| 1 | Schedule-A |
| 2 | Supply & fixexhaust fan, steel bodyAC single Phase. 230V of size 450m sweep with, blades, and frame andlouvers including connecting up with copper cable 3 coreof size 23/.0076 all as specified and directed |
| 3 | Supply and fix Switch flame proof rotary type with termination box inLM6, 25 A, single pole 250V |
| 4 | M & L for making hole by mannual cutting in brick wall for mounting Exhaust fan 450 mm sweep and making good to disturbed surfaces of wall by replastering and distempering etc complete all as directed. |
| 5 | S&F Switch piano flush type, single pole , 6 Amps, one way complete all as specified. |
| 6 | Supply and fixing ceiling fans completewith blades, down rods, electronicregulator and accessories, 230 V, 1200mm sweep. Min air delivery 210 CFMwith service value 6.00 BEE. Five starrated with brushless direct current motor(BLDC) BEE 5 star rated |
| 7 | Supply & fixexhaust fan, steel bodyAC single Phase. 230V of size 300m sweep with, blades, and frame andlouvers including connecting up with copper cable 3 coreof size 23/.0076 all as specified and directed |
| 8 | Supply and fix electric water heater,storage type steel body with copperinner tank and heating element upto2 KW capacity 25 litre, BEE 5 Starrated complete with all accessoriessuch as safety valve, thermostate,NRV, connection piece etc. |
| 9 | Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250 mm |
| 10 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core |
| 11 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundations of poles, laying of cables, pipes etc. and getting outincluding trimming the sides and forming bottom surfaces to required levels in soft/loose soilcomplete all as specified and directed. |
| 12 | Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed. |
| 13 | Removing excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 14 | M&L laying well burnt old sizebricks, sub class \"B\" bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified. |
| 15 | Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete as specified and directed . |
| 16 | Boring/Drilling ( horizontally) manually under existing road (maximum 10 M in width) suitable for passing GI tubing of 80 mm bore complete all as specified. |
| 17 | Supply, laying & fixing galvanised steel tubing 50 mm bore \"light grade\"(Make -QST/ TATA / JINDAL) with GI fittings in trenches/ under roads/ along pole/ wallincluding FI (25 mm x 6 mm ) clamps as required for cable protection all as specified & directed by EIC. |
| 18 | S & F epoxy powder coated distribution box TPN 4 way, grouted flush to wallshaving incomer minimum 4 ways and outgoing 12 ways IP 43with metal door complete all as specified and directed |
| 19 | Supply and fixing 415V 10KA \"B\" curve miniaturecircuit breaker (MCB) of following poles andcurrent carrying capacity in the DB complete withconnection testing and commissioning of size SPN 16 to 32 |
| 20 | Supply and fixing 415V 10KA \"B\" curve miniaturecircuit breaker (MCB) of following poles andcurrent carrying capacity in the DB complete withconnection testing and commissioning of size TPN/FP 16 to 32 |
| 21 | Material and labour for Installation, testing and commisioning of High galvanized mast light 20 meter height suitable for9 lantern symmetrically fitted along with their control gear and wiring including motorized system witg control gear for smooth operation and having two point suspension system with stainless steel wire rope of 6 mm dia 97/19 guage and double drumwith luminaire mounting arm, pully assembly, aviation obstruction light with electrical wiring, lightning arrester spike duly connected to earth test point with Aluminium strip 25 mm including RCC foundation as per design submitted by the manufacturer to withstand wind pressure as per weather conditions in Gurgaon complete all as specified & directed. |
| 22 | Supplying, laying or fixing, jointing and testing LT under ground electric power cableCrossed linked polyethylene ( XLPE)insulated, two or more core, galvanised steel strip or wire armoured,ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of following sizes ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc.( Excavation, earth work, sand cushioning, protection bricks/ tiles/ block,Clamps, nuts , bolts, washers andpipe shall be measured and paid separately under appropriate items ) :-conductor of size 10.0 sq mm 4 core |
| 23 | All as per item No- 02 above but conductor of size 70.0 sq mm 4 core |
| 24 | Supply and fixing LED flood light 170 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed. |
| 25 | M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased inand including 40 mm dia GI \"lightgrade\" pipe from upper end of earth plate upto equipments,20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of |
