| 1 | Engineering, procurement and construction of infrastructure work as listed in Schedule \"A\" section-I(Srl item No. 1 & 2) complete as detailed in scope of work including internal water supply & internal electrification work, DBR and other documents of the tender complete as specified and directed. |
| 2 | Lump sum price worked out by the tenderer for“EXTERNAL ELECTRIC SUPPLY WORKS\" as listed in Schedule ‘A’ Section -III |
| 3 | Schedule ‘A’ Section -III (EXTERNAL ELECTRIC SUPPLY WORKS) |
| 4 | Supply, laying of Double wall corrigated pipe of outer dia 63 mm and inner dia 50 mm for cable protection complete all as specified and directed by Engineer - In - Charge. |
| 5 | Supply, laying of Double wall corrigated pipe of outer dia 110 mm and inner dia 93 mm for cable protection complete all as specified and directed by Engineer - In - Charge. |
| 6 | M & L for boring of holes under main road pavment,hard standing by trenchless technology using ultra sound tecnique and necessary machinefor accomodet upto 40mm bore GI tube (light grade) in the drilled holes,returning ,filling in the end working space including removal of surplus soil and making good the surface.Note : (i)GI pipe light grade shall be measured and paid separately.(ii) Only lengh of the road/had standing/pavement will be measured and necessary excavation at both side of bore will bewill be mearured and paid separately under relevent item of the BoQ |
| 7 | Supply & fix LT panel out door (Kiosk type) type, weather & vermin proof MS sheet housing 3.15mm thick, powder coated over a coat of primer, double door, front & rear openable type, mounted on 40x40x6 mm angle iron frame, floor mounted type with one MCCB, 4 pole, 125 Amp, 25 KA 415 volts as (incomer) and 63 Amp 4 pole (outgoing)-03 Nos, 40 Amp 4 pole MCCB -02 (Outgoing) Nos copper bus bar 200 Amp of length not less than 60 cm, 4 pole duly drilled with holes for cable connections, after due approval of panel drawing including PCC pedestals of suitable size, removal of old unsv panel, making good the area complete all as specified and directed by Engr-in-charge. |
| 8 | Supply, installation, commissioning and testing of factory made cubical LT feeder pillar box, out door type IP 65, powder coated suitable for floor mounting made out of 3.15 mm thick CRCA sheet with front hinged opening with rubber lining, having flush locking arrangement complete providing sufficient space for cable entry from sides suitable including copper strip 1x4 Nos , 150 amps rating mounted on bus bar insulators for connecting with MCCB at outgoing to connect mother accessoriesand consist of following |
| 9 | Incoming |
| 10 | (i)MCCB63 Amps, rating 415 Volts, 4 pole cap 25 KA with thermal magnetic setting type - 01 No. |
| 11 | (ii)Voltmeter with selector switch 0-500 V- 01 No. |
| 12 | (iii)Ampere meter0-50 Amps with CT and selector switch - 01 No. |
| 13 | (iv)LED indicating lamps RYB-01 Set (Set of three). |
| 14 | Outgoing |
| 15 | (i)Supply and fix 3 Pole MCCB 32 Amp, 50 Hz, 415 V with rupturing capacity 18 KA. 02 Nos |
| 16 | (ii)S&F nature switch for automatic ON/OFF of street light by sensing natural light of 3 phase upto 12KW load. For switching ON< = 30 lux,For switching OFF>=10 Lux, Auto high voltgae sense and trip, auto low voltage sense and trip, 50-60HZ, IP66 protection class 2, with copper wiring by minimum of 10 Sqmm . |
| 17 | S&F polycarbonated unbreakable Junction box with fuse provn and suitable connection for three phase incoming cable, single phase out going cable endorsed in thermo plastic enclosure.Shock proof safe IP 65, weather proof, rust proof, dust and water proof internally embedded gasket with provn for cable entry through glade of size 200x160x98mm along with MS Clamps copper bus bar for three phase connection and 02X MCB SP 6 Amp 10 KAincl single phase2.5 sqmm copper conductor PVC sheathed as required at site for electric connection to LED lights and connecting wire from JB to LED fitting as required complete all as specified directed. |
| 18 | M&L for Earthing complete with galvanized iron slotted pipe of dia 40mm bore, 3 mtr long (earth pit not less than 10 mtr deep below normal ground level) surrounded by adequate quantity of charcoal, dust and salt to packed thickness of 15 cm on all sides, connected to GI Strip 32X6 mmby means of bolts, nuts check nuts and washers of galvanized iron and steel earth and rivetted/welded to earth plate at one end and other end of strip connected to equipemnent body/ test point with two nos nuts , bolts including 32X6 mm flat iron clamp. nuts bolts and washers and also watering pipe 20mm bore GI pipe medium garde from earth p[it to top electrode including funnel, wire mesh,copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregateand 40 mm thick PCC 1:2:4 type B1 cover complete all asshown in electrical plate No 3 of SSR Part-Iincluding necessary excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50 mtr complete all as specified and as directed. Note :-PCC Chamber shall be constructedatleast 1.5 Mtr away from the earthing electrode and pipe for watering shall be provided in stanting manner. |
