| 1 | Supplying, Fabrication and Installation of 4 mtr. high Pole made out of 65 mm dia. NB, B-class GI Pipe ISI marked duly welded with MS Base Plate of size 300 mm x 300 mm x 12 mm thick with Stiffener of size 130 mm x 60 mm x 5 mm thick; top edge to be blunted with a horizontal flat>5 mm (No sharp edge), suitable Earth Stud on Base Plate, making suitable size hole in pole at a height of 2.5 meter from base plate for cable entry/exit, painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the existing foundation with the existing nuts-bolts, washers etc. complete as required. |
| 2 | Supplying and Fixing of Single Over Hang (SOH) Bracket- for 50-80 dia. MS/GI Pole made of MS Pipe with 300 mm long top galvanized MS Tube of suitable diameter for Light Fitting accommodation, connection etc. complete as required. |
| 3 | Supplying and Fixing of Double Over Hang (DOH) Bracket- for 50-80 dia. MS/GI Pole made of MS Pipe with 300 mm long top galvanized MS Tube of suitable diameter for Light Fitting accommodation (Angle as per EIC/AE direction). |
| 4 | Providing and Laying in Position, 1:2:4 (1 Cement : 2 Coarse sand : 4 Graded Stone Aggregate) Reinforced Cement Concrete Foundation of size450 mm x 450 mm x 1200 mm deep (900 mm below Ground Level and 300 mm above Ground Level) including excavation of earth, refilling, providing, cutting, bending and placing in position, Reinforcement of Cold Twisted Bars of 12 mm dia.- 1200 mm long (approx.)- 8 Nos. and Reinforcement Ring of Cold Twisted Bar of 8 mm dia.- 1400 mm long (approx.)- 6 Nos. (with suitable spacing) including centering & shuttering as required with Providing, Fixing and Positioning of One Set of Foundation Bolts comprising of 4 Nos., 16 mm dia. 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 Nos. GI nuts and 2 Nos. GI washers etc. per bolt and 1 No. anchor plate (3 mm thick) of suitable size and providing 63 mm (OD) DWC pipe ISI marked for cable entry & exit etc. complete as required. |
| 5 | Supplying, Installation, Testing & Commissioning of Street Light LED Fixture Powder Coated Pressure Die Cast Aluminum body with driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP- 66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR 15, Lenses for Beam Angle as per IESNA type I/II/III as per the width of the road and the project requirement, suitable to fit in up to 65 mm dia. pipe, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C).45 Watt |
| 6 | Supplying of Flood Light, Powder Coated Pressure Die Cast Aluminum body with built in or separate driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP-66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR-15, Lenses for Beam Angle 30°-120° as per the application and the project requirement, suitable tilt able Fitting, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS/HFFR, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C).100 Watt |
| 7 | Supplying and Replacement of Flood Light, Powder Coated Pressure Die Cast Aluminum body with built in or separate driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP-66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR-15, Lenses for Beam Angle 30°-120° as per the application and the project requirement, suitable tilt able Fitting, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS/HFFR, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C) including rebate for dismantle Fixture.200 Watt |
| 8 | Supply and Installation of Pole Connector Box made out of Glass Reinforced Polyester Sheet Moulding Compound Conforming to IS:13410-1992 Grade-S1 of Outside Dimensions 280 mm (H) x 170 mm (W) x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65/80 mm dia. GI Pole with the following Provisions/Accessories Mounting in Box etc. complete as required.a) 2 Nos. Clamps made out of 19 mm x 3 mm MS Strip of suitable Length for Mounting Box on the Pole.b) Water Tight Front Cover with 2 Nos. Stainless Steel Hinges & 1 No. Screw for Tightening.c) 4-Way, 220 V, 30 A, Dough Moulded Connector with SMC with Stainless Steel Inserts- 1 No.d) 16 A, Moulded SMC Rewireable Kit-Kat- 1 No.e) Suitable size Hole at suitable Location on Rear Wall for Cable & Wire Entry in the Connector Box.f) Earthing Bolt M6 x 20 mm.g) Neutral Link- 1 No. |
| 9 | Supplying of following sizes of XLPE (Cross Linked Poly Ethylene) Insulated PVC Sheathed Alumimium Conductor Armoured Power Cable of 1.1 KV grade including connection, testing etc. as required.2C x 16 sq. mm |
| 10 | 4C x 25 sq. mm |
| 11 | Providing and Fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub-main wiring/cable as required. |
| 12 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size Direct-In-Ground including Excavation and Refilling the Trench etc. as required, but Excluding Sand Cushioning and Protective Covering.Up to 35 sq. mm |
| 13 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.Up to 35 sq. mm |
| 14 | Supplying and drawing of following sizes FRLS PVC Insulated Copper Conductor, Single Core Cable in the existing surface/recess steel/PVC conduit as required.3C x 1.5 sq.mm |
| 15 | Supplying and Laying of following size DWC HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS: 14930, Part-II complete with fitting and cutting, jointing etc. direct-in-ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia. (OD-63 mm & ID-51 mm nominal) |
