| 1 | Supply, installation, testing and commissioning of advance maintenance free system based earthing comprising of following accessories complete all as specified and directed:- (a) Set of 01 Nos 3000 mm long, 17.2 mm dia earth electrode made of 99.99% copper circular rods with connect copperstrip and electrode with the help of copper brazzing ofincoming copper strips of size 25mm x 3mmof length as per site requirement upto copper Bus bar/Earth test point as decided by Engr-in-Charge and the distance between two copper earth electrode earthing should be minimum 3 Meter .(b) Copper bus bar of size (300 x 25 x 6)mm act as test point connect with copper nuts and bolts with post insulator.(Nuts/bolts as required is included in the cost).(c)Poly propylene earth pit cover of size 300 mm x 300 mm (with safe working load 5000 Kg)(d) Each pit filled with earth enhancement compound /chemical (Magnesium sulphate) only (min 50 Kgs/pit) all as specified.(e) Required result of earthing should be less than 01 Ohm . If desired Ohmic value is not achieved then additional set of 1 No of3000 mm long, 17.2 mm dia earth electrode made out of 99.9% copper rod with allied items, 01 x Pit cover, 01 x Sub bar as (d) above 50 Kg of chemical shall be provided by contractor without any extra cost to Govt. No price adjustment shall be made, if additional set is not required complete all as directed by Engr- in-charge(f)Necessary excavation work in any type of soil/strata, returning filling and removal of soil is included in the quoted rates.(g) Site inspection for complete Earthing work is mandotry for the Contractor before quoting the tender. No explanation/doubts will be entertained later.(h) Any damage done to govt property during the execution of work will be make good by the contractor at his own cost. (j) The Characteristics of this compound shall highly conductive, hygroscopic, non-magnetic, non-corrosive in nature, and have the best moisture-retaining qualities.Make:- U-Protect/ or as approved by GE. |
| 2 | Material & Labour for U protect R-60 Early Streamer emission Air terminal (ESEAT). Model:U protect R-60The ESEAT has corrosion resistant stainless chrome body capable of working in hazardous atmosphere. The Air terminal is non-radioactive and requires no special licensing. The unit is fully autonomous (no battery, no external power supply is required), collects energy from the ambient electric field. The ESEAT model has been tested in a high voltage laboratory in accordance with NFC 17 to 102 in order to measure the average gain in triggering. The average gain in triggering time (Δ Ts) obtained during the lab test for the offered model is 63 µs.The ESEAT works on negative as well as positively polarized discharges. ESEAT has been tested for such discharges in Central Power Research Institute (CPRI).A dedicated tester is available to test the healthiness of the ESEAT on request (Page No. 37, Point No. 3 of Clause 8.6 of the Revised NFC 17 to 102 version 2011 ).ESEAT Model : U protect R-60- Radius of protection =60 Mtrs @ L- IIILevel of protection considered for the project = Level III, complete all as specified and directed by Engr in Charge. Note :- The Rates are inclusive of following :-(i) Material & Labour for MOUNTING STRUCTURE (MAST), Supply of Standard Mounting Structure of height upto3 Mtrs, complete all as specified and directed by Engr in Charge.(ii)Supply & Fixing for TEST LINK, Each down-conductor should be provided with a test link box in order to disconnect the earth termination system for enabling measurements, complete all as specified and directed by Engr in Charge.(iii) Supply & Fixing of Guy Rope, Insulator, fastener, D-Clamp, Foundation Bolt & other accessories,complete all as specified and directed by Engr in Charge.Make:- U-Protect/ or as approved by GE. |
| 3 | Material & Labour for DISCHARGE EVENT COUNTER, Supply of 6 digit Digital Lightning Event Counter in WEATHER PROOF ENCLOSURE. The counter should give the number of strikes intercepted by the lightning arrester, complete all as specified and directed by Engr in Charge.Make:- U-Protect/ or as approved by GE. |
| 4 | Material & Labour for Down Conductor Supply of 70 sqmm copper Flexible cable, complete all as specified and directed by Engr in Charge. Make:- U-Protect/ or as approved by GE. |
| 5 | Note for item No. 2 to 4 : ESE Air Terminals shall tested in a high voltage laboratory in accordance with NFC 17 102 in order to measure the average gain in triggering. The average gain in triggering time (Δ Ts) obtained during the lab test for the offered models are mentioned with individual models. All ESE Air Terminals shall corrosion resistant stainless chrome body capable of working in hazardous atmosphere. The Air terminal shall non-radioactive and requires no special licensing. The unit is fully autonomous (no battery, no external power supply is required), collects energy from the ambient electric field. The ESEAT works on negative as well as positively polarized discharges. ESEAT has been tested for such discharges in Central Power Research Institute (CPRI). It is specifically clarify that THE ESE LIGHTNING ROD quoted herein is only meant to protect the structure and people against the direct impact of a lightning strike. |
| 6 | Material & Labour for Anti static flooring suitable for ESD station for discharging static electricity completely with copper wire mesh byusing copper tape of size 0.5 mm thick & 0.5 inch width and venyl matting of thickness not less than 3 mm containing conductive Carbon /Graphite particles for static charge dissipation which is to be laid using conductive adhesive suitable for any floor ( concrete/ tiles/ stones surface) & connecting with suitable length of copper strip of size recommended by the OEM with proper connection to nearest copper earthing complete all as specified & as directed.Note :- (i) The rate of Copper earthing is to be paid as per the relevent item of the schedule.(ii)The colour of the flooring is to be decided by the Engr-in-charge/GE.(iii) The make of the Static flooring is to be finilaized by the Garrision Engineer. |
