Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed. |
| 2 | Excavating in trenches, not exc 1.5 metre wide and exc 1.5 metre but not exc 3.00 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in hard soil/ dense soil complete all as specified and as directed. |
| 3 | Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed. |
| 4 | Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed. |
| 5 | M&L for sand cushioning using clean local unwashed river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of under ground electric cable complete all as specified and as directed.Notes:-(i) Approved local river sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured. |
| 6 | Supplying and laying factory made, un-reinforced precast concrete cable cover, ISI marked, Class LV, Type 1, with flat, size 250mm x 150mm x 40mm, laid as cable protection cover in trenches, complete all as specified & as directed. |
| 7 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 630 sqmm Single core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 8 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 150 sqmm 3.5 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 9 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 95 sqmm 3.5 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 10 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 50 sqmm 3.5 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 11 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm 3.5 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 12 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 25 sqmm 3.5 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 13 | Supply, laying, jointing and testing LT XLPE insulated screened,bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 10 sqmm 4 core laid in trenches/ducts, fixing on walls/ through pipe, under floors or roads/ along poles including connecting to installation equipment / panel with bus bar etc with suitable lugs, glands, nuts bolt & washer complete all as specified and directed.Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. |
| 14 | M&L for repairing road cutting with premix ready mix road patching compound including preparing the affected surface by cleaning, sweeping, brushing and apply cat\"s coat primer and pouring the ready mix road patching compound, spreading, leveling and compacting to match with existing road complete all as per manufacturers instruction and as directed |
| 15 | M&L for Earthing to Panels / equipments etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to Panel/ equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed.Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. |
| 16 | Supplying, installing, testing and commissioning of factory fabricated CPRI approved, type tested, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet outer body and 2mm thick CRCA MS sheet inner body duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, including aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermo setting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6mm duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. |
| 17 | The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- Noted: (i) LT panels/ feeders pillar boxes are designed as per latest IS Specification. (ii) All type test certificate and design verification with switchgear (ACB & MCCB) as per IS/IEC : 61439-1:2011 & IS/IEC :61439-2:2011.(a) ACB 1000 Amp, 415 Volts, 4 Pole, breaking capacity 50 kA, 50 Hz with Ics=100% Icu and microprocessor release type -01 No and including spreader terminals - set of 08, direct rotary handle (I/C) - 01 Nos(b) MCCB 350 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(c) MCCB 250 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(d) MCCB 200 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 02 Nos(e) MCCB 160 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 02Nos and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(f) 3 Phase Digital type voltmeter with inbuilt selector switch - 01 set(g) 3 Phase Digital type ammeter with inbuilt selector switch - 01 Set(h) LED type indicating lamps R, Y, B - Set(j) Aluminium main bus bar of size of suitable size and 1.5 x capacity of main incommer ACB/ MCCB(k) CTs/ Control fuse of suitable size complete (Main Panel) |
| 18 | Supplying, installing, testing and commissioning of factory fabricated CPRI approved, type tested, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet outer body and 2mm thick CRCA MS sheet inner body duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, including aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermo setting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6mm duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. |
| 19 | The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- Noted: (i) LT panels/ feeders pillar boxes are designed as per latest IS Specification. (ii) All type test certificate and design verification with switchgear (ACB & MCCB) as per IS/IEC : 61439-1:2011 & IS/IEC :61439-2:2011.(a) MCCB 315 Amp, 415 Volts, 4 Pole, breaking capacity 50 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 08, direct rotary handle (I/C) - 01 Nos(b) MCCB 100 Amp, 415 Volts, 3 Pole, breaking capacity 16 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 02 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(c) MCCB 63 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(d) Aluminium bus bar (RYB & N) 400 Amp rating with 04 Nos (O/G) arrangement- 01 Set(e) 03 Phase Digital type ammeter with inbuilt selector - Set(f) 03 Phase Digital type voltmeter with inbuilt selector - Set(g) LED type indicating lamps RYB set complete set (Panel No - 01) |
| 20 | Supplying, installing, testing and commissioning of factory fabricated CPRI approved, type tested, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet outer body and 2mm thick CRCA MS sheet inner body duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, including aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermo setting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6mm duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. |
