| 1 | Excavation in trenches n. exc 1.5 m wide for foundations, laying cables/ pipes etc. not exceeding 1.5 m deep and getting out in SOFT/LOOSE soil complete, all as specified |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers notexceeding 25cm thick complete, all as specified. |
| 3 | Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete, all as specified. |
| 4 | Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified.NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment. |
| 5 | Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends, or edges of landings etc. and cutting chases for concealed water tubing, concealed conduit wiring, etc., and making good, cutting not exceeding 10 cm girth, in brick walls, complete all as specified. |
| 6 | Brick protection with old size sub class \"B\" bricks laid flat across the route of underground cable all as specified and directed |
| 7 | Boring holes under roads, paths, hardstanding, pavements, runway, taxi trackof any desciption by trenchless technology using ultrasound technique or by maual bring method of hole technique for passing pipe lines (any description)of 150 mm bore pipe and including HDPE pipe of suitable size as required for 0.4 Mpa working pressure complete. |
| 8 | Supply, laying, jointing & testing of LT XLPE insulated cable screened,bedded, galvanised steel strip or wire armourd cable(heavy duty) 1100 volt gradewith aluminium conductor conforming to IS-7098 (Part-I -1988)laid in trenches/ ducts/ through pipes/ in floors / underroads/ hard standing /along poles and testing complete all as specified of following sectional area:- |
| 9 | 10 Sq.mm, 2 core |
| 10 | 50 Sq.mm, 3.5 core |
| 11 | Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes, ISI MARKED, with 3 mm thick plastic/bakelight laminated sheet cover having necessary cutting for fixing switches/ socketscomprising the following: - |
| 12 | One light/fan/exaust fan point controlled by one switch (one way) of 6 Amp or one fan point controlled by one switch (one way) of 6 Amp & fan regulator etc. or for bell/buzzer with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit, complete all as specified and directed. |
| 13 | One Socket outlet of3-pin/ 5-pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, complete all as specified and directed. |
| 14 | One Socket outlet of3-pin/ 5-pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC heavy duty concealed conduit,complete all as specified and directed. |
| 15 | One socket outlet three pin, 6/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit not less than 20mm dia all as specified. |
| 16 | Switch piano flush button single pole one way, 6 Amp complete all as specified. |
| 17 | Socket outlet multipurpose having provision for 2&3 pin, 6 Amp, flush type, complete all as specified and directed. |
| 18 | Switch Socket combomultipurpose of capacity , 2&3 pin, 6 Amp/ 15/16 Amp, complete all as specified and directed. |
| 19 | Ceiling rose, surface bakelite, 65 x 50mm, three terminals complete, all as specified. |
| 20 | MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, \"C\" curve type of rating6 to 32 Amp, complete all as specified. |
| 21 | MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, \"C\" curve type of rating32 to 63 Amp,complete all as specified. |
| 22 | Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 240 volt, breaking capacity not less than 10 kA, complete all as specified. |
| 23 | Sheet metal enclosure for DB for fixing MCB’s, isolators etc., having IP-43 protection, suitable for surface and flush mounting, complete all as specified comprising the following: |
| 24 | SPN, 8 way with 200 Amp rated bus bar, 240 V, double door type. |
| 25 | TPN, 4 way with 200 Amp rated bus bar, 415 V, double door type |
| 26 | Sub main wiring (with approved colour coding as per IS) with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade (main cable: number of runs as indicated below along with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade for earthing in conduits, with and including rigid non metallic PVC medium duty concealed conduit not less than 25mm dia complete all as specified for the following: - NOTES: (i)For payment purposes, total runs of main cable (each run of one running metre) as mentioned above and one run (one running metre) of earth cable shall be considered together as \"1 RUNNING METRE\" |
| 27 | 2 runs of 4 Sq. mm main cable + 1 run of 4 Sq. mm earth cable |
| 28 | 2 runs of 6 Sq. mm main cable + 1 run of 6 Sq. mm earth cable |
| 29 | Surface mounted environment friendly LED 20 Wbatten with polycarbonate housing & integrated electronic driver, lumen output should not be less than 90 lumens per watt including making connections up with three core flexible copper conductor cable, complete all as specified. MAKE: Havells Cat No. LUMILINENXTBS20WLED830SPCWH or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 30 | Environment friendly, modern design, energy saving surface mounted, decorative 10 W bulk head LED luminaire with premium quality diffuser for glarefree light, 6000K, including making connections, completeMAKE: Havells Cat No. HEXAFT10WLED857SSYMBOPCor equivalent in makes mentioned in Appendix \"B\" |
| 31 | Ceiling fan complete with blades, down rods, stepped type electronic regulator and accessories, 230 volt, 1200mm sweep with service value 6.00 BEE with brushless direct current motor (BLDC) including PVC insulated and overall sheathed flexible 3 core 0.5 Sq.mm copper conductor cable complete all as specified |
| 32 | Electronic meter temper proof LCD display with polycarbonate cover 230V, 10-60 amp, accuracy class-I 50Hz, conforming to IS 13779, IP -54,with parameters to show data, time, current reading, load,PF, voltage and KWH complete all as specified and directed |
| 33 | Hi wall split units indoor / outdoor complete with cordless remote control unit invertar type and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rating cooling & heating function and EER 3.2 of capacity 1.5 Tonand including mounting accessories kit with stand complete all as specified. |