| 26 | earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS round bars 6mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I completeall as specified and directed and testing on completion. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 27 | Supply and fixingof High mast control panel made of minimum 1.6 mm GI sheet weather and dust proof, outdoor type having top canopy, double door, locking arrangement, necessary power and control panel wiring inside the panel and necessary assembly for assembling following items-1) 63 Amp 4 pole MCB make- Schneider electric 02 nos.2) Auxilary Contact Block front type 1 NO + 1NC CAF11-01 Nos3) Auxilary Contact Block front type 2NO+2NC CAF22-02 Nos4) Indicating lamp 01 set5) Push buttons for lowering / lifting -02 Nos6) Switch for selection between auto and manual.7) Programmable Astro time switch 24 hours (SST-15 Min) outdoor lights. Make- Havells -01 No |
| 28 | Supply, laying & fixing galvanised steel tubing 80 mm bore \"light grade\"(Make -QST/ TATA / JINDAL) with GI fittings in trenches/ under roads/ along pole/ wallincluding FI (25 mm x 6 mm ) clamps as required for cable protection all as specified & directed by EIC. |
| 29 | M&L for supply, installation, testing and commissioning of double skin Air Handling Unit (AHU) made of 25 mm thick insulated panels with aluminium profile, pre-plasticized GI casing (0.6 mm thick outer and inner layers), polyurethane foam insulation of density 40 kg/m³ factory injected. Complete with DIDW backward curved fans (Kruger / Nicotra make), 6-row chilled water DX coil, filter section with 50 mm thick washable synthetic pre-filters having efficiency 90%down to 10 microns, 5-micron and efficiency 99.9% down to 0.3 micron Hepa filter, 6 KW dehumidifier heater, good quality flexible canvass connection etc, TEFC (IE-2) motor suitable for VFD operation at 415 Volts tolerance limit 10%, 50 Hz, 3 phase, GI dampers at supply, return and fresh air side, mixing box, drain connections, stainless steel drain pan,necessary vibration isolation arrangement etc. complete as per specifications of followingcapacity given below- |
| 30 | Capacity 6000 CFM @125 mmwg, 5.5 KW (fan dia 450 BC) |
| 31 | Dehumidifier unit controller, set range 40–60% RH + Temperature |
| 32 | Supply and fix VRV-X heat pump ODU complete all as specified and directed |
| 33 | Supply and fix the Expansion Valve Kit, complete all as specified and as directed. |
| 34 | Supply and fix AHU Connecting Kit complete all as specified and as directed. |
| 35 | Supply and fix the Wired Remote, complete all as specified and as directed. |
| 36 | Supply and fix MS ODU stand with rubber pads complete all as specified and directed |
| 37 | Supply and fix copper piping 11/8\" & 1/2\" complete all as specified and directed |
| 38 | ODUInstallation & Connection, complete all as specified and as directed. |
| 39 | Humidifier & Dehumidifier Installation complete all as specified and as directed. |
| 40 | Supply and fix 24-gauge GI duct complete all as specified and directed |
| 41 | Supply and fix 10 mm nitrile insulation complete all as specified and directed |
| 42 | Supply and fix motorised damper size 400 × 400 mm complete all as specified and directed |
| 43 | Supply and fix cable tray 6\" (150 mm) with cover complete all as specified and directed |
| 44 | Supply and fix 1 mm² 2-core communication cable with conduit, complete all as specified and directed |
| 45 | Supply and fix MS Framework for the AHU Unit complete all as specified and as directed. |
| 46 | Supply and fix Aluminium Grillies complete all as specified and as directed. |
| 47 | Supply and fix 4-way diffuser 600 × 600 mm complete all as specified and directed |
| 48 | Supply and fix 32 mm drain CPVC pipe, complete all as specified and directed |
| 49 | Supply and fix 4-Pole 63 A ELCB (Earth Leakage Circuit Breaker) is a protective device designed to automatically disconnect the power supply in the event of earth leakage or residual current faults, preventing electric shock hazards and protecting equipment. Suitable for three-phase (3P+N) systems, it is rated for 63 A load capacity and typically operates at 415 V AC, 50 Hz, with a sensitivity of 30 mA, 100 mA, or 300 mA depending on application requirements. The device offers fast tripping (≤ 0.1 seconds) upon detecting leakage, has a breaking capacity of 6–10 kA, and is DIN-rail mountable. It complies with IEC 61008-1/IEC 62423 standards and features an IP20 or higher protection degree, making it suitable for safe indoor or specified outdoor installations complete all as specified and as directed. |
| 50 | Ditto as above items but 40 Amp4-Pole 63 A ELCB (Earth Leakage Circuit Breaker) |