| 16 | Supplying and Replacement of floor mounted LT Feeder Pillar cubical type double door of size 1000 (H) mm x 900 mm (W) x 300 mm (D) with general arrangement made out of 2 mm thick MS CRCA Sheet having hinged gasket covers and screwed knobs with double locking arrangement & Locking Hooks and separate Rain Protection Cover with extension of 100 mm in Width & Depth, supported with MS Angle Iron legs and bottom frame of size 40 mm x 40 mm x 6 mm x 1 mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs (around 25% of length) should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, Painting with Primer, Numbering, Identification Plate of Component embossed and/or printed in Metalincluding Supply & Fixing of following accessories etc. complete as required (as per drawing approved by Engineer-in-Charge).a) 125 A, 36 kA Ics=100% Icu and Operational Voltage 690 V, 4 Pole MCCB- 1 No. (Incomer).b) 3-Phase Submersible Pump Controller (MU-G10) with Single Phase Preventer up to 10 Hp Pump Set, Relay Range 13 to 21 Amp- 1 Set.c) Electronic/Analogue Timer of model FM1/Quartz Daily 110 VAC-240 VAC Base/DIN Mounting in the existing Panel.d) 3-Pole Power Contactor of AC3 Rating 32 Amp, MNX 32 type.e) Ammeter (0-100 A) 96 sq. mm in size and 100/5 CT’s Ratio- 1 Set.f) Voltmeter (0-500 V) 96 sq. mm in size with Selector Switch- 1 Set.g) Indication Lamp (RYB) with Control HRC Fuse with Fuse Fitting- 1 Set.h) 6 A to 32 A ratings, DP MCB, “C” curve, 10 KA breaking capacity- 3 No.i) 6 A to 32 A ratings, TPN MCB, “C” curve, 10 KA breaking capacity- 2 Nos.j) 150 A, 4-Strip Al. Bus-Bar of minimum 400 mm long and of size 30 mm x 5 mm with sleeve and nut-bolts- 1 Set.k) 200 mm x 150 mm MV Danger Notice Plate of 2 mm thickness- 1 No.l) Earthing Stud- 2 Nos.m) Lifting hook on the top of feeder pillar- 1 Set. n) Lamp Holder inside Feeder Pillar- 1 No.o) 4 Way Neutral Link- 2 Nos. |
| 17 | Supplying, Fabrication and Installation of Wire Mesh Protection Frame for Existing Feeder Pillar, constructed from 10 SWG MS wire mesh with a Nominal size of 75 mm x 25 mm Rectangle. The Frame dimensions are 1.5 mtr. (Width) x 1.00 mtr. (Depth) x 2.00 mtr. (Height). It includes a Base Frame made of 40 mm x 40 mm x 6 mm MS Angle Iron, MS Strip Supports of 40 mm x 6 mm, and 0.5-meter-long leg supports of the same Angle Iron, all as per the approved drawing. Additionally, provide a suitably sized door, Supply and Fix a godown lock with locking arrangement, painting, and grouting with 1:2:4 Cement Concrete Foundation, as approved by the Engineer-in-Charge, complete as required. |
| 18 | Supplying of PVC Sheathed, PVC Insulated Copper Conductor Flat Submersible Cable of following size including connection, testing etc. complete as required.3C x 2.5 sq. mm |
| 19 | Supplying of following size ISI marked, FRLS PVC Insulated, Single Core Copper Conductor Cable.1.5 sq. mm |
| 20 | 4 sq. mm |
| 21 | Earthing with GI Earth Pipe 4.5 meter long, 40 mm dia. including accessories, and Providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 22 | Providing and Fixing 25 mm x 5 mm GI Strip on surface or in recess for connection etc. as required. |
| 23 | Painting of Existing GI Poles up to 4 to 6 meters in Height, applying Two Coats of Luxol Hi-Gloss Enamel-Colours including Red Oxide Primer, with Numbering of the Poles. This includes Painting the Base Plate and Mounting arrangements etc. complete as required. |
| 24 | Provision of Qualified Technical Staff for the arrangement, Maintenance, and Operation of Path/Park Lighting Systems to support the entire duration of \"Flower Show/Palash-2026\" event as per attached Terms and Conditions. |
| 25 | Supplying and Temporary Erection of wrapped timber/balli/bamboo support of suitable size and strength, up to 15 ft overall height, embedded 3 ft into the ground, including vertical alignment and bracing as required; temporary mounting of existing 100 W Flood Light on the erected support with Supply and Fixing of all necessary accessories such as clamps, nuts-bolts, and rassi (binding rope) to ensure safe and secure fixation; complete in all respects for temporary use as directed by the Engineer-in-Charge and/or AE(E)-in-Charge. |
| 26 | Supplying, Installation, Testing and Commissioning of 45-Watt Circular LED/Rink LED Post Top with Die Cast Aluminium housing for Gate Light mounted along with CCT-5700 K having Potted Driver, Symmetric Beam, Top Opening (TO) Driver Compartment, Polycarbonate Diffuser, CRI>70, IP-66 complete in all respect including connections with 1.5 sq. mm FRLS, PVC Insulated Copper conductor single core cable and earthing, suitable accessories (like Bracket, nut, bolt) etc. as required. |
| 27 | Supplying, Installation, Testing and Commissioning of Lycus 15-Watt LED Spike Light with Die Cast Aluminium housing for rugged outdoor usage Pendant or Surface mounting mounted with CCT-3000 K having Potted Driver, Symmetric Beam, Top Opening (TO) Driver Compartment, Toughened Glass with Environment friendly, decorative IP-66 LED Spike Light using COB LED as Light Source, IK>07 complete in all respect including connections with 1.5 sq. mm FRLS, PVC Insulated Copper conductor single core cable and earthing etc. as required. |
| 28 | Wiring for Circuit/Sub-main wiring along with Earth wire with the following sizes of FRLS/HFFR PVC insulated Copper conductor, single core cable in Surface/Recessed Medium Class PVC Conduit as required.2 x 1.5 sq. mm + 1 x 1.5 sq. mm Earth Wire |