| Sl. No. | Item Description |
| 1 | Total amount ofSch \"A\" Part-I : (Buildings/ Structures) |
| 2 | Total amount ofSch \"A\" Part-II : (Earthwork, Excavation, Site Clearance& Site Development) |
| 3 | Total amount ofSch \"A\" Part-III : (Internal Water Supply) |
| 4 | Total amount ofSch \"A\" Part-IV : (Internal Electric Supply) |
| 5 | Total amount ofSch \"A\" Part-V :(External Water Supply) |
| 6 | Total amount ofSch \"A\" Part- VI : (External Electric Supply) |
| 7 | Total amount ofSch \"A\" Part-VII: (Lightning Protection) |
| 8 | Total amount ofSch \"A\" Part-VIII : (Area Drainage) |
| 9 | Total amount ofSch \"A\" Part-IX : (Sewage Disposal) |
| 10 | Total amount ofSch \"A\" Part-X : (Road/ Path/ Hardstanding) |
| 11 | Total amount ofSch \"A\" Part-XI (Lift) |
| 12 | Total amount ofSch \"A\" Part-XII : (Fire fighting) |
| 13 | Sch \"A\" Part-XIV: (Miscellaneous B/R & E/M Items (BOQ)(Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only.) |
| 14 | Boring for cast in situ piles 500mm dia to 53m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified. |
| 15 | Boring for cast in situ piles 600mm dia to 53m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified. |
| 16 | Boring for cast in situ piles 500mm dia 45m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified. |
| 17 | RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in cast in situ bored pile of 500mm dia and 45m length all as specified and as shown in drg. |
| 18 | RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in pile cap and grade beam all as specified and as shown in drg. |
| 19 | RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in cast in situ bored pile of 500mm dia and 53m length/ all as specified and as shown in drg. |
| 20 | RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in cast in situ bored pile of 600mm dia and 53m length/ all as specified and as shown in drg. |
| 21 | Providing TMT bars 10 mm dia and over, cut to length, bent to shape required incl cranking, bending, sprilly for hooping for columns etc for bored piles/grade beams/tie beams and pile caps complete all as specfied. |
| 22 | Providing TMT bars 5 mm dia and over but up to 10mm dia as in stirrups/helical stirrups for piles and binding with mild steel wire etc for grade beams, tie beams and bored piles complete all as specfied. |
| 23 | PCC (1:4:8) type D2 using 40mm graded stone aggregate for concrete layer below pile cap/grade beam andfoundation complete all as specfied and as shown in drg. |
| 24 | M&L for form work to sides of pile cap, grade beams and tie beams for rough finished flat concrete surface as specified and as directed. |
| 25 | M & L precast cement concrete block masonry with solid blocks Type C11:3:6 (20mm garded aggregate) exc. 10cm in width and setting in cement mortar 1:6, complete all as specified and as directed. |
| 26 | Testing of piles (initial load test) all as per IS for cast in situ 500 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified . |
| 27 | Testing of piles (initial load test) all as per IS for cast in situ 600 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified . |
| 28 | Testing of piles (Routine load test) all as per IS for 500 mm dia including removing the testing equiptment from site after testing is complete all as specified. |
| 29 | Testing of piles (Routine load test) all as per IS for 600 mm dia including removing the testing equiptment from site after testing is complete all as specified. |
| 30 | S & F for Pillar cock auto closing system with 65 mm extension body 15 mm bore, cast copper alloy fancy type, chromium plated, with lcup screwed down, high pressure, screwed for iron pipe and fixedetc.completeall asspecified and directedMake : Jaguar cat part No. PRS-CHR-031L65 or equivalent in approved list of makes |
| 31 | S & F for conceled stop cock and flush cock 15 mm bore with fitting sleeve, operating lever & adjustable wall flange for WHB, EWC and sink complete as specified and directedMake : Jaguar cat part No. CQT-CHR 23083Kor equivalent in approved list of makes |
| 32 | S & F for brass with cromium plated health faucet with 8 mm dia, 1 m long flexible tube chrome finish & wall hook with NRV(back flow preventer) screwed for iron pipe and fixed complete as specified and directedMake : Jaguar cat part No. ALD-CHR-577 andor equivalent in approved list of makes |