| 7 | Material & Labour for earthing complete with galvanized copper earth plate electrodesize 600 mmx 600 mm x 3 mm thick buried directly in groundvertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized copper strip 25 mm x 3 mm earth lead by means of bolts, nuts, check nuts and washers of galvanized copper includingGI pipe light grade of size of 40 mm dia for protection and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 using 40 mm grade stone aggregate excavation and earth work in any type of soil all as shown in electrical plate No 5 connected to earthing test point complete all as specified and directed or indicated including testing on completion. |
| 8 | Material & Labour for point wiring complete with 4 Sqmm single core FRLS PVC insulated unsheathed cable 1100 V grade multi stranded copper conductor drawn through and including non metallic rigid PVC conduit and accessories concealed in walls/ceilings including 4 Sqmm dia multistranded copper cable as earth continuity conductor connected to common earth dolly, including 1.22 mm thick pressed steel terminal boxes for provision of Modular switches to house switch/regulators etc including Modular Plate and Covers forPower Socket/AC/Geyser on independent board controlled by one switch complete all as specified & directed. |
| 9 | Supply and fixmodular switch 1 way 16A 1 module complete all as specified and directed. |
| 10 | Supply, fixing, commissioning of wall mounting split type Air conditionerelectric driven single phase indoor unit and outdoor unit with cordless remote control unit and with inbuiltair ioniser and plasama filter for indoor air quality, cutting, brazing and connecting the copper pipe of size 1/2 inch and 1/4 inch size of pipe and making holesfor passing of copper pipes and electric cables and pressure testing with nitrogen and feron gas vacumising the system and charging the Non CFC refrigrent and testing the complete system for smooth functioning of split AC upto satisfaction and having 3 star rating conforming to IS-1391 para II 1992 having herimatically sealed air compressor working with non cfc refrigrent suitable for wall mounting 4500 K cal/hrs 1.5 ton complete as per OEM recommendations including fixing on suitable mounting brackets etc. complete all as specified and directed. Note :- The cost is inclusive of mounting brackets of suitable size.Make:- VOLTAS/ L.G./ DAIKIN. |
| 11 | Supply and fixindustrial wall mounted plug socket suitable for IP 44 degree of protection of 20Amps rating 1P+N +E complete all as specified and directed. Make: L&T/C&S/Legrand/Indoasian |
| 12 | Supply & Fixing in repairs Powder coated Alu grill of approved pattern using channel of required size, screwed to windows & ventilators with self tapping screws complete all as specified and directed. |
| 13 | Supply & Fixing in repair aluminium powder coated window sliding type (3 track) with frame size 100 mm x 35 mm x 1.20 mm and shutter 39.40mm x 17.70 mm xm1.20 mm with two glass shutter and one stainless steel wire mesh shutter including necessary jointing cleats, glazing clips, rubber packing powder coated aluminium snap beading screws with 4mm plain float glass and 0.36 mm dia SS wire mesh, 1.4 mm average width of aparture fittings etc, and necessary locking arrangements and including making good the jambs and painting with matching type and shade complete all as specified and directed. |
| 14 | Supply & Fixing in repairs aluminium anodised door with frame and shutter and including glazing with 5 mm thick tinted glass or 12 mm thick prelaminated particle board exterior grade in panels, rubber gasket, aluminium glazing clips, mortice lock, Aluminium stopper cleat, hydraulic door closer, floor spring, iron mongary etc. section of aluminium door including powder coating of any colour (min thickness of powder coating 50 micron)shall be of following sizes:-Frame : 100 mm x 44 mm x 1.80 mm thick with rawal plugMiddle lock rail: 100 mm x 44 mm x 1.80 mm thickBottom rail : 100 mm x 44 mm x 1.80 mm thickTop rail / Style: 46 mm x 44 mm x 1.80 mm thickGlazing beading: 0.70 mm thickAluminium handle \"D\" type: 150 mm longAluminium tower bolt 9.9 mm dia shoot 200 mm long Mortice lock – 100 mm 4 lever, Aluminium stopper cleat Note :- (i) Making good of wall surface withmatching to existing surface is included in quoted rate complete all as specified and directed. |
| 15 | Supply & Fixing in repairs aluminium anodised door with frame and SS wire mesh shutter including necessary jointing cleats,rubber packing powder coated aluminium snap beading screws with 0.36 mm dia SS wire mesh and average width of aparture 1.4 mm fittings etc, and necessary locking arrangements, mortice lock, Aluminium stopper cleat, hydraulic door closer, floor spring, iron mongary etc. Section of aluminium door including powder coating of any colour (min thickness of powder coating 50 micron) shall be of fwg sizes:-Frame : 100 mm x 44 mm x 1.80 mm thick with rawal plugMiddle lock rail: 100 mm x 44 mm x 1.80 mm thickBottom rail : 100 mm x 44 mm x 1.80 mm thickTop rail / Style: 46 mm x 44 mm x 1.80 mm thickAluminium handle \"D\" type: 150 mm longAluminium tower bolt 9.9 mm dia shoot 200 mm long Mortice lock – 100 mm 4 lever, Aluminium stopper cleat Note :- (i) Making good of wall surface withmatching to existing surface is included in quoted rate complete all as specified and directed. |
| 16 | Material & Labour for 20mm thick Granite work (table rubbed and polished) in steps, jambs, cills, cooking platforms,counter tops and like in cement mortar (1:4) including pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite, over and including 20mm thick Screed bed in CM 1:4, complete all as specified and directed.Note : The rate quoted is deemed to be included for full moulding of edges and making, opening for kitchen sink all as directed by Engr-in-Charge. |