| 1 | Supply, laying, testing & commissioning of HT 11 KV (Earthed) XLPE insulated screened PVC bedded, electric power cable (heavy duty) ISI markedwith aluminium conductor 11000 volts grade,circular screened with extruded semi conducting compound in combination with copper tape, inner sheath of PVC tape galvanized steel strip flat , around and overall PVC sheathed, armoured conforming to IS 7098 Part II, 1985 amended upto date, of size 3 core 95 Sqmm, ISI marked, laid in trenches or passing through pipes/ducts including taking down old cable of any size all as specified and as directed. |
| 2 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm. |
| 3 | Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with aluminium conductor after removing old one of followingsize:-(a) 10 Sqmm 2 Core |
| 4 | (b) 10 Sqmm 4 Core |
| 5 | (c ) 16 sqmm 4 Core |
| 6 | (d) 120 sq mm 3.5 core |
| 7 | (e) 400 sq mm 3.5 coreNote for Ser Item No 1 & 3 to 7 : Excavation & Earthwork, protection pipe will measured and paid seprately under the relevant item of this Schedule. |
| 8 | Excavation in trenches not exc 1.5 meter wide and not exc. 1.5 mtr in depth for laying of under ground cable, pole foundation and stays etc and getting out in soft / loose soil all as specified and as directed |
| 9 | Returning and filling in, including spreading and levelling, water and well remming in layers not exc. 25cm all as specified and directed. |
| 10 | Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed. |
| 11 | Supply and fixing wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, Three core cable in surface/recessed as required 2x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire (From PVC Junction box to Security light) |
| 12 | Supply & laying of heavy dutyHDPE DWC pipefor HT cablepipe ISI marked of outer dia 110 mm and Inner dia 95 mm polythylenewith smooth internal and external surface for non pressure under ground cable icluding coupler and bends complete all as specified and directed Make : Supreme/Finolex/Prince/Astral |
| 13 | Supply & laying of heavy dutyHDPE DWC pipefor HT cablepipe ISI marked of outer dia 50 mm and Inner dia 95 mm polythylenewith smooth internal and external surface for non pressure under ground cable icluding coupler and bends complete all as specified and directed Make : Supreme/Infra/Finolex/Prince/Astral |
| 14 | M&Lin replacement of40mm dia GI Pipe light grade ISI Marked with all fittings laid in trenches , fixed to walls / poles with FI Clamps of size 40x5 mm all as directed. |
| 15 | M&Lin replacement of50 mm dia GI Pipe light grade ISI Marked with all fittings laid in trenches , fixed to walls / poles with FI Clamps of size 40x5 mm all as directed. |
| 16 | M&Lfor GI Tubes,of size 80mm dia Medium grade, galvanised, with all fitting , laid in trenchesfor protection of cable in road /drain crossing complete all as specified and as directed. |
| 17 | M&L for road cutting upto 300mm deep and 200mm wide for crossing GI pipe line through road including making good the disturbed surface by filling mass concrete (1:2:4)etc complete all as specified and directed by Engineer-in-Charge.Note : Rate of mass concrete is included in quated rate. |
| 18 | Supply, installation, testing and commissioning of outdoor, of ACthree phase , 50 HZ, 315 KVA capacity,IS 1180 ( PART I) : 2014, LEVEL 2 transformer step down , out door type 11000/433Volt (at No Load) copper wound , oil immersed , naturally cooled with external cooling tubes, core type delta connected on primary (HV) side and star connected on secondary (LV) side in accordance with vector symbol DYN-11/vector group-4) with neutral brought on secondary (LV ) Side & having tapping in equal steps of 2.5% from (+) 5% to (-) 7.5% on primary side by means of hand operated off load tap change /correct LT voltage on secondary side including provision of all necessary / standard fittings mainly comprising of:-(a) One cable box on primary HV side having cable glands suitable for 3 core 150 sqmm XLPE 11 KV HT Cable consisting of 03 nos of porcelain HT bushing with brass/gun metal bushing rods complete with nuts and washers.(b) One cable box on secondary (LV) side consisting of 04 Nos porcelain bushing with GM bushing rods complete with GM nuts and washers with one nos of cable gland suitable for reception of out going LT PVC sheathed armoured cables of size 3.5 Core 240 sqmm.(c ) Oil conservator with filter type , drain valve and oil level gauge.(d) Dehydrating breather with first fill of dehydrating agent.(e ) Explosive Vents(f) Thermometer pocket on tank cover.(g) One No 100mm dia dial type thermometer vapour pressure type having range 0-120 degree centegrade with temp reading pointer, max temp indicator and resetting device.(h) Rating plate ith terminal markings.(j) Two earthing terminals on tank/tank cover to facilitate fixing of 32x6mm GI Earth strip. |