| 34 | Hi wall split units indoor / outdoor complete with cordless remote control unit invertar type and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rating cooling & heating function and EER 3.2 of capacity 2.0Tonand including mounting accessories kit with stand complete all as specified. |
| 35 | Note : for Item No 23 & 24 : The installation shall include mouting/ fitting indoor and outdoor unit at respective locations. Laying refregerent piping, drain pipe utp 6mtr length and connecting both units after drilling holes, putting PVC sleeve, sealing and finishing the same duly matched with adjoining surface refrigerant pipe shall be insulated with expanded polythelene foam not less than 5mm thick. Leak testing of the entire system after installation to be carried out. Rate quoted will include charging refrigerant gas in the unit, suitable electric connection between indoor and outdoor unit (upto 6 mtr) and upto switch (upto 3 mtr) |
| 36 | Voltage stabilizer for automatic operation single phase naturally air cooled indoor type & designed for input variation between 170 to 270 volt with output voltage stabilizer at 230 V with accuracy of + 2.5% and current capacity 2 KVA complete. |
| 37 | Voltage stabilizer for automatic operation single phase naturally air cooled indoor type & designed for input variation between 170 to 270 volt with output voltage stabilizer at 230 V with accuracy of + 2.5% and current capacity 3 KVA complete. |
| 38 | Voltage stabilizer for automatic operation single phase naturally air cooled indoor type & designed for input variation between 170 to 270 volt with output voltage stabilizer at 230 V with accuracy of + 2.5% and current capacity 5 KVA complete. |
| 39 | Water cooler electric driven (single phase) having approx storage capacity of 80 ltr and nominal cooling capacity of 40 ltr per hour complete all as directed. |
| 40 | Refrigerator electric driven single phase, suitable to operate between 100 to 300V AC 50 Hz supply. 165 to 198 ltr capacity. BEE 5 star energy rating, frost free cooling technology completed |
| 41 | Air termination, single pointed aluminium rod 12 mm dia 300 mm long complete all as specified. |
| 42 | Aluminium strip of size 25mm x3mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as specified |
| 43 | Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GIstrip 32x6 mm as earthing lead by means ofGI or steel bolts/nuts/washers, protected by 15 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mmbore GI light grade pipe for watering and including funnel, wire mesh, RCC cover, reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steel handle 12 mm dia, using round bar, PGI funnel with wire mess & frame, PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, all as specified & shown in electrical plate No. 3 of MES Schedule Part – I., complete all as specified. Note:- (i)PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate.(iii) Earth resstance shall be less than 3 ohm. In case the test results are not found less than 3 ohm, complete earthing shall be redone by the contractor without any extra cost to Govt. |
| 44 | LT Panel Board factory made CPRI approved panel, weather, dust & vermin proof outdoor cubical compartmental type, double door, fornt and back side openable, with providing rubber/PVC gasket of suitable size all sides of door, with copper busbar wrapped with pvc tape/sleeves with maintained the colour code and copper strip busbar of suitable rating to MCCB input andMCCB output of suitable length, made out of 3.00 mm thick mild steel CRCA sheet with 40x40x6mm size angle iron supporting frame including applying two cats of Powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing/incoming including PCC foundation complete all as directed and specified installation, commissioning and testing and comprising of the following fitment accessories:-INCOMING(a)Copper strip busbar of current carrying capacity 400Amps wrapped with PVC sleeves with maintained the colour code and provision of making holes with copper nuts, bolts & washers for cable connections including hydorgrapic insulators with nuts & bolts at both ends = 04 Nos(b)MCCB IP 44 and IP 66/67 protection, 4 pole,l 415 volts, Lcu=36 KA breaking capacity, rating 200 Amps, adjustable thermal magnetic type, thermal release range (64 to 100%) with O/L, S/C protection including all fixing accessories with both ends spreader links -01 Nos(Make : Legrand/Scheider/L&T).(c)LED Neon indicator lamp (RYB) with holder, 230/250 volts, AC-01 Set (set of three) Make:- AE/L&T.(d)DIgital Ammeter of range (0-400) Amps, flush mounting type of size 100mmx100mm(4\"x4\") square dial withy CT\"s of ration 630/5 and selector switch-01 set(Make: Legrand/Schneider/L&T).(e)DIgital Voltmeter of range (0-500 Volts, flush mounting type of size 100mmx100mm(4\"x4\") square dial withy CT\"s of ration 630/5 and selector switch-01Nos (Make: Legrand/Schneider/L&T).OUTGOING(a) MCCB IP 44 and IP 66/67 protection, 4 pole,l 415 volts, Lcu=36 KA breaking capacity, rating 160 Amps, adjustable thermal magnetic type, with O/L, S/C protection including all fixing accessories with both ends spreader links -01 Nos(Make : Legrand/Scheider/L&T).(b) Spare Pocket for MCCB-02 Nos |
| 45 | Taking down and refixing of existing Ac 1.5 Ton split type with voltage stabilizer the installation shall include mounting/fitting indoor and outdoor unit at respective location laying existing refregerent piping with new insulator drain pipe upto 6 mtr length and connecting both units after drilling holes putting PVC sleeve sealing ang finishing the same duly matched with adjoining surface leak testing of the entire system after installation to be carried out rate quoted will include required top up refrigeratent gas unit suitable electric connection between indoor and outdoor unit (upto 6 mtr ) and upto switch (3 mtr) complete. |