| 1 | Taking down carefully point wiring of any type/size (Light, fan, socket ) complete including making good the disturb surface finishing of wall /floor etc,complete all as specified and directed. |
| 2 | Taking down existing sub main wiring of any type/size complete from wall and making good distrubed surface. |
| 3 | 1.M&L for point wiring with 1.5 Sqmm PVC FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable in & incl PVC casing caping of suitable size as per site reqmt, ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc all as per site requirements including stainless steel terminal boxesfor mounting of switches/ sockets/regulator etc and PVC FRLS insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead connected to common earth dolly complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green. Make for cable Anchor/Polycab / Plaza (a) For one light point/fan Point controlled by one way switch. |
| 4 | All as per item No 3 (a) here-in-before but for power point wiring with 2.5 Sqmm FRLS PVCinsulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 2.5 Sqmm FRLS PVCinsulated, unsheathed, copper conductor, stranded 1100 volt grade cable for earth continuity. |
| 5 | Material and labour for sub main wiring with 2 x 4 Sq mm PVC insulated single core unsheathed stranded copper conductor drawn in and including PVC conduit pipe of suitable size ISI marked including continuous running earth wire by 4Sqmm PVC unsheathed single core stranded copper conductor connected to common earth dolly including plastic terminal boxes completed all as specified and directed by Engr in Charge. |
| 6 | Supply and fixing switch piano flush type 5 Amp single pole, one wayall as specified and directed by Engr in charge. |
| 7 | Supply and fixing switch socket combination 5 in 1, 6 pin, 5/16 Amp, flush type universal, 240 V completeall as specified and directed by Engr in charge. |
| 8 | Supply and fixing in repair ceiling rose surface bakelite 65 x 50 mm three terminal complete all as specified and directed by Engr in charge. |
| 9 | Supply and Fixing MCB DB single door SPN2 way, 240 Volt complete all as specified and directed by Engr in charge. |
| 10 | Supply and Fixing MCB SPN 32 Amps, 240 Volts, C Curve with breaking capacity 10 KA complete all as specified and directed by Engr in charge. |
| 11 | Supply & fixceilling fan complete with blades, down rods, electronic regulator and accessories, 230 volt, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE 5 Star rated with brushless direct current motor (BLDC) complete all as specified and directed by Engr in Charge. |
| 12 | Supply and fix in replacment of electric water heater storage type steel body with glasslead inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 star rated complete with all accessories such as safety valve, thermostate, NRV connection pipe complete all as specified and directed by Engr in Charge. Note : Old u/s water heater any size any make should be deposited in E/M store yard for BER disposal. |
| 13 | NOTE :- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs 1660.00/- ] |