| 19 | Item No 18 ...Contd/-(k) Oil Level gauge.(l) Oil Drain and filter valve (m) Oil filter hole with cap/plug with connections complete.(n) Lifting Lugs(o) Air Relief valve plug(p) Four plain solid cast steel detachable rollers.(q) First fill of fresh oil conforming to relevant IS and tested upto 40 KV dielectric strength.(r) Extra bushing for neutral outside the LT cable box for providing independant earthing for neutral.(s) Provision of 02 Nos of danger board 250x200mm size made out of 1.6 mm thick MS Plate, vitreous enameled white with letters, figures in marathi, Hindi and english of voltage and conventional skull and bones in signal red colour , one at HT side and other on LT side .(t) Any other fittings /accessories so as to conform the whole transformer to IS-2026.(u) Buccholz Relay.(w) Chainlink fencing ofsuitablesizebut not less than 45 Sqmtr including gate not less than 1.5 mtr including channel, including line wires, any mesh, size dia 4 mmthick and steel wire mesh aperture 50 mm ofstandards, rails, straining bolts, etc.including necessary hooking binding cutting etc and angle of size 50 x 50 x 6 mm thick angle iron frameflat iron 40 x6 mm cut length including drilling holes for fixing of nut and bolts to hold chain link fencingincluding painting with two coats of synthetic enamel paint over one coat of red oxide primer on all exposed complete .Make: Voltamp, Urja Techniqus, Mahati, Indian Transformer, Silerverline |
| 20 | S&F invertical type air break switch, gang operated, tripple pole, mechnically operated, outdoor type, with all fittings and accessories mounted on andincluding HT 11 KV porcelain insulators and steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements , suitable for 11000 volts, 400 Amps current rating complete including dismantling existing one all as specified and as directed. |
| 21 | S&F of HT 11 KV out door non-linear type lightening arrestor with mountings, accessories complete fixed on cross arms of two pole structure /GI flat strip and connect with same size of ACSR conductor encashed in PVC alkathine pipe with all fittings connected to earth strip with nuts, bolts and washers, transmission class having discharge capacity of 65 KA and rupturing capacity 5 KVA and suitable for working pressure 9 KV RMS compelete including taking down old lightning arrestor all as specified and as directed including dismantling existing one all as specified and as directed. |
| 22 | S&F drop out fuse unit, explusion type for out door air break gang oprated switch, single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts and washer etc synthetic bounded fuse tube complete with line capcity suitable for current carrying capacity upto 100 Amps all as directed including taking down old one all as specified and as directed |
| 23 | S&F stay assembly complete with accessories as shown in Electrical Plate No 1 of SSR 2009 (Part I) using stay rod 20mm dia, including clamps made out of 50 x 6mm MS flat, MS galvansied stay plate 300mmx 300mm x 6mm and galvanised thimble including insulator 90x140mm all as specified and as directed. (loop type insulator, stay clamps, excavation & earthwork and PCCC shall be measured and paid separately under the relevant item of this Schedule. |
| 24 | M & L for replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 25x20cm size |
| 25 | Supply, erecting and fixing in true vertical position of steel tubular swaged pole, 11 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-55, conforming to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of botton portion up to 1.8 mtr length all as specified and provide circular bend 1 No of width 2 cm complete all as specified and directed. (Excavation and earth work, foundation concrete and PCC coping shall be measured and paid separately under the relevant item of this Schedule.) |
| 26 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, botls, washers, welding bending cold or hot, drilling holes for bolts, in any shape or size as indicated or irected and inclusive of one coat of red oxide primer, one under coat and one inishing coat of aluminium paint all as specified and as directed. |
| 27 | Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar1000 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger noticefor 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Main PanelIncoming : - (i) MCCB 630 Amp adjustable type with , 4 Pole,50 KA - 01 No. (Ics=100%Icu)(ii) Digital maltifunction meter with CT– 01 No .(iii) Indicating lamp LED type one set in incoming phases.(iv) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 Volt grade IS 694 marked of appropriate gauge including all copper lugs.(vi) Connection from MCCB to Busbar shall be of solid Aluminium conductor.(vii) MCCB shall be provided with suitable spreader of aluminium conductor for fixing of incoming cable.(viii) KWH meter CT operated as per suitable capacity of LT Panel.Outgoing ways :- MCCB 500 Amps adjudtable type,4 pole,36 KA-02Nos(Ics=100%Icu )MCCB 63 Amps adjudtable type, 4 pole,36 KA-01Nos(Ics=100%Icu ) |
| 28 | M &L for construction ofplinth (of size 2000mm x 2000 mm x 1500 mm) including excavation in trenchs in any type of soil,PCC 1:4: 8 in foundation fly ash bricks masonary in cement mortor1 : 6 ,filling with moorum inside the plinth and RCC 1:2:4 over plinth including 16 mm bar reainfrocement with center to centre distane 100mm and external surface of masonary shall be plasterd with cement morter 1:4 andpainted with weather coat paint ( double coat paint ) of shadecomplete all as specified and directed by Engr in charge |
