| 1 | Disconnecting electrically and mechanically indoor/outdoor transformer capacity upto 630 KVAfrom HT/LT terminals and lowering down/getting out from 2/4/6 pole structure/plinth orinside sub station for major repairing/minor repair complete all as specified and directed by Engr-in-Charge. |
| 2 | Disconnecting electrically and mechanically indoor/outdoortransformersinside the substation or outdoor type on outside plinth of capacity 750 KVAcarefully for major/minor repairs complete all as specified and directed by Engr-in-Charge. |
| 3 | Material and Labour for draining out complete transformer oil from transformer of upto 750 KVA capacity at site which found major repair and storing the oil in suitable container (container to be provided by the contractor to keep aside for re-use (after repair) and lifting of core assembly by opening of top cover and other items for inspection/examination of core assembly, to make it ready for transportation to carry out rewinding work in workshop (Transportation charges shall beborne by the contractor against item No 1 & 2 of schedule ‘A’here in after) complete all as specified and directed by Engr-in-Charge. |
| 4 | Material and Labour for transportation of unserviceable transformer of capacity upto 630 KVA from site to workshop and return back for re-installation it on original position/location after repairing from workshop (Rate is deemed to be inclusive of transportation, T&P, crane and man power) complete all as specified and directed by Engr-in-Charge. |
| 5 | All as per item No 4.0 above but of capacity upto 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 6 | Shifting of transformer of capacity upto 500 KVAfrom MES store Yard/Sub Stn (indoor/outdoor) for installation in another place complete all as specified and directed by Engr-in-Charge. |
| 7 | Material and Labour labour for alternative arrangement by hiring, transportation of transformer of capacity 500 to 750 KVAin place of unserviceable transformeron hire basis for 15 daysincluding, installation, connecting and testing of transformer and returnback after installation of repaired transformer complete all as specified and directed by Engr-in-Charge.Note : (i)Repairing of transformer have to be completed within 15 daysno extra cost will be paid toward hiring charges beyond 15 days .Moreover contractor shall not be allowed to shift the hired transformer until it is replaced by the repaired transformer .In case any fault /burning /peeling of painting and any other defects occured in hired transformer the contractor shall have to made good himself from his own expenses. (ii)Contractor should check the available infrasturcture and to be sure regarding safety of hired transformer before installation .The rate quoted is deemed to be includetransportation cost, earthing lead etc.(iii)In case the defective transformer not repaired & installed on its site within the specified period of 15 days from the date of handing over to contractor a panelty recovery @ Rs 1000 /- per day will be charged from his dues.During this period contractor shall not be allowed to shift the hired transformer until it is replaced by the repaired transformer .No extra cost beyond 15 days will be paid to contractor on this account. |
| 8 | Taking down the unserviceable copper wound from transformer of capacity upto 250 KVA, opening top cover,and carrying out the following workcomplete all as specified and directed by Engr-in-Charge:- (a) Dismantling of all attachment viz breather assembly, conservator, oil temperature gauge, HT/LT bushing etc. and keeping aside for reuse.(b)Taking out the core with winding assembly.(c) Removing of complete winding from core and dismantling the core, cleaning of core laminate sheet and keeping aside for reuse(d) Cleaning of complete transformer tank, oil fins, conservator tank removing of sludge, and making the inside surface of tank dry by blowing of hot air and rectify ant leakages in tank or any welding work is reqd as directed and specified. |
| 9 | All as per item No 8.0 here-in -beforebut capacity of transformer 315 to 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 10 | (a)Repairsto the transformer of capacityupto 250 KVA complete all as specified and directed by Engr-in-Charge as follows :-(i) Rewinding of primary/secoundary coil complete using copper wire /strip of appropriate gauge, size and turn as per existing with double paper coated insulation including all requisite insulating materials like packing sleeves, separator, tapes etc. heating, varnishing the core and winding assembly after framing up top and bottom steel structure of transformer all as specified and directed. (ii) Replacement of all insulating materials other than incorporated for rewinding of HT/LT coils as per existing.(iii) Replacement of HT procelain bushing with studs, nuts, washers 3 Nos. and LT procelain bushing with studs, nuts, and washers 4 Nos. and connection with primary and secondary windings and reconnecting with the main terminals as required and directed. (iv) Fixing only breather assembly, conservator, oil temperature gauge after proper cleaning, minor repairs etc. as required and directed.(v) Replacement of all unserviceable gasket from top cover ,4.0mm/6.0mm thick duly pasted with suitable adhesive .(vi) Replacement of unserviceable bolts with new one and fixing of existing serviceable bolts, nuts, washers of different sizes and tightening properly.(vii) Repositioning of core and winding assembly inside the tank, assembling complete unit and making the transformer ready for filling oil and subsequent testing as directed. (viii) Painting of Transformer with existing colour with sparying machine.(b)Note :-HT/LT leg coilsand transformer oilrequired for top up shall be measured and paid separately under relevant items of this Schedule here-in-after as supply only. |