| 51 | Supply and fix 10 sqmm 4-core copper cable is a heavy-duty, multi-core electrical cable designed for power distribution. It consists of four conductors, each made of high-conductivity, annealed copper with a cross-sectional area of 10 sqmm, insulated with high-grade PVC for thermal and electrical protection. The cores are color-coded for easy identification, laid together with suitable fillers, and sheathed with durable PVC/FRLS (Flame Retardant Low Smoke) or equivalent outer covering to ensure mechanical strength, moisture resistance, and fire safety. Typically rated for 1100 V (1.1 kV) operation and conforming to IS 694/IS 1554 (Part 1) or IEC standards, it offers excellent conductivity, low power loss, and reliable performance in fixed wiring complete all as specified and as directed. |
| 52 | Ditto as above items but 4 sqmm 4- core copper cable. |
| 53 | Supply and fix in replacement of factory made epoxy polyster powder coated distribution board double doorTriple pole and neutral 4 way 415V fabricated from minimum 1.6 mm thick CRCA sheet with double door (IP-43 protection) fixed flush to wall and standard DIN rail, earth bar and cable ties for cable management, suitable for one incoming MCB TPNand 3 outgoings MCB TPN complete all as specified and confirming to IS: 8623 (Make: Legrand /Siemens). Note: Cutting on wall and taking out old one and then flushing new DB and making all the connection as before and any accessories required to fix the DB including making good the disturbed surface is deemed to be included in quoted rate. Make: Legrand /Siemens/Schneider. |
| 54 | Material & Labour for concealed point wiring with single core PVC insulated and unsheathed 1100 volts grade cable with multistranded copper conductor of size 1.5 Sqmm nominal area drawn through & including non metallic rigid PVC conduit (circular/flat pvc conduit), medium duty not less than 20 mm dia concealed in wall/fixed on wall/ceiling with GI saddles , GI screws , rawl plugs with all fittings including tees , junction boxes & provision for modular box and modular cover of suitable size for mounting modular switches , sockets & regulators & drawing through continuous earth wire of PVC insulated unsheathed 1100 volts grade cable with copper conductor solid conductor of size 1.5 sqmmcomplete all as specified & directed by Engineer -In-Charge.Note: Cost for cutting chases and making good to match the existing surface shall be deemed to be included in the quoted rate. |
| 55 | For one light/fan point wiring with cable 1.5 Sqmm size |
| 56 | For one 3 pin sockets outlet 5 Amps on the same board with other switches with cable of size 1.5 sqmm |
| 57 | For one 3 pin sockets outlet 15 Amps idependent with cables 2.5sqmm size |
| 58 | Supply and Fixing of modular switches 1 way, 6 Amp 1 module complete all as specified & directed by Engineer - In-Charge. |
| 59 | Supply and Fixingmodular Socket, 6A - 2/3 pin combined 2 module, complete all as specified & directed by EIC. |
| 60 | Supply and Fixing of modular switches 1 way, 16 Amp 1 module complete all as specified & directed by Engineer - In-Charge. |
| 61 | S&FGI Modular gang sunk-in pressedterminal boxes of required size not less than 1.2 mm thick factory made for following module complete all specified and directed.Note: Flushing of module box in wall with cement and repairing the wall as before is deemed to be included in quoted rate. |
| 62 | Metal flush box 3 module |
| 63 | Metal flush box16 module |
| 64 | S&F white cover plate with frame of following module complete all specified and directed. |
| 65 | White cover plate with frame 3 module |
| 66 | White cover plate with frame 16 module |
| 67 | Supply & Fixing of Ceiling Rose, 3 phase polycarbonate isolated body complete all as specified & directed by Engineer - In-Charge. |
| 68 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light completewith driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable sizecomplete. |
| 69 | S&F wall mounted fan 450 mm sweep, 230 volts, 50 Hz AC, single phase, heavy duty type with metal body and guard, aerodynamically designed aluminum / ABS blades, minimum speed 1400 RPM, air delivery not less than 100 m³/min, having three speed control and oscillation arrangement complete with wall mounting bracket, pull cord control and necessary fixing arrangements, including making good disturbed surfaces, testing and commissioning all as specified and directed.Make: Crompton / Havells / Usha / Orient / Bajaj or equivalent approved by Engineer-in-Charge. |