| 33 | S & F for 2 way bib cock 15 mm bore of cast copper alloy, fancy type, chromium plated with adjustable wall flange for health faucet screwed for iron pipe and fixed etc. complete as specified and directedMake : Jaguar cat part No. ORP-CHR 10041PMor equivalent in approved list of makes |
| 34 | S & F for single lever sink mixer with swinging spout on upper side (wall mounted model) with connecting legs 15 mm bore,of cast copper alloy, fancy type, chromium plated with wall flange screwed for iron pipe and fixed etc. complete as specified and directedMake : Jaguar cat part No. LYR-CHR-38165 or equivalent in approved list of makes |
| 35 | S & F for autoclosing conceled urinals flush valve 15 mm bore with wall flangescrewed for iron pipe and fixed etc. complete as specified and directedMake : Jaguar cat part No. PRS-CHR-073 or equivalent in approved list of makes |
| 36 | Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly for one light/ ceiling fan /exhaust fan/Bell point controlled by one 5/6 amps one way switch complete all as specified and directed. |
| 37 | All as per item No 36 but for One Socket outlet, three/ five pin, 5 Amp, independent controlled by one 5/6 amps one way switch Point or switch/socket combination 5 amps, 5 pin complete all as specified and directed. |
| 38 | All as per item No 36 but for One Socket outlet, three/five pin, 5 Amp, same board controlled by one 5/6 amps one way switch complete all as specified and directed. |
| 39 | All as per item No 36 but for One light point controlled by 2 Nos, Two Way switches 5/6 Amps complete all as specified and directed. |
| 40 | Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty, PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 2.5 Sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent. |
| 41 | S&F LED light fitting 22 watt, 220 V AC Square/Circular shaped recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size completeall as specified and directed. |
| 42 | S&F LED light fitting 10 watt, 220 V AC Bulkhead with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size completeall as specified and as directed. |
| 43 | S&F hybrid solar security light with luminous efficacy 175 lum/Watt along with monocrystalline solar panel of peak wattage 35W, Lithium ferro phosphate type battery of capacity min 20Ah, battery voltage 12.8 V, charge controller MPPT type of wattage min 17W, fitting shall be made of pressure die cast aluminium housing with IP65 protection and impact resistance of IK 08 complete with and including wall mounted bracket fabricated out of 40mm GI pipe light grade bend to shape1.5 mtr long and two nos wall mounting clamps using 25x4mm thick MS strip bend to shape and welded with pipe to form solid structure and one run of 1sqmm PVC insulated multistranded copper conductor wire connecting PVC terminal to fitting all as specified and as directed. |
| 44 | S&F Vertical TPN Distribution Board 4 way double door 415 Volts with provision for MCCB 4P as incomer and SP/TP MCBs as out going with IP 43 protection, door earthing, isolated neutral bar, mechanical impact strength IK 09 including cement spill protector all as specified and as directed. |
| 45 | Sheet metal enclosure distribution board MCB DB SPN 6 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified. |
| 46 | S&F MCCB 100A, 16KA 4P along with enclosure suitable for mounting the MCCB all as specified and as specified. |
| 47 | Design, Supply, install and testing of Air insulated type feeder/distribution with insulation class F, dust and vermin proof made up of hot galvanised sheet steel enclosure with four Nos aluminium bus bars with five galvanic process in the entire length as per IEC 61439-6, degee of protection IP55 of ampere rating 160A all as specified and as directed. |
| 48 | Supply and fix flange end suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 49 | Supply and fix bends suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 50 | Supply and fix end cover suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 51 | Supply and fix internal fire barrier suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 52 | Supply and fix rigid support suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 53 | Supply and fix spring support suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 54 | Supply and fix normal support suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 55 | Supply and fix Tap off box with 40A MCB suitable for installation of 160A BBT system as per item No 47 all as specified and as directed. |
| 56 | Supply and fix Tap off box with 63A,16KA, MCCB (feeding DG Bus duct) suitable for installation of 160A BBT system as per item No 42 all as specified and as directed. |
| 57 | Supply and fix Tap off box with 100A, 16KA MCCB (feeding UPS Bus duct) suitable for installation of 160A BBT system as per item No 42 all as specified and as directed. |
| 58 | Design, Supply, install and testing of Air insulated type feeder/distribution with insulation class F, dust and vermin proof made up of hot galvanised sheet steel enclosure with four Nos aluminium bus bars with five galvanic process in the entire length as per IEC 61439-6, degee of protection IP55 of ampere rating 400A all as specified and as directed. |
| 59 | Supply and fix flange end suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 60 | Supply and fix bends suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 61 | Supply and fix end cover suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 62 | Supply and fix internal fire barrier suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 63 | Supply and fix rigid support suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 64 | Supply and fix spring support suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 65 | Supply and fix normal support suitable for installation of 400A BBT system as per item No 58 all as specified and as directed. |
| 66 | Supply and fix end feed box with 400A 25KA MCCB suitable for installation on 400A BBT system as per item No 58 all as specified and as directed. |
| 67 | Supply and fix Tap off box with 63A,16KA, MCCBsuitable for installation on 400A BBT system as per item No 58 all as specified and as directed. |
| 68 | Supply and fix Tap off box with 100A, 16KA MCCB suitable for installation on 400A BBT system as per item No 53 all as specified and as directed. |
| 69 | Supply and fix Tap off box with 125A, 16KA MCCB suitable for installation on 400A BBT system as per item No 58 all as specified and as directed. |
| 70 | Cutting existing 200 mm boreDI water mains fresh water line and inserting Tee of size 200x200x100 mm dia for taking branch connection including fittings and lead joints all as specified and as directed. |
| 71 | Supply and lay DI, S/S pipe including specials, Class K-9 fittings, 100 mm (4\") dia including Add for Cost of flange (Cost considered for 1 Mtr Pipe), leather gasket, bolts, nuts, washers, transportaion charges etc. all as specified and as directed. |
| 72 | Supply and fixWafeertype Butterfly Gate Valves of 80 mmdia complete with and including flanges, leather washers, rubber gasket, bolts, nuts all as specified and directed by the Engr-in-charge. |
| 73 | M & L Valve chamber of internal size 1.20 m X 1.20 m X 1.20 m (internal dimentions) including excavation of earth work in any type of soil, 150mm thick PCC in 1:4:8 type D2 foundation , brick work in CM 1:6, 15 mm thick rendering in CM 1:4 to both internal and external surfaces upto 150mm depth below GL, PCC 1:3:6 type C1 as in coping, cover with two Nos of hinges and one No. handle made out of MS round bar 10mm dia with necessary locking arrangement including painting to the steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer complete all as shown on drg and as specified. Note:- The estimated cost includes all earthwork and connected items. |
| 74 | Supply, installing, testing and commissioning of electrically driven centrifugal Pump set as per specification, motor TEFC type, 2900 rpm, 420 V, 50 Hz, 3 ph, class \"F\" insulation, IP 55 protection, not less than 5 HP, starting on suitable DOL/Star Delta starter. The pump shall be horizontal, end suction, top discharge. The pump shall have cast iron casing, cast iron/bronze impeller(as per manufacturer), carbon steel shaft with common base frame (fabricated mild steel channel frame or cast iron type) placed on RCC (1:2:4) including foundation bolts, nuts etc. complete with antivibrator pad as required capable of discharging not less than 450 LPM at 55 mtr head inclusive of suitable rated 3 ph starter as recommented by the manufacturer, PVC insulated copper cable connection from starter to the motor terminals all as specified and directed by the Engineer-in-charge.Make:- Kirloskar Brothers/ equaivalent. |
| 75 | Supply and fix foot valve conforming to IS 4038, 80mm (3\") dia all as specified and as directed. |
| 76 | Supply and fix valve ductile iron Non Return valve Gun Metal type conforming to IS 5312 all as specified and as directed. |
| 77 | Supply, install, testing and commissioning of factory made and manufacture having type test certificate of CPRI out door type feeder pllar box suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating of suitable 1000 Amps for phases and suitable 500 Amps for neutral fixed on porcelain insulators.The panel shall be weather proof, dust and vermin proof IP-65 class protection and fabricated out of 3.15mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxhas LT switchgear and measuring instrumentson both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practicesand comprising of followings acessorties( Location LTP No1 ofschematic plan)INCOMING(a) ACB Draw out type 4P 630 Amps 50 KA 415 Volts, 50 Hz, Thermal magnetic Release (Draw out type)(b) Digital volt meter 0-500 Volts-01(c)Digital Ampere meter 0-300 Amps with andincludingCTs |
| 78 | OUTGOING(a) MCCB TPN 320 Amps 36 KA Thermal magnetic Release- For building panel incomer.(b) MCCB TPN 200 Amps , 25 KA Thermal magnetic Release -03 Nos for (stand by supply panel, capacitor bank and spare)(e) Internal wiring of panel with stranded copper cable of suitable size(f) Neon phase indicating lamp(Set ofthree)-01 Nos(g) Stenceling of pannel boardincludingmarking of distribuitions |
| 79 | Supply, install, testing and commissioning of factory made and manufacture having type test certificate of CPRI Outdoortype pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating of suitable 300 Amps for phases and suitable 150 Amps for neutral fixed on porcelain insulators.The panel shall be weather proof, dust and vermin proof IP-65 class protection and fabricated out of 3.15 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxhas LT switchgear and measuring instrumentson both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practicesand comprising of followings acessorties :-(Location: LTP No.2 (DG AMF Panel) ofSchematic plan) INCOMING(a) MCCB TPN 200 Amps, 25 KA Thermal Megnatic Release.(b) Digital volt meter 0-500 Volts-01(c)Digital Ampere meter 0-300 Amps with andincludingCTs-01 No |
| 80 | OUTGOING(a) MCCB 415 Volts, 125 A TPN,18KA- 02 Nos (for fire fighting panel and spare)(b) MCB 415 Volts 40 A TPN,18 KA - 05 Nos ( for 03 nos 13 passenger lift, 01 No fresh water pump panel and 1 spare)(c) MCB 415 Volts 25 A SPN - 02 No ( for aviation obstruction light,security light and stair case lightning)(d) Internal wiring of panel with stranded copper cable of suitable size(e) Neon phase indicating lamp(Set ofthree)-01 Nos(f) Stenceling of pannel boardincludingmarking of distribuitions |
| 81 | Supply, install, testing and commissioning of factory made and manufacture having type test certificate of CPRI indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 500 Amps for phases and 250 Amps for neutral fixed on porcelain insulators.The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 40 x 40 x 5 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxhas LT switchgear and measuring instrumentson both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practicesand comprising of followings acessorties :-(Location: LTP No 3(Building panel) |
| 82 | INCOMING(a) MCCB TPN 320 Amps 36 KA, Thermal megnatic Release -01 No (Incoming)(b) Digital volt meter 0-500 Volts-01(c)Digital Ampere meter 0-100 Amps with andincludingCTs-01 NoOUTGOING(a) MCCBTPN 40 Amps 4 pole , 415 Volts - 08 No (G+7).(b) MCB SPN 32 Amps - 02 No(c) Digital volt meter 0-500 Volts-01 No (d) Digital Ampere meter 0-300 Amps with andincludingCTs(e) Neon phase indicating lamp(Set ofthree)-01 Nos(f) Stenceling of pannel boardincludingmarking of distribuitions |
| 83 | Supply, install, testing and commissioning of factory made and manufacture having type test certificate of CPRI indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 60 Amps for phases and 30 Amps for neutral fixed on porcelain insulators.The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 40 x 40 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxhas LT switchgear and measuring instrumentson both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practicesand comprising of followings acessorties :-(Location: LTP No - 4 Fresh water supply panel)INCOMING(b) MCCB 40A 415 Volts, TPN , 18 Ka, 50 Hz-01 NO.(b) Digital volt meter 0-500 Volts-01(c)Digital Ampere meter 0-100 Amps with andincludingCTs-01 No |