| 19 | Supply, Erecting & Testing Gl. Octagonal pole 7.0 mtr long top dia 70 mm & bottom dia 130 mm with base plate 220 x 220 x l2 mm, thickness 3.0 mm, including G.l. Foundation Nut & Bolt [420, 600 mm long (4 Nos) & GI. Single arm bracket 1.0 mtr long 40 mm dia. Including earth work complete all as specified and directed by Engineer -In -Charge |
| 20 | Supply and laying double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 90 mm, minimum inside dia 37 mm conforming to IS 16205 (Part 24) : 2017 complete all as specified and as directed. |
| 21 | Supply and installation of 11 KV Compact Sub Station with non extensible RMU consisting of 1 No manually operated 11 KV/630 Amp VCB in SF6 insulated stainless enclosure, HT cable /Bus bar, 1 Nos transformer 160 KVA ,11 KV/433 CRT dry type & associated LT devices complete as directed. |
| 22 | Supply, installation, commissioning and testing of Diesel Generating set out door type alongwith having prime mover rating of 160 KVA capacity 415 Volt, AC 3 Phase 04 wire 1500 RPM, 0.8 lagging power factor at 415 Volt suitable for 50 Hz 3 phase system with micro based control system including in built retrofitting emission control device as per latest IS specification and CPCB (Central Pollution Control Board) norms-IV and noise level shall not exceed 75 decibel at distance of 01 Mtr with all standard accessories i.e, tool box & tools including as required size of PCC foundation as per recommendation of manufacturer (OEM) and comprising the following :-(a) Diesel Driven Engine :- Diesel Engine 4 stroke water cooled electric start of suitable BHP at 1500 RPM suitable for output of alternator at 47 degree C, 50% RH and confirming to IS 10001 Engine capable for taking 10% overloading for 01 Hour after 06 Hours of continuous operation. The engine will be fitted complete with all the required accessories:-(b) Engine mounted instrument panel fitted with and having digital display for following:-(i) Start stop switch with key.(ii)Water temperature indication.(iii)Lubrication oil pressure indication.(iv)Battery charging indication.(v) RPM indication.(vi)Oil temperature indication.(vii)Low lubrication oil trip indication.(viii) Engine hour indication. |
| 23 | (c) Alternator :-Synchronous alternator rated at 160 KVA at 1500 RPM 415 Volt at NTP 0.8 power factor 3 Phase 50 Hz, AC supply confirming to IS 4722.The alternator shall be having SPDP enclosure, brush less, continuously self excitation and self regulated as confirming to latest IS suitable for tropical conditions with H Class insulations.(d) Base frame and foundation :- Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement foundation and vibration isolation arrangement as per recommendation of manufacturer. |
| 24 | (e) Fuel tank:- Fuel tank of suitable capacity fabricated out of 3mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves, level indication and accessories as required as per specifications.(f) Exhaust system:- Dry exhaust manfold with hospital exhaust silencer and catalytic converter.(g) Starting system:- 12 Voltstarting system comprising of starter motor, voltage regulator and arrangement for initial excitation with complete with suitable numbers of batteries (lead acid type) as required as per specifications.(h) Acoustic and weather proof enclosure with arrangement for fresh air inlet for cooling of the engine and alternator, excitation, discharging hot air into the atmosphere as per specifications.(j) Control Panel & AMF Panel :- Control panel and AMF panel of size 1.5m x 1.5m x 0.60m, fabricated out of 2mm thick CRCA sheet indoor pedestal type support on MS iron channel 75x40mm, totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary stickering of switcher gear about termination of switch gear and the nuts, bolts etc used are to be made of rust proof materials including as per IS 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hoz, 415 Volts, 400 Amp capacity with powder coated with incoming / outgoing terminals control wiring with copper cable of suitable size for 160 KVA DG Set, including all engine and alternator control switches and indicator as per manufacturer desgn and comprising of the following :-(i) MCCBs of 250 Amp capacity 415 volts 4 Pole, rupturing capacity 36 KA for incoming/ outgoing with over load and short circuit protections - 02 Nos |
