| 2 | Supply and installation in repairs, commissioning and testing polycarbonate ASTA CPRI approved OEM made DC SMB (24 IN 1 OUT) outdoor type Floor Mounting type (Mini. Size 2550x1450x255mm). The DC SMB Isc : 18.5A, SYSTEM VOLTAGE : 1000V DC shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES shall be DESIGN TEMPERATURE: 50 degree centigrade , DESIGN STANDARD: IEC 60 364-7-712, UV resistance, anti-acid, anti corrosive and FR material.The manufacture of DC SMB shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. DEGRRE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITHIEC 60529 and the gasket shall be internally embedded made of polyurethane. The Panel Should be mounted on angle legs of size 40mm x 40mm legs with Gound clearance 450mm duly spray painted internally and externallywith two coats of synthetic enamel paint over a coat of red oxide primer ,legs grouted in PCC(1:2:4) Type B-1(using 20 mm graded stone aggregate) including all provision of opening for nincomming Bus Bar Rating 30x10mm (TIN COATED CU)/outgoing 50x10mm(TIN COATED CU). The DC SMB Cable Size I/c-1Cx 6SqmmCAble - 48nos (Spare 4 Nos), RS 485-2Cx1.5Sq.mm Cable-1 No and O/G 1Cx300Sq.mm Cable-2Nos, Earthingfor SPD 1Cx16Sq.mm Cable-1 No made by aproved Hensel, ABB,Schneider & they shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel as per following.a). 1. In accordance with IEC 60 439-1 (IS8623) at ASTA ( CPRI Bhopal Laboratory ) and IEC 61 439-2 for powerswitchgear and controlgear assembly. The type test report as per CPRI ( in accordance with IEC 60 439-1 ) should consist with following:i) Degree of protection of system ii) Temperature Rise Limitiii) Dielectric Properties (iv) Short Circuit Withstand Strength (v) Effectiveness of protective circuit (vi) Clearance and creepage distance (vii) Mechanical Operation (b). Glow wire test at 9600C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self- extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit (c).Degree of protection against mechanical load IK 08 (5 Joule) ) in accordance with accordance with EN IEC 62262 (d). Rated insulation voltage should be 690Vac / IEC 1000 Vdc as per IEC 60664 (e). UV-resistance in accordance with IEC 61 439-1, Clause 10.2.4: The material is examined for UV resistance.INCOMER:-500A , FP 1000V DC Isolator with Direct Handle, B.B - 01 No - Make Socomec, Auxiliary contact - 01 No Make Socomec,40A, 1000V DC Diode With Heat sink - 24 Nos,1000V/24VDC Power Supply Unit [DC/DC Converter] - 1 No.,1000V DC Surge Arrester, Type ll With FM - 01 No, Surge Protector for ataline(DLA-12D3 Type) - 01 No,Hall Based String Monitoring PCB/Card with RS 485 MODBUS - 1 No, String Monitoring PCB/Card (Slave) - 2 Nos.,Voltage Monitoring device - 1 No,3A,1000V DC Fuse Link - 2 Nos,.30A, 1000V DC Fuse Link - 24 Nos,32A, 1000V DC Fuse Base without Indication - 26Nos.Providing the suitable Terminals,Internal wiring 6Sq.mm Cable Diode terminals + VE Diode+VE fusesNOTES:) Contractor shall the test reports & drawing. 2. M&L for REVA Type 1+2 AC SPD 3AYNPV1500-SPD5 - Each - 23. Supply and fix 6 sqm Solar DC Cable Each 2004. Supply and fisSolar pnelMC4 Y Connector Each 205. Supply and fisSolar pnelMC4 YConnector RM 42 |