| 1 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil) for laying of cables or GI pipe and getting out including levelling of bottom suface to required level complete all as specified and directed by Engr-in-Charge. |
| 2 | Description all as per Serial item No 1.00 above but depth exceeding 1.5 mtr and not exceeding 3.00 mtr complete all as specified and directed by Engr-in-Charge. |
| 3 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables and in substation ducts for cushioning of cables etc, complete all as specified and directed by Engr-in-Charge.(Measurement should be after punning down) |
| 4 | Supply and Fixing sub class B bricks having minimum compressive strength 75 Kg/ Sq cm laid in trenches for cable protection etc complete all as specified and directed by Engr-in-Charge. |
| 5 | Laying only old bricks retrived from Item No 1.00 complete all as specified and directed by Engr-in-Charge. |
| 6 | Returning filling in,. including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 7 | Removing excavated material (ie soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed by Engr-in-Charge. |
| 8 | Material & labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate . in mass concrete and filling completefor foundation ofpadof polecomplete all as specified and directed by Engr-in-Charge. |
| 9 | Material & labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate . in mass concrete and filling completefor foundation of Panel & Transformer yeard, pole/stay/ of polecomplete all as specified and directed by Engr-in-Charge. |
| 10 | Material & labour for PCC 1:2:4 type B-1 using 20 mm gradedstone aggregate incoping for replacement of new pole and breaking old existing copingand like includingweather slightly rounded or chamfered angles and throatyand necessary formwork completefor pole ,all as specified and directed by Engr-in-charge. |
| 11 | Material and labour for Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and directed by Engr-in-Charge. |
| 12 | Material and labour for Cement Concrete type B-2 mix, 1:2:4 (40mm graded aggregate) 150mm thick, finishing the top surfaces fair and even complete all as specified and directed by Engr-in-Charge. |
| 13 | Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 40 to 100 mm bore and making good both ends complete all as specified and directed by Engr-in-Charge. |
| 14 | Supply and lay GI pipe light grade in replacement as cable protection laid on trench/floor, fixed on pole/wall etc of following sizes all as specified of size 100 mm dia. complete all as specified and directed by Engr-in-Charge. |
| 15 | All as per item No 14.0 above but of size 80 mm dia complete all as specified and directed by Engr-in-Charge. |
| 16 | All as per item No 14.0 above but of size 50 mm dia complete all as specified and directed by Engr-in-Charge. |
| 17 | All as per item No 14.0 above but of size 40 mm dia complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply, laying, jointing, testing and commissioning in replacementof LT underground cables of size 25 Sqmm 4 core, 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavyduty armoured, with multistranded aluminium conductors, IS-7098, Part-II marked, laid in trenches/ duct/ under road/ footpath/ etc or against re-routing / diversion from residential buildings/ road/ footpath etc complete all as specified and directed by Engr In Charge. |
| 19 | All as per srl item No 18.0 here-in-before but of size 35 Sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
| 20 | All as per srl item No 18.0 here-in-before but of size 50 Sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 21 | All as per srl item No 18.0 here-in-before but of size 70 Sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 22 | All as per srl item No 18.0 here-in-before but of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 23 | All as per srl item No 18.0 here-in-before but of size 120 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 24 | All as per srl item No 18.0 here-in-before but of size 150 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 25 | All as per srl item No 18.0 here-in-before but of size 185 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 26 | All as per srl item No 18.0 here-in-before but of size 240 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 27 | All as per srl item No 18.0 here-in-before but of size 300 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 28 | All as per srl item No 18.0 here-in-before but of size 400 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 29 | Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade complete all as directed for the size 25 to 50 Sqmm x 3.5 core/ 4 core complete all as specified and directed by Engr-in-Charge. |