| 11 | All as per item No 10.0 here-in -beforebut capacity of transformer 315 to 750 KVAcomplete all as specified and directed by Engr-in-Charge. |
| 12 | Supply only HT/LT coils with super enamelled copper wire/strip /DPC of high quality duly matching with the existing guage and impedance complete all as specified and directed by Engr-in-Charge. |
| 13 | Material and Labour for ON load Centrifuging and dehydration includingfilteration and cleaning of transformer oil by dehydration machine of 11/0.433 KV transformer at siteand topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed by Engr-in-Charge.Note :-Deficient quantity of Transformer oil required for top up shall be measured and paid separately under relevant items of this Schedule here-in-after as supply only. |
| 14 | Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5 mm gap for filling in transformer or for topping up complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply only Porcelain Transformer bushing on LT (440 Volt) side, including brass stems conical bush for transformer of capacity upto 250 KVA as per existing size complete all as specified and directed by Engr-in-Charge. |
| 16 | All as per Serial item No 15.0 here-in-before butcapacity 315 KVA to 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply only Porcelain Transformer bushing on HT (11 KV) side, including brass stems conical bush and gasketfor transformer of capacity upto 250 KVA as per existing size complete all as specified and directed by Engr-in-Charge.. |
| 18 | All as per Serial item No 17.0 here-in-before but315 KVA to 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply only Gasket of 6 mm thickness for Transformer of any cap complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply and fixing in replacement, Silica Gel Breather assembly incl Silica Gel for indoor/outdoor transformers,capacityupto 250 KVA complete all as specified and directed by Engr-in-Charge. |
| 21 | All as per Serial item No20.0 here-in-before butcapacity 315 KVA to 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply and fixing 3 mm thick Sheet Transparent glass (each not exceeding 0.9 Sqm) ordinary quality and glazing with oil putty on cabin of OTI and WTI gauge of transformer upto capacity 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 23 | Supply and fixing Thermometer of transformer capacity upto 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 24 | Material & Labour for painting of transformer of capacity upto 250 KVA with existing colour, with spraying machine, after cleaning, preparation of outer surface of transformer, including writing of Sl No ,SM No, and capacity of transformercomplete all as specified and directed by Engr-in-Charge. |
| 25 | All as per item No- 24.0 above but of cap315 to 750 KVA complete all as specified and directed by Engr-in-Charge. |
| 26 | Disconnecting electrically& mechanicallyindoor/outdoor transforemrs upto 250 KVA capacity, lowering down/getting out from plinth, 4/6 pole Structure carefully for prevent/stoping for leakage of transformer oil by welding / tightening the loose points at site, including opening of top cover, draining out transformer oil and other items and storing the oil in suitable container (container to be provided by the contractor to keep aside for re -use) including replacement of all unserviceable gasket, replacing the unsv HT/LT porcelain Bushing/studs as directed after repairing/stopingof oil leakage the same re-connecting electrically and mechanically, testingcomplete all as specified and directed by Engr-in-Charge. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transformer oil,T&P, crane, opening/closing of top cover by unscrewing nut, bolts washers , welding etc. The HT/LT porcelain Bushing , studs or gasket should be paid under relevent items of Sch as supply only. |
| 27 | All as per item No 26.0 above but of capacity 315 KVA to 630 KVA complete all as specified and directed by Engr-in-Charge. |
| 28 | All as per item No 26.0 above but of capacity750 KVA complete all as specified and directed by Engr-in-Charge.Note:- (For item no 15.00 to 23.00) Fixing charges of parts under these items are included under item no-26.0 to 28.0). |
| 29 | Supply and filling in replacement of silica gel for transformer of any cap complete all as specified and directed by Engr-in-Charge.. |
