitted on suitable insulator all housed in suitable size chamber and fixing of digital Voltmeter, Ammeter with built in selector switch, CT\"s of suitable ratio, pilot indication lamps including internal connection with suitable size of cable, cable lugs and cable glands, panel embeded with 50x50x6mm mild steel angle iron frame 600mm above the normal ground level complete, PCC foundation 1:4:8 (using 40mm graded stone aggregate) and testing after installation complete all as specified and comprising of the following :-(a)Aluminium busbar 500 amps size 50mm x 10mm - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral.(b)MCCB 250 amps, 415 volt, 50 KA breaking capacity 4 pole - 01 Nos ( as incoming)(b)MCCB 160 amps, 415 volt, 36 KA breaking capacity 4 pole - 01 Nos( as outgoing)(c)MCCB 100 amps, 415 volt, 36 KA breaking capacity 4 pole - 02 Nos( as outgoing)(d)MCB TPN 32 Amps, 415 volt - 01 No. (as outgoing)(d)Three phase panel mounted digital type voltmeter 0-500 volts, selector switch and Ammeter 0-500 Amps with selector switch and LT-CT operated complete - 01 Set(e) Phase indicating lamp LED type for Red, Yellow and Blue - 01 Set |
| 24 | Supply, install, testing and commissioning single pole lightening arrestor, gapless metal oxide out door type complete with all fittings, distribution class, discharge capacity 30 KA suitable for 11000 Volts grade including necessary connection and fittings all as per IS-3070 Part-III and IEC 1994 including dismantling of existing lightening arrestor complete all as specified and as directed. |
| 25 | Supply and fixing triple pole mechanically operated air break isolator (GOD), Horizontal mounting, rotating type, mounted on insulator and steel frame with operating mechanism worked from one meter above ground level complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 11000 Volts grade, 50 Hz, with 6 insulator of rating upto 200 Amps including taking down old U/S GOD complete all as specified and directed. |
| 26 | S & F drop out fuse single pole mounted on insulator, 11000 Volts grade double pole steel frame of current rating 50 Amps including taking down existing DO fuse complete and removing from site complete all as specified and directed. |
| 27 | S&F galvanized steel water tubing medium grade of15mm bore complete with all fittings such asbends elbows, tees, short pieces, connectors, back nuts, diminishingpieces, caps and pigs, unions including taking up or down existing steel tubing with fittings all as specified and directed.Make : TATA / JINDAL / ZENITH |
| 28 | All as per item No.27 above but 20mm bore |
| 29 | All as per item No.27 above but 25mm bore |
| 30 | All as per item No.27 above but 40mm bore |
| 31 | All as per item No.27 above but 50mm bore |
| 32 | All as per item No.27 above but 80mm bore |
| 33 | All as per item No.27 above but 100mm bore |
| 34 | S&F in repairs gunmetal globe or gate valve with iron wheel head screwed both ends for iron pipe of 15mm bore including taking down complete all as specified and directed.Make : TATA / JINDAL / ZENITH |
| 35 | All as per item No.34 above but20mm bore |
| 36 | All as per item No.34 above but25mm bore |
| 37 | All as per item No.34 above but40mm bore |
| 38 | All as per item No.34 above but50mm bore |
| 39 | Supplyand lay of 20mm dia 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed complete to walls, ceilings or in floors etc. Make : SFMC/ PRINCE / SUPREME |
| 40 | All as per item No.39 above but25mm bore |
| 41 | All as per item No.39 above but32mm bore |
| 42 | All as per item No.39 above but40mm bore |
| 43 | All as per item No.39 above but50mm bore |
| 44 | Supply and fix PP-R Gate valves (brass insert) of 20mm outer dia as per requirement of the site complete all as specified and directed.Make : SFMC/ PRINCE / SUPREME |
| 45 | Supply and fix PP-R Gate valves (brass insert) of 25mm outer dia as per requirement of the site complete all as specified and directed.Make : SFMC/ PRINCE / SUPREME |
| 46 | Supply and fix PP-R Gate valves (brass insert) of 32mm outer dia as per requirement of the site complete all as specified and directed.Make : SFMC/ PRINCE / SUPREME |
| 47 | Supply and fix PP-R Gate valves (brass insert) of 40mm outer dia as per requirement of the site complete all as specified and directed.Make : SFMC/ PRINCE / SUPREME |
| 48 | Supply and fix PP-R Gate valves (brass insert) of 50mm outer dia as per requirement of the site complete all as specified and directed.Make : SFMC/ PRINCE / SUPREME |
| 49 | Material & LabourDI fittings for spigot/flanged end pipes such as bends any type (radius and angle) tapers any type (straight, bend increasing or decreasing double socket flanged etc), Tee pieces, single branch, \"Y\" junction, double branch cross (all socket or socket and spigot or flanged, Collars,caps and plug etc all as specified and directed up to 250mm bore. |
| 50 | Dismantling and taking out existingunserviceable foot valve of for size 80mm bore from the pipeline andreplacing with new CI foot valve of 80mm bore complete with necessary nuts,bolts and gasket as per site requirement fixing in position all as specified and directed by Engineer-in-Charge.Make : KIRLOSKAR / LEADER |
| 51 | All as per item No.50 above but100mm bore |
| 52 | All as per itemNo.50 above but150mm bore |
| 53 | All as per itemNo.50 above but200mm bore |
| 54 | Construction of valve chamber with PCC 1:4:8 type D2 for foundation, brick wall in cement mortar (1:4), PCC 1:2:4 type B1 for coping, rendering in CM (1:4) 15mm thick for internal surfaces, 3mm thick MS sheet welded to frame made out of 40 x 40 x 3 as cover (of suitable size wrt chamber size)fixed with hinges welded to frame of 50 x 50 x 6mm embedded in coping and applying two coats of synthetic enamel paint over a coat of redoxide primer to the steel surfaces including necessary excavation and earthwork in any type of soil complete for chamber of size 600x600x600mm complete all as specified and directed. |
| 55 | All as per itemNo.54 above but900x900x900mm depth. |
| 56 | All as per itemNo.54 above but 1200 x 1200 x 1200 mm depth. |
| 57 | S & F in repair NRV of 80mm dia matching existing model complete with necessary, nuts,bolts and gasket as per site requirement complete all as specified and directed.Make : KIRLOSKAR / LEADER |
| 58 | S & F in repair NRV of 100mm dia matching existing model complete with necessary, nuts, bolts and gasket as per site requirement complete all as specified and directed.Make : KIRLOSKAR / LEADER |
| 59 | S & F in repair NRV of 150mm dia matching existing model complete with necessary, nuts, bolts and gasket as per site requirement complete all as specified and directed.Make : KIRLOSKAR / LEADER |
| 60 | Dismantling and taking out unserviceable air release valve of size 80mm bore from the pipeline and replacing with new CI Air release valve with two air outlets of 80mm bore complete with necessary nuts, bolts and gasket as per site requirement fixing in position all as specified and directed by Engineer-in-Charge.Make : KIRLOSKAR / LEADER |
| 61 | M&L for cutting of road, hard standing of approx depth 2 meter made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of pipe line all as directed and making good the road/hard standing by using all old/new materials and with PCC (1:2:4) etc., required to match with the existing surface complete all as specified and directed. |