| 70 | S&F submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 20mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 4 Sqmm single core HR Grade and one run of 4 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB/ AC plug points complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 71 | S&F submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 6 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 72 | S&F submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 20mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 1.5 Sqmm single core HR Grade and one run of 1.5 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to plug points complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 73 | Supply , Laying , testing and commissioning in replacement of XLPE insulated and PVC Sheathed , galvanized steel strip or wire armoured , heavy duty electric cable with multi stranded aluminium conductor, 1100 volts grade of size 70 sqmm 3.5 core complete all as specified & directed by Engineer - In - Charge. |
| 74 | Labour and required toolsfor carrying out horizontal boring below roads/PCC hard standing/Drain suitable for 50mm dia GI pipeall as specified as directed for inserting GI pipe of the following size with a depth upto 1.5m & length of road upto 12m of the 50mm size of bore. |
| 75 | S&F in repalcement of MCB SP 6-32 Amps ,10 KA 230 Volts ,50 HZ complete all as specified and as directed by Engineer -in -charge .Make : Make: Legrand /Siemens/Schneider. |
| 76 | Supply and fixing SPN 63 amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) oftwo pole complete with connection testing and commissioning. |
| 77 | Supply and fix in replacement of factory made epoxy polyster powder coated VTPN distribution boardTriple pole MCB4 way 415V fabricated from minimum 1.6 mm thick CRCA sheet with double door (IP-43 protection) fixed flush to wall and standard DIN rail, earth bar and cable ties for cable management, provision for 125 Amps MCCB as one incommerand 12 outgoings single pole MCB with 2 Neutral bar, 2 Earthbar, Fully insulated busbar rated capacity above 160Amp, shrouded Neutral bars and cable ties for cable management complete all as specified and confirming to IEC 61439-3,Reversible door IP 43 & IP 54. Make: Legrand /Siemens/Schneider. Note: Cutting on wall and taking out old one and then flushing new DB and making all the connection as before and any accessories required to fix the DB including making good the disturbed surface is deemed to be included in quoted rate. |
| 78 | Supply & Fixing MCCB 125 Amps4 Pole, 415 V, fixed thermal & fixed magnetic setting electromechanical type with Ics=75 % of Icu , with breaking capacity 16 KA conforming to IS: 13947-II complete all as specified and as directed. |
| 79 | Supply and fix in replacement of factory made epoxy polyster powder coated distribution board double doorSP&N 12 way 240V fabricated from minimum 1.6 mm thick CRCA sheet with double door (IP-43 protection) fixed flush to wall and standard DIN rail, earth bar and cable ties for cable management, suitable for one incomingand 6 outgoings complete all as specified and confirming to IS: 8623 (Make: Legrand /Siemens). Note: Cutting on wall and taking out old one and then flushing new DB and making all the connection as before and any accessories required to fix the DB including making good the disturbed surface is deemed to be included in quoted rate. Make: Legrand /Siemens/Schneider. |
| 80 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip of size 25 x 4 mm as earth lead by means of bolts, nuts, check nuts and washers , of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified includingprovision of GI stripprotected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation andearth work & connecting the earthing to an earthing test pointcomplete all as specified & directed by Engr-in-Charge. |
| 81 | Supply and fix in replacement ofAluminiumStrip of size 25 X 3 .15mm buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 82 | M&L of single core PVC unsheathed multi stranded copper cable (FRLS) 6 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 83 | M&L of single core PVC unsheathed multi stranded copper cable (FRLS)1.5Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 84 | S&F Rigid non-metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusiveof all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, locknuts, saddles, pipehooks etc. |
| 85 | Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300m complete all as specified and directed |
| 86 | S & F MCB SPN DB 8 way , Double door, with 200Amp rated bus bar and connecting up complete all as specifiedEngr-in-Charge.Make-Indoasian / L&T/Havell/Legrand . |
| 87 | S&F MCB SPN, 220 volt , 50 Hzs, 32 A, 10 KA , \"C\" series |
| 88 | S&F MCB SP, 220 volt , 50 Hzs, 6 to 32 A, 10 KA , \"C\" series |
| 89 | Note:- The amount of Rs……. against Schedule of Crediton Srl Page………. shall be deducted from the total amount quoted against Sch \"A\" |