| 30 | Supply only new off load tap changer assembly complete, making connection and testing complete of the transformer of following capacity complete all as specified and directed by Engr-in-Charge. |
| 31 | 63 KVA to 250 KVA |
| 32 | 315 KVA to 630 KVA |
| 33 | 500 KVA to 750 KVA Note:- (For item no 30.01 to 30.03) Fixing charges of parts under these items are included under item no-10.0 to 11.0). |
| 34 | Material & labour for replacement of oil level indicator of Transformer of any Cap complete all as specified and directed by Engr-in-Charge. |
| 35 | Platform :- Material and Labour for Brick Masonry ( Using sub class \"B\" Brick) platform of size 2.0 m x 2.0 m x 1 m hight , built in CM 1:4 complete with excavation & earth work , PCC 1:4:8 type D-2 in foundation 150 mm thick , sub class \"B\" brick work in CM 1:5 mm thick rendering in CM 1:6 on sides and top of the brick work , upto 150 mm below ground level , supply and fixing of 02 Nos MS Chennels of suitable sizefor balancing of Transformerembedded in PCC 1:2:4 type B-1 up to 100 mm Thick RCC 1:3:6 with 10 mm steel bar includding 20 mm graded aggregate , including provn of stair case on one side complete all as specified and directed by Engr-in-Charge. |
| 36 | Material and labour for crushed stone aggregate of size 40 mm, for loose filling under 2/4/6 pole structure / along the transformer plinth in side the fencing area after cleaning/ surface excavation and including making boundary around the 2/4/6 pole structure/ transformer fencing area using sub class B brick etc, complete all as specified and directed by Engr-in-Charge. |
| 37 | Material and Labour for disconnecting burnt end or portion of cable from Transformer / LT panel/pole, removing the cable from loop including necessary excavation & earth work in soft/loose soil relaying and reconnecting the cable by removing burnt portion of cable and preparing fresh terminals including fixing of new lugs for 95 Sqmm to 400 Sqmm 3½ core of LT cable including taping, complete all as specified and directed by Engr-in-Charge. |
| 38 | All as per Srl item No. 34.0 here in before but for upto 70 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 39 | Material and labour for fixing in replacement of Aluminium straight bolt terminal cable to flat type suitable for transformer\"s LT/HT stud any size for fixing LT cables complete all as specified and directed by Engr-in-Charge. |
| 40 | Supply, laying, jointing, testing and commissioning in replacmentLT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavyduty armoured, with multistranded aluminium conductors, IS-1554 marked of size 630 Sqmm 1 core , laid in trenches/duct complete all as specified and directed by Engr-in-Charge. |
| 41 | All as per srl item No 37.0 here-in-before but of size 400 Sqmm single core complete all as specified and directed by Engr-in-Charge. |
| 42 | Supply andfix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified and directed by Engr-in-Charge offollowing size :- |
| 43 | 95 Sqmm 3 core. |
| 44 | 120 Sqmm to 185 Sqmm, 3 core. |
| 45 | Supply andfixCable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified and directed by Engr-in-Charge offollowing size :- |
| 46 | 95 Sqmm 3 core. |
| 47 | 120 Sqmm to 185 Sqmm, 3 core. |
| 48 | Material and labour for dismantling, testing & reinstallation of Battery Charger incl transportation to workshop and back for servicing of Bty Bank Charger of cap 24-110 Volt DC of any make including replacement of the following unsv spares complete all as specified and directed by Engr-in-Charge:- (i) AVR Card Single Phase Charger -01 No(ii) Control Transformer -01 No(iii) Rotary Switch (1 Pole) -01 No(iv) Power Diode-01 No-03 Nos(v) Power SCR-02 Nos(vi) DC capacitors-01 No(vii) Potentiometer -06 Nos(viii) Pilot Lamp -01 No |
| 49 | Supply and fixing in replacement battery bank comprising 50 volts, 100 AH@ 2 Volt each- 25 Nos sealed maintenance free battery complete all as specified and directed by Engr-in-Charge. |
| 50 | Material and Labour in replacement Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5mbelow normal ground level, connected to galvanized strip 32 x 6 mmby means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electricalplate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised iron side complete all as specified, including testing and commissioning complete all as specified and directed by Engr-in-Charge.Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in soft/loose soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 type C2as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement 6mm dia both waysas in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc.(b)The quoted rates shall also deemed to include the cost of earth test point and earth strip/GIlead wire and protection pipe upto 7.5 meter beyond the earth plates electrode. |
| 51 | All as per item No 43.0 above but using copper plate 60 cm × 60 cm × 3 mm thick electrode and 20 × 3mm copper strip as earthing lead, in replacementof any types of earthing, complete all as specified and directed by Engr-in-Charge. |
