| 1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) asrequired. |
| 2 | Earthing with Copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) asrequired. |
| 3 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm diaGIpipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required |
| 4 | Providing and fixing 25 mm X 5 mm GI strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required |
| 5 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 6 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3½ X 185 sq. mm (57mm) |
| 8 | Providing and laying in position cement concrete 1:2:4 (1 Cement : 2 Coarse sand: 4 Graded stone aggregate 20 mm nominal size) in foundation of pump, DG set eyc including form work etc as required. |
| 9 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. 3.5X 120 Sqmm |
| 10 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following sizein the existing masonry open duct / along pole / loose for connections etc as required. (ISI marked Make Havells /Polycab/ Finolex /CCI / /RR Kabel) 3.5X 120 Sqmm |
| 11 | Providing and fixing of On-Load manual changeover switch in sheet steel enclouser. Rated current 250 A, 415 V AC, 4 Pole on exixting wall including making connection etc as per direction of engineer in charge,. Make- Havells. |
| 12 | Dismenteling and removing ofexisting 125 KVA DG set etc as required. |
| 13 | Transportion of new 125 KVA DG sets from Sector HQ Jaisalmer South to 126 Bn HQ Ramgarh, by taking all precautionary measures to avoid damage of DG set through respective 4 X 2 vehicle of suitable capacity(Suitable for moving on pacca) etc as per site requirement, including loading/unloading of DG sets by means of Hydra/Mechanical means at pick up point and DG set base respectively. |
| 14 | Proving and fixing of exhaust medium class GI pipe size 100 mm, 1.5 mtr long with the help of suitable size flange, bendi/c cutting, bending & welding according to existing DG set exhaust pipe including making hole & smooth surface etc as required. |