| 84 | OUTGOING(a) MCB 16 Amps rating 4 pole -02 Nos( For G+7 and one spare)(b) DOL starter for 05 HP Fresh water supply pump- 2Nos(c)Digital volt meter 0-500 Volts-01(d)Digital Ampere meter 0-100 Amps with andincludingCTs(e) Neon phase indicating lamp(Set ofthree)-01 Nos(f) Stenceling of pannel boardincludingmarking of distribuitions |
| 85 | Supply, install, testing and commissioning of factory made and manufacture having type test certificate of CPRI indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 200 Amps for phases and 100 Amps for neutral fixed on porcelain insulators including necessary components and cabling for controling through presure switch, PLC control, NO-NC contacts, Battery charger, over speed lock, high water temperature control, low lubricant presure cut out, Dry Run prevetor, over load protection, current sensing type single phase preventor complete with all accesories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual off operation, interlocking of pumpset as specified.The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 40 x 40 x 5 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxhas LT switchgear and measuring instrumentson both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practicesand comprising of followings acessorties :-(Location: (No 5 - fire fighting panel) |
| 86 | INCOMING(a) MCCB 415 Volts, TPN 125 Amps,4 P, 25 kA - 01 No (Incoming)(b) Digital volt meter 0-500 Volts-01(c)Digital Ampere meter 0-100 Amps with andincludingCTs-01 NoOUTGOING(a) MCB TPN 100 Amps 18 kA - 01 Nos(b)MCB TP 40 Amps 18 kA - 01 No(c)MCB SPN 25 Amps 10 kA - 01 No(d) Star Delta starter for 75 HP pump- 1Nos(e) DOL starter for 7.5 HP Jockey pump- 1Nos(f) Neon phase indicating lamp(Set ofthree)-01 Nos(g) Stenceling of pannel boardincludingmarking of distribuitions |
| 87 | Supply and installation of HT 11 KV, 630 Amps, 21 KA Motor operated compact outdoor both side extensible, non drawout type (+C+) (01 No. Load break Switch (OD) incomer SAFEPLUS Compact gas insulated for existing Ring Main Unit (RMU), All live parts enclosed in a welded stainless steel tank of IP 67 class of protection including coupling accessories with battery and battery charger all as specified and as directed. The RMU will be installed at existing \"FOST\" open sub station where HT supply tapping point. Make: Crompton. |
| 88 | Supply and installation of HT 11 KV, 630Amps,21KA Motor operated compact outdoor both side extensible, non drawout type (+CV+) (01 No Load break Switch (OD) incomer and no fixed type motor operated Vaccum circuit breaker outgoing SAFEPLUS Compact gas insulated Ring Main Unit (RMU), All live partse enclosed in a welded stainless steel tank of IP 67 class of protection including coupling accessories with battery and battery charger all as specified and as directed. (The RMU will be installed at proposed powerhouse near project building.) |
| 89 | Supply,spreading and levelling riddled soil as earth cushioning to UG cable by usinng IS sieve to seprate the composite/roots etc and refilling spreading in trenches as cushioning and rammed down to form a solid bedall as specified and directed at site. Note:- Punned thickness shall be measured and paid. |
| 90 | Supply and laying GI pipe Medium grade of size 150mm for cable protection , road crossings, canal, sewage lineincluding all necessary fitting complete all as specified by Engineer -In Charge. |
| 91 | S&F HT Cable route marker of Cast Iron type Circle 100 diaall as specified and as directed. |
| 92 | S&F LT Cable route marker of Cast Iron type Circle 100 dia all as specified and as directed. |
| 93 | Supply and fix MD-XL Double metalized paper (Extra Low Loss) Capacitor for 3 phase,440 V, 50 Hz system for permissible non-linear load 20 %Automatic Power Factor Correction (APFC) Panel outdoor type alongwith protection enclosure,capacity 80 KVAR all as specified and as directed. |
| 94 | S&F blue metal stones for Electric installations of size 20 mm all as specified and as directed. |