| 52 | Supply and fixing in replacement for Danger Notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white , with letters, figures and conventional skull and bobes in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25 x 20 cm size including taking down old one complete all as specified and directed by Engr-in-Charge. |
| 53 | Material and labour for Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and directed by Engr-in-Charge. |
| 54 | Material and labour for Cement Concrete type B-2 mix, 1:2:4 (40mm graded aggregate) 150mm thick, finishing the top surfaces fair and even complete all as specified and directed by Engr-in-Charge. |
| 55 | Material and Labour for cutting and removing grass, vegetation bushes etc from surrounding of installation/LT Panel/Four Pole structure/Sub Stations and removing all rubbish to a distance not exceeding 50 m complete all as specified and directed by Engr-in-Charge. |
| 56 | Material and labour for servicing /testing ofbreaker/control panelincludingCT, PT and relays in control panelof RMU / VCB of capacity 400-1250 Amps and rating 11 KVcomplete as details mentioned complete all as specified and directed by Engr-in-Charge as under:- (a) Details of servicing of breaker :-(i) Adjustment of mechanism if required.(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.(iv) Check for rust and wear.(v) Check Spring Tension and pitting of the Cluster Contacts.(vi) Visual check for rust and deformation.(vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.(viii) Check for loosened connections, rust, damaged lead wires.(ix) Check whether the contacts are damaged by arcing. |
| 57 | (x) Checking of control circuit & tighten the connections if any.(xi) Check close & trip coil.(xii) Checking of Jaw Contacts Conditions and repair/adjust.(xiii) Replace the jaw contacts,If required.(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.(xv) Replacement of Dashpot/shock absorbers .(xvi) Replacement ofcarbon brush of spring charging motor (b) The following test shall be carried out:-(i) Primary Injection Test of CT / PT(ii) Closing & Opening Timing Test for all three poles.(iii) IR Test with megger in open and closed condition.(c) Testing of following relays of control panelwith Secondary Injection Kit ,checking andprogramming of relay: -(i) Over current and earth fault relay(d) Testing of followig Aux relay(i) DC Supply supervision relay.(ii) Master trip relay |
| 58 | Supply and fixing in replacement of Numerical relay drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 59 | Supply and fixing in replacement of current transformer (CTs) having ratio 200/100/5-5Amps for 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 60 | Supply and fixing in replacement of current transformer (CTs) having ratio 150/75/5-5Amps for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 61 | Supply and fixing in replacement of current transformer (CTs) having ratio 100/50/5-5Amps for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 62 | Supply and fixing in replacement of current transformer (CTs) having ratio 60/30/5-5Amps for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 63 | Supply and fixing in replacement of potential transformer 3phase 3 limbs (PT) unit drawout type for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 64 | Supply and fixing in replacement of LED indication lamp (R,Y,B) for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 65 | Supply and fixing in replacement of anti-condensation space heater for drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 66 | Supply and fixing in replacement of vaccum interruptor for 400/630/800Amps drawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 67 | Supply and fixing in replacement of isolating contact assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 68 | Supply and fixing in replacement of fixed blockcontact assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 69 | Supply and fixing in replacement of moving blockcontact assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 70 | Supply and fixing in replacement of motor and gear assembly 230Volt ACfor 400/630/800Ampsdrawout type in 11 KV,HT VCB, ABB/Siemens/Crompton complete all as specified and directed by Engr-in-Charge. |
| 71 | Supply and fixing in replacement of spring bearing gear assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 72 | Supply and fixing in replacement of closing coil assembly 24V DCfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 73 | Supply and fixing in replacement of tripping coil assembly 24V DC for 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as specified and directed by Engr-in-Charge. |
| 74 | Supply and fixing in replacement of auxillary contact(7NO+7NC) assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as directed by Engr In Charge by Engr In Charge. |
| 75 | Supply and fixing in replacement of digital Amp meter(CT secondary side selectable 5A)for 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as directed by Engr In Charge by Engr In Charge. |
| 76 | Supply and fixing in replacement of digital volt meter( secondary voltage 110 V) selectable 5A)for 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as directed by Engr In Charge by Engr In Charge. |