| 29 | M & L for fabrication of bus bar chamberof sizenot less than 600 x 600 x450 mm suitable for415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion ofsuitable cable glands for all incoming and out going cable including grouting of panel board60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Incoming MCCB : 160 AMps ,4P,25 KA Busbar Capacity : 250 AMpsmounted on DMC/ porcelain insulator support with RYB indicatorOutgoing : one MCB/MCCB mounted chanel slotted500 mm long Notes:- 1. The PanelShould be approved by CPRI.2.The rates Quoted shall include for earth work,Plinth protection around the panel apprx 75cm and excavation for angle iron frame for foundation of panel board up to 0.50 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.40 M from GL to the bottom of panel board. |
| 30 | M&L forearthing with galvanised steel earth plate electrode of size 600 x 600 x6mm thick buried vertically in ground not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level and connected to GI strip 32x6 mmby means of nuts, bolts and washers and encased in and including 15 dia GI medium grade pipe upt 2.4 mtr height form ground level fixed by MS flat iron clamp 40mm x 5mm with nut, bolt and washers, GI strip fixed to base along pole and connected to over head line for providing earthing to HT pole/feeder AB switch LA complete with charcoal dust, salt packed around plate 150 mm thick including watering GI pipe, medium grade 40 mm dia with blanking cap 1.5 mtr long fixed to funnel with wiremesh complete with PCC chamber and RCC chamber over all as per Electrical Plate No 5 of SSR Part I - 2009 incl excavation and earth work in any type of starta and testing on completion. |
| 31 | Supply only in electrical outdoor installation yard, stone aggregate of size 20 mm at 11KV substations / Near DP structures after through cleaning, anti grass treatment etc all as per pecified and as directed. |
| 32 | M&L for cement concrete (1:3:6 ) type C1 using graded stone aggregate as in foundation for pole including necessary form work all as specified & directed. |
| 33 | M & L for PCC(1:2:4) type B1 using 20mm grade stone aggregatesfor copingand similar work all as specified and directed. |
| 34 | Supply, erecting and fixing in replacement of true vertical position of steel tubular swaged pole, 9 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-31, conforming to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of botton portion up to 1.8 mtr length all as specified and provide circular bend 1 No of length 2 m including taking down existingcomplete all as specified and directed. (Excavation and earth work , foundation concrete and PCC coping shall be measured and paid separately under the relevant item of this Schedule.) |
| 35 | S&F Shock Proof, Rust Proof, Fire Retradrant, Non-transparent Kiosks Pole Box of size 200 x 175 x100 mm made of Engineering Plastic on Piece moulding for Outdoor type, Heavy duty with 4 No. insulated Alunminium Bus-bar of 60 Amp capacity, mounted on Unbreakable Insulators MCB SP, 10 Amp, complete with Aluminium Lugs of suitable size upto 50 Sqmm including 2 No. Flat Iron 40x3mm Clamps with suitable size Mild Steel Bolts, Nuts & Washers, etc.including Taking down Unserviceable Pole Box of any description from any Height, complete all as specified and as directed. |
| 36 | Supply and fix in replacement New generation energy saving and environmental friendly long life LED street light made up of pressure diecast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07, with luminaries 100 watt, with inbuilt surge protection 10 KVincluding 50 mm dia size ofGI Bracket of length 1.2 Mtr, with Clamp,Nut, Bolt and washer, connection with 1.5 sqmm 3 runcopper wire from junction box to streeght light and4 sqmm 2 core aluminium servicecable pvc insulated 2.5 RM per fitting where over head line existingforconnection of street light to over head conductor complete all as specifiedand directed. Make : Havells cat part no ENDURAOMNIPLUSSL120WLED757SASYTOPC and equivalent |
| 37 | Supply and fixing of 40 Amp time light DB with TP 40 amps mcbat incomer with 40 Amp AC3 duty contractor along with design as per IEC 61439, material and CRCA sheet up to 1.2 mm with Asrtonomical time switch complete prewired IP 55 protection auto manual selector switch for auto manual selector switch for auto manual operation,power indicator and 2 Amp fuse for protection of time switch,input output terminal block of termination of input output cable with gland special provision of incorporation of under voltage over voltage relay for protection of incarporated contractor coil,including the cost of labour charges for erectingon pole /walls/panel including clamps,nut bolts to complete the job up to the entire satisfaction of Engr in charge of work .Make : Indoasian cat ref no TL040ASO and equivalent. |
| 38 | S &F PCC Cable route Indicator with suitable reinforcement ofsize 50 x 10 x 10 cm with letter inscribed on both side as \"MES LTCABLE \" of specified front side not less than 30 mm as directed andcomplete using PCC 1: 2:4 B1 using 20 mm graded stone aggregate and including painting using cement based paint to thesatisfaction of engr in charge |