| 95 | Supply and installation of Transformer step down, indoor type, copper wound, oil cooled complete with standard fittings HT 11/0.433 KV, 3 phase, 4 wire with off load tappings on HT side to vary secondary voltage within limit +/- 5% in step of +/- 2.5%. ONAN all as per IS :1180,2026 of capacity 400 KVA duly initial oil filled up to normal level and EEL1 level of tranformer as per IS 1180 with following accessories and functions alongwith foundation as per the recommendations of the manufacturer.(i) No load loss as per standard (subject to IS tolerance) (ii) Full load loss as per standard (subject to IS tolerance) (iii)Impedance is 4.75% (subject to IS tolerance) (iv) Vector group is Dyn 11 (v) Silica gel breather (vi) conservator with plain oil gauge and oil drain plug (vii) Top filter valve (viii) Bottom filter cum drain valve (ix) shut off valve between buchholz relay and conservator (x) Off circult tap changer (xi) Rating and dilagramme plate (xii) Earthing terminals (xiii) Thermometer pockets (ivx) Lifting lugs (xv) Air relief plug (xvi) Jacking pads (xvi) Bi-directional rollers (xviii) Explosion vent with single diaphragm (xix) Detachable radiators (xx) Inspection cover (xxi) Danger notice board (xxii) cable entry box., The secondary LT will be laid suitable ampere rating insulatedGI srip for 400KVA tranformer upto main LT panel boardinlcuding incoming/outgoing HT cable/ bus bar trunk be drawn through 100 GI garde pipe with supporting structure. |
| 96 | S&F Chain Link fencing with angle iron bar type over perimeter of electric installation area 10X 4 Square meter by 0.5 meter PCC foundation all around inculding gateall necessary connections complete alll as specified by Engineer-in-Charge |
| 97 | Supply and fixing AcrylicLetter sign board waterproof outdoor type wall mounted at pump house/power house on top of building,of size1 Mtr X1 Mtr sheet thickness 5mmdisplying matter : POWER HOUSE/ PUMP HOUSEin English LetterLetter size 5\" heightall necessary connections complete alll as specified by Engineer-in-Charge |
| 98 | Supply and fixing AcrylicLetter sign board waterproof indoor type wall mounted at pump house/power house on wall,of sheet thickness 5mmdisplying matter : ELECTRIC SUPPLY DISTRIBUTION/ WATER SUPPLY DISTRIBUTIONin English LetterLetter size 2\" heightall necessary connections complete alll as specified by Engineer-in-Charge |
| 99 | M & L Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized iron strip of size 32 x 6 mm size by means of bolts, nuts, check nuts and washers of galvanized ironsteel all as shown in Electrical Plate No.3 connecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1(using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form workincluding painting of earth value & name of earth pit on top of earth pit cover with handrail will be above checked or parking tiles complete including necessry test on completionall as specified and as directed. Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 20 mm dia watering pipe, wire mesh, 40 mm dia light grade GI protection pipe for earth lead etc.complete. |
| 100 | RCC septic tank designed for 50 users to carry sewage and sullage water, excavation in any type of soil, , PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls, Base Slab, Baffle walls and Roof slab including beams etc with Vent shaft, manhole opening with cover connection etc. complete with effective depth of 1.5meter and overall depth of 3 meter all as specified and as directed. |
| 101 | RCC septic tank designed for 100 users to carry sewage and sullage water, excavation in any type of soil, , PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls, Base Slab, Baffle walls and Roof slab including beams etc with Vent shaft, manhole opening with cover connection etc. complete with effective depth of 1.5meter and overall depth of 3 meter all as specified and as directed. |
| 102 | Soakage well 1.8 M dia X 3.0 M effective depth Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size all as specified and as directed. |
| 103 | Sockage well 3 M dia and 1.2 M deep incl excavation any type of soil, PCC 1:3:6 foundation honey combbed PCC block wall M 25 topping incl intercepting chamber in cement mortar, RCC cover slab, interconnecting RCC pipe filled with brick bats etc all as shown on drg. |