| 77 | Supply and fixing in replacement of panel door lock assemblyfor 400/630/800Ampsdrawout type in 11 KV,HT VCB,complete all as directed by Engr In Charge by Engr In Charge. |
| 78 | Supplying and fixing (in replacement) factory made and tested,Bus bar chamber, outdoorpedestal type,suitable for LT415 volts 3 phase 4 wire, 50 Hz , AC supply system, havingduly insulated fourNos aluminumbus bars,of rating600 Amps, installed on epoxy / SMC typeinsulator. One no of MCCB of cap 250 Amp, 4 pole, 25 KA, adjustable type alongwith separator terminal should be connected with Main Bus Bar as outgoing. The panel shall be dust and vermin proof, IP-65 Protection class and made of 3.15 mm CRCA MS sheet and 40x40x5mm thick angle iron base frame work, suitable for connection of two nos LT cable of size 3.5 core 400 Sqmm one nos 70 sqmm 3.5 core, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,both side openingtype, with aprons for cable entry,with double door shutter and locking arrangement of minimum size 65\0cm x 60cm x 45cm ( box size excluding legs) and mounted on angle iron pedstal 45 cms above groungd level allas specified including taking out oldfeeder pillar , LT cable from loop for connecting in new panel and necessary excavation etc incl necessary PCC work for foundation complete all as specified and directed by Engr-in-Charge. |
| 79 | Material and Labour forpainting with two coats of superior aluminium/smoke grey paint or as existing including necessary preparation of surfacesof steel fencing by brushing/cleaning complete with steel structure/wire mesh/frame/ gate for 11 KV transformer/2 pole to 8 pole structure/ HT panels/ Sub Station complete all as specified and directed by Engr-in-Charge. |
| 80 | Material and labour Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cementcomplete all as specified and directed by Engr-in-Charge. |
| 81 | Fencing :-Material and Labour for perimeter fencing of size 04m x 04m x 2m havingMS work ofangle ironfor post and struts of fencing around the transformer plinth/substation/LT panels etcdrilling holes flat iron fillet for securing wire mess by welding to angle iron frame and framed workas in door/gate of angle ironand wire mesh. Door to be fixed by 03 nos 100 mm long hinges and one sliding door bolt of 300 mm long for locking arrangement complete all as specified and directed by Engr-in-Charge.Details are as follows:-(a) Angle iron post to post distance maintained not more than 02 mtr ,size of angle shall be 40x40x5mm.Angle Iron shall be embedded in natural ground not less than 0.60 m deep.(b) MS wire 75x75mm mesh 3.15 mm dia ,2mtr height and shall befixedto post with flat iron 32 x 6 mm fillet with two coats of synthetic enamel paint over a coat of red oxide primer.(c) Cement concrete type D-2, 1:4:8 using grade crushed stone aggregate for mass concrete/ foundation.(d) Brickwork with subclass \"B \" bricks, straights or curved on plane exc 6m mean radius ,built in cement mortar 1:6 complete for toe wall along the perimeter fencing. The toe wall shall be one brick thick (23 cm), 30cm high (15 cm above GL and 15 cm below GL) on 75 mm thick PCC lean concrete.(e) The exposed surfaces of brickwork shall be rendered 15mm thick in CM (1:4) finished fair and even without using extra cement.(f) The steel gate shall be of size 1.00m x2.00 m fabricated from angle iron 40x40x5 mm frame and 12x12 mm square guard bars.(g) All the exposed surfaces of steel shall be painted with two coats of Synthetic enamel paint over one coat of Red Oxide Primer.(h) Necessary excavation and earthwork shall be included in the quoted rate. |
| 82 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in softloose soil for laying / taking up/ taking down of cablesand getting out and leveling of bottom surface to required level all as specified and directed by Engineer- in- Charge. |
| 83 | Returning filling in,. Including spreading, leveling,. Watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 84 | Removing excavated material (i.e. soil) from site to a distance n. exec 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge. |
| 85 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed by Engr-in-Charge. |
| 86 | Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm complete all as specified and directed by Engr-in-Charge. |
| 87 | All as per srl item above but here-in-before but using old cable coveobtained during excavation complete all as specified and directed by Engr-in-Charge. |
| 88 | Supplying, laying, jointing testing and connecting in replacementXLPE insulated, screened, PVCbedded, galvanized steel strip or wire armored,electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed by Engr-in-Charge of following sizes |
| 89 | 120 sqmm 3 core. |
| 90 | 185 sqmm 3 core |
| 91 | Supply andfix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable complete all as specified and directed by Engr-in-Charge of following size :- |
| 92 | 120 sqmm 3 core |
| 93 | 185 Sqmm, 3 core. |
| 94 | Supply only Fuse wire of any size (as per site reqmt) |
| 95 | Note : Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work orderand shall be verified by the Engr-in-charge. |