| 1 | I. WIRINGWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.a) Group C |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.a)20 mm |
| 4 | II. MCB & DB\"s Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)a) 6 Way , Double Door |
| 5 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a)Single Pole |
| 6 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.a)40 Amps |
| 7 | III. FITTING AND FIXTURESSupplying of surface mounted LED batten Fitting powder coated CRCA sheet for 20 Watt T8 Lamp similar to Luker Code LLTB with 20W Retrofit LED glass tube light Havells Cat No. CRYSTALT81213SSTL20WLED865SGLASS or its equivalent. |
| 8 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 9 | Supplying of surface mounted LED Bulkhead Fitting similar to Polycab Code PLT0101316 Bulkhead 10W BHE10W60, 6000K or its equivalent. |
| 10 | Supplying of 5W mirror light of length 1 feet surface mounted LED batten/Tube light Havells Cat No. LHEXBLP7IN1W005 or its equivalent. |
| 11 | Installation ,Testing, Commissioning of wall bracket /ceilingfittings of all sizes and shapes containing upto two GLS/CFL/LEDlamps per fitting, complete with all accessories including connections etc. as required |
| 12 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 13 | Supplying of 9W LED Lamp directly fitted in the Batten Holder similar to Crompton, Cat No. LED 9W-B22-CDL or its equivalent as required. |
| 14 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 15 | Providing and Fixing of Hot Press Mounted Sintex SMC Meter Box Single door of size 250 x 200 x 100 mm (outside) for accommodating and LT Single Phase KWh Meter with cutout similar to Code GSMB-2520or its equivalent as required. |
| 16 | Providing and Fixing of 32A, 240V Kit-Kat rewireable porcelain fuse unit on the existing SMC Meter Box,making connections, etc., as required. Make: Havells, Cat No. IHKKRN2032or its equivalent as required. |
| 17 | IV. EARTHING Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)(Proof/ Test Certificate should be enclosed) |
| 18 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 19 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |