| 1 | SH-1(Wiring) |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. i) Group B |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.i) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.ii) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.iii) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | SupplyinganddrawingfollowingsizesofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. i) 3 x 1.5 sq. mm |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recesincluding cutting the wall and making good the same in case of recessed conduit as required.i) 20 mm |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modularsocketoutletand2nos.5/6 A modular switch, connectionsetc.asrequired. (Forlightplugs tobeusedinnon residential buildings). |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required |
| 11 | SH-2 (Fans, & fittings) |
| 12 | Providing and installaion of 25 W LED tube Light , 6500K, Decorative ultra slim polycarbonate LED lighting fixture with high lumen output, environmental friendly,energy efficient ready to use pack,complete with all accessories and tube/lamp etc directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as required. |
| 13 | Providing and installaion of 10 W LED tube Light 2 FT, 6500KLED lighting fixture with extruded polycarbonate, environmental friendlyenergy efficient ready to use pack directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as required |
| 14 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades having CURVED BLADE DESIGN, anti-dust lacquer coating for anti dust purpose, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 225 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%,electronic regulator or remote and remote holder unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for wide voltage range of 140 280 V, 50 Hz, single phase AC Supply, 5-year warranty, earthing etc. complete as required. |
| 15 | Supplying and installation of400 mm BLDC copper motor based wall fans, Wattage 35 W, Finish Type-Gloss Finish, No.of Blades- 3, Air Delivery (CMM) 76, Speed 1500 RPM, Voltage range 165 - 285 V connection, testing, commissioning i/c nut bolt supporting clamp, remote and remote holder connecting wire etc as required |
| 16 | SH-3 (MCCB, MCB & DB’S ) |
| 17 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)ii) 12 way, Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. i) Single pole |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. iii) Double pole |
| 20 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. asrequired. i) 25 A |
| 21 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. asrequired. ii) 40 A |
| 22 | Supplying and fixing of 4 way, 100 AmpsWall Mounted Busbar Chamber, 415 volts,Busbar made of ETP Grade Copper, Standard - IS 61439-6, Colour - RAL 7035 Semi Glossy, DB Sheet Thickness - 1 mm & 1.6mm, Ambient Temperature - 40ºC, Support Material for Busbar - DMC, Complete with connections, etc. as required. ( make like: Havells/ Anchor/ legrand,ABB, Schinder) |
| 23 | SH-4 (EARTHING ) |
| 24 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories,andprovidingmasonryenclosurewithcoverplate havinglocking arrangement and wateringpipe etc. with charcoal/ coke and salt as required. |
| 25 | Providing and fixing 6 SWG dia GI. wire on surface or in recess for loop earthing as required. |