Tender For Supply, Installation, Testing And Commissioning Of Radiation Shielding In Existing 2 Nos Modular Operation Theatres, Bilaspur-Himachal Pradesh
TDR : 52782677
Tender Notice
BOQ
Expired
Bilaspur
Himachal Pradesh
Tender For Supply, Installation, Testing And Commissioning Of Radiation Shielding In Existing 2 Nos Modular Operation Theatres
Frame made of Imported pine wood size 1.75” x 1.75” of soft texture, high moisture content (around 12-15% when finished), moderate density (roughly 34-44 lbs./ft³ or 505 kg/m³), and good workability.
3
Lead Sheet 1.5mm Thickness with 99.9 % purity Certificate from Government approved laboratory (as per AERB requirement) Per Sq. Mtr. of lead sheet should not be less than 19.33 KT
4
Automatically Hermetically Sealed Sliding Door with Lead Lining upto 1mm Thickin compliance to 12207 EN StandardsDoor Leaf:The door leaf has thickness of 60mm with PIR core (CFC free) with high-pressure laminate (HPL) on both sides conforming to EN 438- 3:2005. The door profile are flushed with door leaf in Aluminium Alloy, Grade 6063, Temper T6 natural anodized finish.Sealing:The door leaf has thickness of 60mm with PIR core (CFC free) with high-pressure laminate (HPL) on both sides conforming to EN 438- 3:2005. The door profile are flushed with door leaf in Aluminium Alloy, Grade 6063, Temper T6 natural anodized finish.Wall Frame: Aluminium Alloy, Grade 6063, Temper T6 in natural Anodized 20 MicronVision Panel:Double Glazed IG unit with 5mm tempered glass on both sidesLever Handle:Solid AISI 304 Grade Stainless Steel with rubber spring systemRail:Aluminium Alloy, Grade 6063, Temper T6Natural Anodized. single length upto 1800mm wide doors45° indentations with simultaneous “down and in” movementRollers: Special Grade Self-lubricating PAAir Permeability:Air tightness to an overpressure of upto 100 PaDimensions:CH: 1800 to 2100mmAccessories:View panel, Touchless switch, Foot switchFinishes:High Pressure Laminate (HPL)Approved Makes: Metaflex, Ribbon, Kone, Becon, Hermed
5
Reinstallation of Existing Wall Panels:- Wall Panelswith Substructure of Vertical Structures, Lower & Upper Aluminum Profiles
6
Easily replaceable all around EPDM gasket. When closed, the EPDM gasket is pressed against the frame to make sure perfect sealing.