| 25 | Note:- (i)Initial filling of lubricating oil/ coolant and fuel required for testingwill be provided by the contractor without any extra cost. (ii) All arrangement for testing of DG set shall be made by contractor with in overall cost quoted.(iii) Pre-commissioning test shall be carried out by rep of Accepting Officer. Test for DG set shall be carried out for duration of 12 Hours. |
| 26 | Supply & fix LT panel out door (Kiosk type) type, weather & vermin proof MS sheet housing 3.15mm thick, powder coated over a coat of primer, double door, front & rear openable type, mounted on 40x40x6 mm angle iron frame, floor mounted type with one MCCB, 4 pole, 250 Amp, 36 KA 415 volts as (incomer) and 200 Amp 4 pole (outgoing)-02 Nos, 40 Amp 4 pole MCCB -02 (Outgoing) Nos aluminium bus bar 200 Amp of length not less than 60 cm, 4 pole duly drilled with holes for cable connections, after due approval of panel drawing including PCC pedestals of suitable size, removal of old unsv panel, making good the area complete all as specified and directed by Engr-in-charge. |
| 27 | Supply, installation, commissioning and testing of factory made cubical LT feeder pillar box, out door type IP 65, powder coated suitable for floor mounting made out of 3.15 mm thick CRCA sheet with front hinged opening with rubber lining, having flush locking arrangement complete providing sufficient space for cable entry from sides suitable including copper strip 1x4 Nos , 160 amps rating mounted on bus bar insulators for connecting with MCCB at outgoing to connect mother accessoriesand consist of following |
| 28 | Incoming |
| 29 | (i)MCCB250 Amps, rating 415 Volts, 4 pole cap 50 KA with thermal magnetic setting type - 01 No. |
| 30 | (ii)Voltmeter with selector switch 0-500 V- 01 No. |
| 31 | (iii)Ampere meter0-50 Amps with CT and selector switch - 01 No. |
| 32 | (iv)LED indicating lamps RYB-01 Set (Set of three). |
| 33 | Outgoing |
| 34 | (i)Supply and fix 3 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 50 KA. 01 Nos |
| 35 | Supply and erecting factory made Octagonal Hot rolled steel pole conform to IS-2062/BSEN 10025 with hot dipped galvanised finishing of 7 mtr long with junction box, mild steel base plate grouted alongwith foundation by means of 4 Nos M20 x 600 LG foundation bolts including single swan neck bracket.Note- (i) Excavation,earth work shall be measured and paid seprately under appropriate sch. (ii) RCC M20 and steel for foundation shall be as per OEM recommendation and drawing which shall deemed to be included in quoted rates |
| 36 | Lump sum price worked out by the tenderer for“EXTERNAL WATERSUPPLY WORKS\" as listed in Schedule ‘A’ Section -II |
| 37 | Schedule ‘A’ Section -II(EXTERNAL WATER SUPPLY WORKS) |
| 38 | Supply and fixing Gun metal gate valve with locking device and open shut indicator for 25 mmbore iron pipe , with iron wheel head, screwed both ends conforming to IS 778 - 1984 complete all as specified and directed. |
| 39 | Supply and fixing Gun metal gate valve with locking device and open shut indicator for 20 mmbore iron pipe , with iron wheel head, screwed both ends conforming to IS 778 - 1984 complete all as specified and directed. |
| 40 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine or by using manual mechnical tools with manpower including passing suitable for GI pipe medium Grade. |
| 41 | Supply and lay Centrifugally cast (Spun) Ductile Iron pressure pipe with spigot & socket end, class K-7 conforming to IS:8329/2000 suitable for (push on) rubber gasket jointing with centrifugally applied inside cement mortar lining and external zinc coating with a finishing layer of black bitumen coating on external surfaces, size 100 mm (4”) dia including jointing material i.e. ethylene propylene diene monomer (EPDM) rubber gasket conforiming to IS: 5382 of bulb type complete as specified and directed by Engr-in-charge. |
| 42 | Cutting existing water pipe line bore 200 mm and inserting of flanged Tee 200x200x100 mm , flanged socket, rubber gasket, nut bolt etc. and making leak proof joint complete for new water pipe connectionsNote:- DI fittings special fittings shall be measured and paid seperately. |
| 43 | DI fittings, class K-12, confirming to IS-9523-2000 suitable for spigot & socketed pipes such as bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc), tee pieces, single branch, \"Y\" junction, double branch, cross collar, caps and plugsetc. suitable for spigot and socketed pipes upto 200 mm bore complete all as specified and directed by Engineer-in-charge. |
| 44 | Lump sum price worked out by the tenderer for“EARTH WORKS\" as listed in Schedule ‘A’Section IV |