| 1 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .11 KV End Termination Kit Outdoor type3 core 120/150/185 Sq.mm |
| 2 | 11 KV Straight Through joint Kit3 core 120/150/185 Sq.mm |
| 3 | 33 KV End Termination Kit Outdoor type3 core 240/300/400 Sq.mm |
| 4 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .3 core 185.0 Sq.mm |
| 5 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .1 core 400 Sq.mm, 33 KV ( as per JVVNL) |
| 6 | Supply & fixing and fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . ( M.S channel 100X50X6 ,M.S angle 75X75X6 ) |
| 7 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR300.0 Sq. mm1 core |
| 8 | Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 9 | Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double pole as per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 10 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom\"s specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRLT cross arm 1200 mm long with clamp |
| 11 | Supply and erection of RS joist of 116 x 100 mm, 11 Meter long with the welded/ bolted top hamper 65 x 65 x 6mm (0.7 Mtr long) making necessary arrangement for fixing 11 kV \"V\" cross arm, LT bracket and guard wire bracket, grouted in ground 1/6 th of its length and fixed with cement, coarse and grit in 1:3:6 ratio in 1/5th of its length (40cm dia) from the bottom including two coats of aluminium paint over the complete length of joist etc. as required. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 12 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM. |
| 13 | Supply and fixing of 11 KV Outdoor 4 way feeder pillar Box confirming to Discom specifications and made of 3.15 mm thick powder coated CRCA sheet enclosure confirming to IS 14772/IEC 60670 (1989) of Size 1000 mm x 1000 mm x 1500 mm, Both front and rear doors should have 3 heavy duty M.S. hinges with Brass pin inserted inside and locking arrangements.The bottom foundation frame stand should be made from 65x65x6mm MS Angle with four legs of 200mm height provided with 150x150x6mm flats grouted with C.C. of M-10 grade to achieve the height of 2.0 feet above the road level suitable for four outgoing. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 14 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 15 | Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 16 | Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 17 | Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 18 | Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 19 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 20 | Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 21 | Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 22 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR .16.0 Sq.mm |
| 23 | 150.0 Sq.mm |
| 24 | 25.0 Sq.mm |
| 25 | 6.0 Sq.mm |
| 26 | 185.0 Sq.mm |
| 27 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR100 Amp. Distribution Kiosk suitable for Underground cable of Size 500mm x 550 mm x 700 mm |
| 28 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR16.0 Sq. mm4 core |
| 29 | 150.0 Sq. mm 3.5 core |
| 30 | 185.0 Sq. mm 3.5 core |
| 31 | 6.0 Sq. mm 2 core |
| 32 | Labour charges for Dismantling of service line connection of industrial/domestic connection, single phase supply/three phase supply system on existing cross arm PCC pole, MS channel different sizes of poles along with the ACSR conductor/service line weather proof cable/ Armoured cable, guard wire, stay wire and other electrical item of the pole comming along the alignment of the road and removal and re-rolling as well as handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and temporary supply electrical connection to domestic/industrial connection to consumer where supply disconnected and as per the direction of Engineer Incharge and clean the site good as per the requirement , all complete works. |
| 33 | Labour charges for Dismantling of following existing street light electric poles with street light fixtures, underground cable, MS box and other electric items of the pole coming along the alignment of the road and removal and re- rolling MS poles/PCC poles of different sizes as well as handing over the same to DISCOM/UIT/MC store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from concering authority, all complete works. |
| 34 | Labour charges for Dismantling of existing electric poles (PCC poles, MS channel, Lattic tower 12.6mtr. , 11 mtr. along with the ACSR Conductors, 11KV/33KV/LT line etc. 11KV insulator LT insulator guard wires, staywires and other electric items of the pole coming along the alignment of the road and removal and re- rolling PCC pole, MS channel different sizes as well as handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from DISCOM/ concering authority, including all complete works. |
| 35 | Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per IS :2551-1982 & specification of Discom on the existing poles complete in all respectas as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 36 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 37 | Removing & re-fixing of Transfrmer including all accessories as required with feeder piller box up to testing commsiisong of all type of work and fencing, installtion of all capacity of distribution transformer ( as per JVVNL) |
| 38 | S&F of 11 KV Link Chamber for UG network ( AS PER BESL) |
| 39 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 160 mm size Please Enable Macros to View BoQ information |