| 21 | The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- Noted: (i) LT panels/ feeders pillar boxes are designed as per latest IS Specification. (ii) All type test certificate and design verification with switchgear (ACB & MCCB) as per IS/IEC : 61439-1:2011 & IS/IEC :61439-2:2011.(a) MCCB 200 Amp, 415 Volts, 4 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 08, direct rotary handle (I/C) - 01 Nos(b) MCCB 100 Amp, 415 Volts, 3 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(c) MCCB 63 Amp, 415 Volts, 3 Pole, breaking capacity 25 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(d) Aluminium bus bar (RYB & N) 250 Amp rating with 04 Nos (O/G) arrangement- 01 Set(e) 03 Phase Digital type ammeter with inbuilt selector - Set(f) 03 Phase Digital type voltmeter with inbuilt selector - Set(g) LED type indicating lamps RYB set complete set (Panel No - 02 & 03) |
| 22 | Supplying, installing, testing and commissioning of factory fabricated CPRI approved, type tested, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet outer body and 2mm thick CRCA MS sheet inner body duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, including aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermo setting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6mm duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. |
| 23 | The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- Noted: (i) LT panels/ feeders pillar boxes are designed as per latest IS Specification. (ii) All type test certificate and design verification with switchgear (ACB & MCCB) as per IS/IEC : 61439-1:2011 & IS/IEC :61439-2:2011.(a) MCCB 100 Amp, 415 Volts, 4 Pole, breaking capacity 36 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 01 No and including spreader terminals - set of 08, direct rotary handle (I/C) - 01 Nos(b) MCCB 63 Amp, 415 Volts, 3 Pole, breaking capacity 25 kA, 50 Hz with Ics=100% Icu and microprocessor release type - 03 No and including spreader terminals - set of 06, direct rotary handle (O/G) - 01 Nos(c) Aluminium bus bar (RYB & N) 200 Amp rating with 04 Nos (O/G) arrangement- 01 Set(d) 03 Phase Digital type ammeter with inbuilt selector - Set(e) 03 Phase Digital type voltmeter with inbuilt selector - Set(f) LED type indicating lamps RYB set complete set (Panel No - 04) |
| 24 | Supply & Fixing of Bus Bar Chamber outdoor type made out of 1.6 mm CRCA sheet 6 Nos outgoing TPN 200 Amps Bus Bar rating with and provision for fixing of 125 Amps MCCB 4 Pole, rupturing capacity 36 kA, 415 Volt, 50 Hz (Incoming) with Ics=100% Icu and with microprocessor release type - 01 Nos as main incommer includingfixing on Wall / Pole with suitable size of clamp, Nut & Bolt or as per site requirement for fixing of outdoor site with provision of angle iron legs 45x45x3mm, 750mm long including PCC for grouting and incommer and outgoing cable connections with suitable size of lugs complete all as specified and directed. |
| 25 | M&L for cable jointing kit for 1100 Volts grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 10 sqmm to 35 sqmm complete all as specified & as directed. |
| 26 | M&L for cable jointing kit for 1100 Volts grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified & as directed. |
| 27 | M&L for cable route indicator showing \"MES LT UG cable\" and route of cable with arrow made with eliptical/round shape and fixed on angle iron 40x40x6mm, 800mm long painted in Blue colour with two coats of synthetic enamel paint over a coat of red oxide primer duly embeded in PCC block 0.40x0.40x0.40m (1:3:6) type C1 using 20mm graded stone in ground and 0.15 metre above ground level complete all as specified and directed. |
| 28 | Supply & fixing Automatic Security light control panel having sheet steel enclosure power coated CRCA sheet suitable for three phase, 6 KW rating, outdoor installation, IP 54 protected, Slop 1:2, denger notice plate including making all connections and grouted in PCC (1:2:4) type B-1, using 20mm graded stone aggregate with foundation should be 100mm above ground level complete with comprising of the following switch gears:-(i) MCB TPN 40 Amp rating -01 No(ii) Digital Timer Switch - 01 Nos(iii) Contactor with nominal current rating 32 Amp TP (iv) Outgoing MCB SP with Suitable rating - 03 Nos(v) Auto/manual switch (vi) Incoming and outgoing terminal suitable for three phase supply. (vi) MS cable glands for entry & exist point of cables. |
| 29 | Supply and fixing in replacemnt moulding compound street lightjunction box of size not less than 250mm x 250mm x 160mm complete with shock and rust proof, termite resistant, tamper proof, front openable type and including suitable provision for three phase, four wire cable (size upto 25 Sqmm 4 Core) incomming & outgoing loop -in loop connection and including one no. MCB Single Pole 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete all as specified and directed. |
| 30 | Boring of holes under road, Pavement, Hard standing or as directed by trenchless technology using ultra sounding technique and necessary machine forcrossing of LT ElectricXLPE cable as per fallow with standard technical specification including with HDPE pipe of dia not less than 150mm suitable for 0.4Mpa working pressureand vertical depth n. exc. 2 mtrand horizontal dian. exc. 200mmand including getting out excavated surplus soil to a distance not exceeding 50 mtr and depositing where as directed at a level compllete all as specified. |
| 31 | Supply & fixingPVC insulated FRLS unsheathed flexible copper conductor cable of size 1.5 Sqmm, multistranded, three core,1100 volts grade for connecting from loop in loop out box to street light fitting including taking down old existing unserviceable flexible cable any description and complete all as specified and directed. |
| 32 | Dismantling existing unserviceable stay assembly and concrete etc complete all as specified and directed.Note : Demolition of cement concrete and excavation of stay assembly shall be included in this item. |
| 33 | Dismantling of existing unserviceable LT Over Head line aluminium conductor and earth wire, steel reinforced ACSR conductors of any size/ type/capacity from existing overhead lines on LT steel tubular poles/PCC poles (of any height) complete including PVC spacers, PG clamps by binding wire from insulators including disconnecting from the existing system complete all as specified and as directed. |
| 34 | Dismantling MS work such as cross arms channel, MS clamp, angle section etc. complete and setting aside for re-use within 500m including as per site requirement any size and shape, nuts, bolts, washer etc complete all as specified and directed. |
| 35 | Dismantling existing unserviceable GI earthing wire, guard or cradles of any size from existing LT pole, including disconnecting from existing system complete all as specified and directed. |
| 36 | Dismantling old unserviceable insulators of any type, any size including MS spindle GI washers nuts etc on LT Poles complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy