| 1 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy ≥120 and <135 lm/Watt)Supplying,Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).70 watt |
| 2 | Supplying of following sizes of XLPE (Cross Linked Poly Ethylene) Insulated PVC Sheathed Alumimium Conductor Armoured Power Cable of 1.1 KV grade including connection, testing etc. as required.2C x 16 sq. mm |
| 3 | 4C x 25 sq. mm |
| 4 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size Direct-In-Ground including Excavation and Refilling the Trench etc. as required, but Excluding Sand Cushioning and Protective Covering.Up to 35 sq. mm |
| 5 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.Up to 35 sq. mm |
| 6 | Supplying and drawing of following sizes FRLS PVC Insulated Copper Conductor, Single Core Cable in the existing surface/recess steel/PVC conduit as required.3C x 1.5 sq.mm |
| 7 | Supplying and Laying of following size DWC HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS: 14930, Part-II complete with fitting and cutting, jointing etc. direct-in-ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia. (OD-63 mm & ID-51 mm nominal) |
| 8 | Supplying and Replacement of floor mounted LT Feeder Pillar cubical type double door of size 1000 (H) mm x 900 mm (W) x 300 mm (D) with general arrangement made out of 2 mm thick MS CRCA Sheet having hinged gasket covers and screwed knobs with double locking arrangement & Locking Hooks and separate Rain Protection Cover with extension of 100 mm in Width & Depth, supported with MS Angle Iron legs and bottom frame of size 40 mm x 40 mm x 6 mm x 1 mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs (around 25% of length) should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, Painting with Primer, Numbering, Identification Plate of Component embossed and/or printed in Metalincluding Supply & Fixing of following accessories etc. complete as required (as per drawing approved by Engineer-in-Charge).a) 125 A, 36 kA Ics=100% Icu and Operational Voltage 690 V, 4 Pole MCCB- 1 No. (Incomer).b) 3-Phase Submersible Pump Controller (MU-G10) with Single Phase Preventer up to 10 Hp Pump Set, Relay Range 13 to 21 Amp- 1 Set.c) Electronic/Analogue Timer of model FM1/Quartz Daily 110 VAC-240 VAC Base/DIN Mounting in the existing Panel.d) 3-Pole Power Contactor of AC3 Rating 32 Amp, MNX 32 type.e) Ammeter (0-100 A) 96 sq. mm in size and 100/5 CT’s Ratio- 1 Set.f) Voltmeter (0-500 V) 96 sq. mm in size with Selector Switch- 1 Set.g) Indication Lamp (RYB) with Control HRC Fuse with Fuse Fitting- 1 Set.h) 6 A to 32 A ratings, DP MCB, “C” curve, 10 KA breaking capacity- 3 No.i) 6 A to 32 A ratings, TPN MCB, “C” curve, 10 KA breaking capacity- 2 Nos.j) 150 A, 4-Strip Al. Bus-Bar of minimum 400 mm long and of size 30 mm x 5 mm with sleeve and nut-bolts- 1 Set.k) 200 mm x 150 mm MV Danger Notice Plate of 2 mm thickness- 1 No.l) Earthing Stud- 2 Nos.m) Lifting hook on the top of feeder pillar- 1 Set. n) Lamp Holder inside Feeder Pillar- 1 No.o) 4 Way Neutral Link- 2 Nos. |
| 9 | Supplying, Fabrication and Installation of Wire Mesh Protection Frame for Existing Feeder Pillar, constructed from 10 SWG MS wire mesh with a Nominal size of 75 mm x 25 mm Rectangle. The Frame dimensions are 1.5 mtr. (Width) x 1.00 mtr. (Depth) x 2.00 mtr. (Height). It includes a Base Frame made of 40 mm x 40 mm x 6 mm MS Angle Iron, MS Strip Supports of 40 mm x 6 mm, and 0.5-meter-long leg supports of the same Angle Iron, all as per the approved drawing. Additionally, provide a suitably sized door, Supply and Fix a godown lock with locking arrangement, painting, and grouting with 1:2:4 Cement Concrete Foundation, as approved by the Engineer-in-Charge, complete as required. |
| 10 | Supply and replacement, laying, testing & commissioning of \"B\" class medium duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :a) 50 mm dia. |
| 11 | Supplyingandreplacement of submersible pumpsets (water filled motor) operating on 3 phase, 415 Volts, 50 Hz of following specification including lifting of dismantle Pumpset & Lowering of newsubmersible pump set in the existing bore well up to the required depth alongwith existing G.I. pipes and sub. Cable etc. water proof, jointing of sub. cable, Replacement of reqd. nuts- bolts, washers and packing, nipple, reducer, connection, testing etc. complete as reqd .a) Approximate Head Range (m)-12 m - 103 mb) ApproximateDischarge Range (L / min)-60 L / min - 290 L / min c) Capacity – 5 HP d) No. of stages - 10e) DeliverySize- 50 mm |
| 12 | Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. complete as required.3C x 2.5 sq. mm |
| 13 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.i) 4 Pole MCCB 100 Amp. 30 K.A. |
| 14 | ii) 4 Pole MCCB 250 Amp. 36 K.A. |
| 15 | Earthing with GI Earth Pipe 4.5 meter long, 40 mm dia. including accessories, and Providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 16 | Providing and Fixing 25 mm x 5 mm GI Strip on surface or in recess for connection etc. as required. |
| 17 | Providing and Fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub-main wiring/cable as required. |
| 18 | Painting of Existing GI Poles up to 4 to 6 meters in Height, applying Two Coats of Luxol Hi-Gloss Enamel-Colours including Red Oxide Primer, with Numbering of the Poles. This includes Painting the Base Plate and Mounting arrangements etc. complete as required. |
| 19 | Provision of Qualified Technical Staff for the arrangement, Maintenance, and Operation of Path/Park Lighting Systems to support the entire duration of \"Flower Show/Palash-2026\" event as per attached Terms and Conditions. |
| 20 | Supplying , Installation , testing and commissoning of15 watt LED with IK≥ 07, IP≥65 & CCT-3000 K mountedspike light with modern design , compact size with high powerLED to provide focused lightwith connection making necessary arrangement for input supply including conduit etc. as reqd. |
| 21 | Supply and installation of 30watt LED cylindrical type downlighter having aesthetic aluminum housing and a superior power coated finish iaking suitable hole on gate /ceiling for fixing of light ,providing suitable accessories for fixing arrangement like nut bolt,testing commissiong, making necessary arrangement for input supply including conduit etc. complete as required. |
| 22 | Supplying , fabrication & fixingof wooden extension board of suitable size including 16 amp power socket, and switch in 5 numbers each including in internal wiring of size 4 sq. mm. with copper wire with with all accessories & extra 2 mtr. Wire for input supply complete as required. |
| 23 | Supplying and Temporary Erection of wrapped timber/balli/bamboo support of suitable size and strength, up to 15 ft overall height, embedded 3 ft into the ground, including vertical alignment and bracing as required; temporary mounting of existing 70 W Flood Light on the erected support with Supply and Fixing of all necessary accessories such as clamps, nuts-bolts, and rassi (binding rope) to ensure safe and secure fixation; complete in all respects for temporary use as directed by the Engineer-in-Charge and/or AE(E)-in-Charge. |
| 24 | Painting of existing wire mesh protection frame/ feeder pillar of different size with 2 Nos of enamel paint coating incuding primer,cleaning etc. complet as required. |