| 1 | Civil Works |
| 2 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge. |
| 3 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. |
| 4 | For thickness of tiles 10 mm to 25 mm |
| 5 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 6 | All kinds of soil. |
| 7 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 8 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. |
| 9 | Granite stone slab of colour black, Cherry/Ruby red |
| 10 | Area of slab over 0.50 sqm |
| 11 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 12 | 25 mm thick |
| 13 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 14 | Fixing of existing aluminium partition frame of size 12 sqm |
| 15 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. |
| 16 | 32 mm nominal dia Pipes |
| 17 | Providing and fixing Glass mossaic tiles on finished plain wall surface of size 20 mm x 20 mm x 4 mm in all colour, design , fixing in customize design as per direction of Engineer-in- Charge. The glass mosaic tiles to be fixed on the wall surface with the help of approved adhesive applied at the rate of 2.5 kg per sqm and grouting of the same. The rate is inclusive of all operation, material and required pattern approved by Engineer-in-Charge |
| 18 | Providing and fixing Floating Fountain with Lights having IP 68 protection, 1/2 hp, 5000 GPH pump and with 3 Spray Modes, 50 ft power cord. |
| 19 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. |
| 20 | 20 mm nominal dia Pipes |
| 21 | Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete. |
| 22 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 23 | Electrical Works |
| 24 | Wiring for light/ power plug with 2X4 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 25 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. |
| 26 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 27 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 28 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 29 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cuttingthe wall and making good the same in case of recessed conduit as required. |
| 30 | 25 mm |
| 31 | 50 mm |
| 32 | Supplying and laying DWC HDPEpipeISImarkedalongwithall accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required |
| 33 | 63 mm dia |
| 34 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 35 | 15/16 A switch |
| 36 | 6 pin 15/16 A socket outlet |
| 37 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 38 | 3 Module (100mmX75mm) |
| 39 | 6 Module (200mmX75mm) |
| 40 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required |
| 41 | 3 Module. |
| 42 | 6 Module |
| 43 | Supplyingandfixing5Ato32Arating,240/415V,10kA,\"C\" curve,miniaturecircuitbreakersuitableforinductiveloadof singlepolesintheexistingMCBDBcompletewithconnections, testing and commissioning etc. as required |
| 44 | Triple pole and neutral |
| 45 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 46 | 12 way (4 + 36), Double door |
| 47 | Supplying and fixing 30 A, 415 V, TPN Industrial typesocket outlet, with 4 pole and earth, metal enclosedplug top along with 30 A \"C\" curve, TPMCB, in sheetsteel enclosure, on surface or in recess, with chainedmetal cover for the socket out let and complete withconnections, testing and commissioning etc. asrequired. |