| 30 | All as per item No 29.0 but size 70 to 95 Sqmm x 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 31 | All as per item No 29.0 but size 185 to 240 Sqmm x 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 32 | Supply and Installation ofLT CT operated Trivector Meter in replacement with the following specifications: Meter Type:LT 3 Phase 4 Wire Electronic Tri vector Meter, Standard: IS 13779:1999 / CBIP 88, Accuracy: Class 1.0, Voltage and Current rating: (i) Reference Voltage- 415V for LT Meter, (ii) Basic Current (Ib)- 5 A, Maximum continuous current (Imax) - 10 A, Rated Frequency (variation) - 50Hz (±5%), Power consumption: (i) Voltage circuit: Less than 1.5 W and 10 VA per Phase at reference voltage, reference temperature and reference frequency,(ii) Current circuit: Less than 1 VA per phase at basic current, reference frequency and reference temperature, Display type: 8 digit 7 segment backlit LCD display, not less than10 mm character height Display in the event of Power Failure: Internal battery back-up for LCD display, Communication port: (i) Galvanically isolated Optical Communication port for data transfer through either CMRI or remote device or both is provided (ii) RS 485 for DLMS protocol, Energy recording - Unidirectional, Instantaneous parameters (30 Min) - Each Phase Current, Each Phase Voltage, Each Phase Power, Each Phase Power Factor, Each Phase Reactive Power, Power, Power Factor, Apparent Power, Reactive Power, Frequency, Load survey (30 Min) parameters - Energy, Apparent Energy, Daily Survey: Cumulative Energy, Cumulative Apparent Energycomplete all as specified and directed by Engr-in-Charge. |
| 33 | Taking outfaulty underground1100 Volt LT cable of differentsizes by excavation and removingbricksof any size and relaying in the same trenches after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using newbricks as required complete all as specified and directed by Engr-in-Charge.Note: (a) 1100Volt LTcable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable brickswill be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for seperately under respective items of schedule. |
| 34 | Material and Labour for disconnecting burnt end or burntportion of cable, removing the cable from loop with and including necessary excavation & earth work, relaying and re-connecting the cable by removing burnt portion of cable and preparing fresh terminals including fixing of new lugs for 50 Sqmm 3½ / 4 to 400 Sqmm of LT cable at Poles/Main switch etc complete all as specified and directed by Engr-in-Charge. |
| 35 | Dismantling the existing unserviceable (damaged/broken) PCC electric pole of any type and size, from ground after necessary excavation & breaking of concrete foundation & encasing the pole including making good the disturbed surfaces complete all as specified and directed by Engr-in-Charge. |
| 36 | Supplying & Erecting Steel Tubular Pole 410 SP-31 (9 metres long) in replacement complete with cast iron base plate all as specified in IS 2713 of 1980 (Part I & II) including painting of Poles with one coat of red oxide primer and one coat of aluminum paint before fixing and one coat of aluminum paint after fixing. The complete embedded portion shall be painted with two coats of black bituminus paint complete all as specified and directed by Engr-in-Charge. (Note:- The necessary earth work and PCC work will be measured and paid separately under respective items.) |
| 37 | Preparation ofold painted surfaces of LT PCC poles for cross arms, MS strap, nuts, bolts, washers, cable protection pipe wherever provided etc and painting with one coat of aluminium paint and painting of bottom area of pole upto 2.1 m from ground level with synthetic enamel paint in alternate layer (30 cm wide) with black and yellow paint including writing pole numbersin white letter of approved size on black groundcomplete all as specified and directed by Engr-in-Charge. |
| 38 | Supply & fixing in replacement KIOSK Box weather proof made up ofone piece mounted on SMC base and door pole mounted hinged door of size 333 x233x 120 mm outside and 300 x 200 x105 mm inside dimension comprising of aluminum bus bar 4 strips for 3 phase and neutral 63 Amp and 6 Amp fuse grip with base for controlling the steet light fitting and FL clamps 30x4mm with necessary MS nuts bolts and washers and including applying two coasts of synthetic enamel paint over a coat of red oxide zinc chrome primer on new steel surface and including embassing/painting of Danger notice of size not less than 10 cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and directed by Engr-in-Charge. |
| 39 | Earthing complete in replacement with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (Earth pit not less than 3.5 meter deep below ground level) with top edge of plate not less than 2.5 meter below normal ground level, connected with and including galvanised iron earth strip 32 X 6mm by means ofnuts, bolts, check nuts and washers of galvanised iron or steel and provisions of charcoal dust and common salt packed all around the earth plate and testing on completion complete all as specified and directed by Engr-in-Charge. and shown in Electrical Plate number 3 of MES SSR Part-INOTE : The quoted rates shall be deemed to include the cost of(a) Excavation and earth work in any type of Soil. (b) PCC pit in cement concrete 1:3:6 mix, type B-1, Pre cast RCC cover with suitable handle, 40 mm thick in RCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/Sq metre. (c)Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc (d) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection ofearthing lead(e)Requisite quantity of common salt and charcoal in alternate layers completely packed as directed. (f)Testing of earthing on completion. |
| 40 | Supplying and fixing in replacementof old street light fitting any type, LED street light fittings, 60 Watt, IP-65 complete all as specified and directed by Engr-in-Charge. |
| 41 | Supply & fixing Street light bracket suitable for PCC/ Steel Pole made to shape out of GI pipe 40 mm bore light grade, 1.5 mtr length and fixed in replacementwith MS Calmps of size flat MS iron 50 mm x 6 mm ,nuts, bolts and washers on pole complete all as specified and directed by Engr-in-Charge. |
| 42 | Taking down of unsv street light from street light pole and material and labour for fixing in replacement of Driver suitable for LED Street light 45-60 watt, any make complete all as specified and directed by Engr In charge. |
| 43 | All as per item No-43.0 but of cap 60-120 watt LED Flood Light complete all as specified and directed by Engr-in-Charge. |
| 44 | Supply and fixing in renewal of 3 pole power contactor ML-6 mounted on any type/description LT panel/feeder pillar/wallafter taking down old existing un serviceable contactor complete all as specified and directed by Engr-in-Charge. |
| 45 | Supply and fixing in renewal of 3 pole power contactor MNX-110 mounted on any type/description LT panel/feeder pillar/wallafter taking down old existing un serviceable contactor complete all as specified and directed by Engr-in-Charge. |
| 46 | Supply and fixing in renewal ofAnalog Time switch , 240 Volt AC , 50 Hz , mounted on any type/description LT panel/feeder pillar/wallafter taking down old existing un serviceable time switchcomplete all as specified and directed by Engr-in-Charge. |
| 47 | Supply drawing, connecting and testing in replacement3 core, 1.5 Sqmm PVC insulated and PVC round sheathed copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from KIOSK box to street light fitting including providing suitable copper lugs complete all as specified and directed by Engr-in-Charge. |
| 48 | Supplying and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable of size 16 Sqmm flat complete all as specified and directed by Engr-in-Charge. |
| 49 | All as per Sritem No 48.0 above but of size 10 Sqmm. complete all as specified and directed by Engr-in-Charge. |
| 50 | All as per Sritem No 48.0 above but of size 6 Sqmm. complete all as specified and directed by Engr-in-Charge. |
| 51 | Preparation ofold painted surfaces of Steel tubular LT poles, any height including cross arms, MS strap, nuts, bolts, washers, cable protection pipe wherever provided etc and painting of complete poles with one coat of aluminium paint from 2.1 m above ground level to top of pole including cross arms and protection pipe and painting of bottom area of pole upto 2.1 m from ground level with synthetic enamel paint in alternate layer (30 cm wide) with black and yellow paint including writing pole numbersin white letter of approved size on black ground complete all as specified and directed by Engr-in-Charge. |
| 52 | Disconnecting LT connection, junction box ,taking down steel tubular Pole ,9 metres long carefully by excavation, after demolition of PCC and Material & labour for shifting of to another place as directed complete with cast iron base plate complete all as specified and directed by Engr-in-Charge.(Note :- The above quoted rate is included for T & P , man power etc. The necessary earth work and PCC work will be measured and paid separately under respective items.) |
| 53 | Prunning/trimming the branches of trees if any along LT overhead line/ street light pole, 3 mtr on all side below/above/sides of LT overhead line and removing the same upto 150 mtr away each span not exceeding 50 mtr complete all as specified and directed by Engineer-in-Charge (The above is to be ensured for the entire contract period by cutting/trimming of trees any number of times as required). |
| 54 | Stringing/stretchingincl jointing in situ of different sizes of ACSR or GI earth continuity conductors with/ withoutguarding wires on LT electric poles at different locations all as ordered manually or by mechanical means to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium tapes after stringing complete all as specified and directed by Engr-in-Charge as ordered :- |
| 55 | ACSRof different size e.g Squirrel, weasel, ferret, etc. complete all as specified and directed by Engr-in-Charge. |
| 56 | GI Earth continuity/Guarding wire 4 mm /3.15 mm dia.complete all as specified and directed by Engr-in-Charge. |
| 57 | Material & labourproviding shackle type insulator LT 1100 volt grade porcelain vitreous white or brown including insulator bolts, nuts 12 mm dia, 75 mm height and 90 mm dia of insulator complete all as specified and directed by Engineer-in-Charge. |
| 58 | Disconnecting LT cablesand Material and labour for shifting of LT Panel of any size/capacity and reinstall with all connections, necessary foundation to another site all as specified and directedby Engr In charge. |
| 59 | Supply, install, testing and commissioning in replacement offactory made tested LT panel board cubical double door compartment outdoor type leg mounted suitable for , 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with aluminiumbus bar of rating not less than 1.5 times of Incomer/ Outgoings MCCBs, installed on proceline/ SMC insulator. The panel shall be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and innercompartment 2.0 mm, 40X40X6 mm thick MS angle iron frame work, powder coated finished over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer and rear opening type with apran for cable entery closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size (but not less than 1.5 sqmm) and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform complete all as specified and directed by Engr-in-Charge of suitable size:- INCOMING:- (i) MCCB3 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magneticsetting- 1 Nos (iii) CT ratio 400/5 Amp class-1 ISI marked - 01 Set of three (iii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No(iv) Ammeter 0-500 Amp digital type with 3 way rotary selector switch - 01 No(v) CT ratio 400/5 Amp class-1 ISI marked - 01 Set of three (vi) Indicating lamp one set of threeOUTGOINGS:- (i) MCCB3 pole, 160 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magneticsetting- 2 Nos(ii) MCCB3 pole, 100 Amps, 50 Hz, 415 Volts, 16 KA Adjustable Thermal and Adjustable Magneticsetting- 5 Nos Note :-i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimbles. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel paint/ Flourcent refelctive lettring .(iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.(iv) Costruction of Foundation & taking out of the old connected cables and reconnection of the same with new thimbles, gland of suitable size are deemed to the above quoted rate. |
| 60 | Supply, laying, jointing, testing and commissioning in replacementof LT underground cables of size 400 Sqmm 1 core, 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavyduty armoured, with multistranded aluminium conductors, IS-7098, Part-II marked, laid in trenches/ duct/ under road/ footpath/ etc complete all as specified and directed by Engr In Charge. |
| 61 | Supply and fix in repairs MCCBs of following current carrying capacity complete all as specified and directed by Engr-in-Charge. |
| 62 | 3 Pole MCCB 400 Amps, Adjustable type,415V, 36KA rating |
| 63 | 3 Pole MCCB 250 Amps, Adjustable type, 415 V, 36KA rating |
| 64 | 3 Pole MCCB 200 Amps, Adjustable type, 415 V, 25KA rating |
| 65 | 3 Pole MCCB 160 Amps, Adjustable type, 415 V, 25KA rating |
| 66 | 3 Pole MCCB 125 Amps, Adjustable type, 415 V, 16KA rating |
| 67 | 3 Pole MCCB 100 Amps,Adjustable type, 415 V, 16KA rating |
| 68 | 4 Pole MCCB 400 Amps, 415 V, Thermal Magnetic Release with breaking capacity 36 KA |
| 69 | 4 Pole MCCB 250 Amps, 415 V, Thermal Magnetic Release with breaking capacity 36 KA |
| 70 | 4 Pole MCCB 200Amps, 415 V, Adjustable type with breaking capacity 25 KA |
| 71 | 4 Pole MCCB 160 Amps, 415 V, Thermal Magnetic Release with breaking capacity 16 KA |
| 72 | 4 Pole MCCB 125 Amps , 415 V, Adjustable type with breaking capacity 16 KA |
| 73 | Note : Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work orderand shall be verified by the Engr-in-charge. |