| 104 | Supply, installing, testing and commissioning of passenger lift having capacity (884Kgs)/ 13 passengers, AS per IS 14665 Lift well dimension 2500X1900 mmand lift entrance door opening is 900 mm, Microprocessor controlled complete with power driven automatci stainless steel (SS) electrically operated with simplex full collective/selective control suitable for operation with or without attendent to serve 8 floors, ie ground floor and 7 upper floors with rated speed of 1.50 mtr/second with and including electric power operating doors, automatic electric levelling device, automatic rescue devices, a screen of infrared beam acting on a curtain across the door entrance, stainless steel enclosures as specified including all steel works in machine room such as machine beam, bearing plate with beam and necessary buffer support, channel and ladder in pit. Inluding Automatic Rescue Device (ARD).a) Stops and openings:-8 stops/ 8 openings on the same side. |
| 105 | (b) The integral dimension of the lift car should be suitable size for the specified load and in accordance with the statutory requirements.(c) The inside car measurement shall be based on lift well dimensions shown on drawings forming part of the Contract.Each lift shall be complete with following accessories & fittings.(i) Double button with 7 segmentaldisplay at all floors. (ii) Car opening panel with micro stroke push button with 7 segment digital car position indicator, car direction indicator (iii) Fire exitingusher which provided at main lobby. (iv) Battery operated alarm bell and emergency lift with battery. (v) Voice Synthesizer (vi) Car Chime (vii) Provision of cross flow rectangular (low noise/mild air flow) fan-01 of approved make. (viii) S&F Decorative LED spot light (ix) Provn of emergency intercom system (car machine room-control system) (x) Oveload function, constant indication/buzzer. (xi) 5/15 A power socket & light point at every floor level in the hoist way. (xii) MS Ladder (xiii) 3 Phase power supply & earthing from machine room to all equipment. (xiv) Multi beam full length infra red door sensor (minimum of 32) (xv) Emegency landing device ELD (ARD) (xvi) Extra cores in travelling cable for customer smoke detectors. (xvii) Back ground music speakers. |
| 106 | Supply and lay pipe ductile Iron,flanged type including specials, Class\"K-9\", 150 mm (6\") dia all as specified and as directed. |
| 107 | Supply and fix Automatic air release valve 50 mm dia suitable for domestic water with 50 mm gun metal stop valve complete all as specified and as directed. |
| 108 | Supply and fix Automatic air release valve 25 mm dia suitable for domestic water with 25 mm gun metal stop valve complete all as specified and as directed. |
| 109 | Supply and fix mild steel class \"C\" diesel pump exhaust pipe 150 mm dia with one layer of 10 mm thick ceremic fiber rope insulation and including all fitting clamp/Structural steel supports complete all as specified and as directed. |
| 110 | Supply and fix foot valve conforming to IS 4038 150 mm(6\") dia cast iron all as specified and as directed. |
| 111 | Supply and fix foot valve conforming to IS 4038 100 mm(4\") dia cast iron all as specified and as directed. |
| 112 | Supply of Analog addressable type active loop repeater (Loop power/external power) Fire terminal with inbuilt turbo isolator, Backlit LCD Display 6 x40 characters display, having controls for reset, mute,accept, silence alarms and self test, with programmable free keys and duly approved by EN54/LPCB/VDS/FMall as specified and as directed. |
| 113 | LED Emergency exit signage luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency backup upto 05 hours as specified and as directed. |
| 114 | LED Emergency escape lighting luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency backup upto 05 hours as specified and as directed. |
| 115 | Supply, installation testing and commissioning of XLPE insulated PVC sheathed FRLS galvanised steel strip or wire (Heavy duty) electric cable with copper coductor of size 1.5 sq.mm, 2 core suitable for working pressure 1100 Volts to IS:7098 and drawn into PVC conduit pipe 20 mm all as specified and directed. |
| 116 | Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized earth wire 4 mm dia. by means of bolts, nuts, check nuts and washers of galvanized ironsteel all as shown in Electrical Plate No.5 connecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1(using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work including painting of earth value & name of earth pit on top of earth pit cover with handrail will be above checked or parking tilescomplete including necessry test on completionall as specified and as directed. Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 20 mm dia watering pipe, wire mesh, 15mm dia light grade GI protection pipe for earth lead etc., complete all as specified and as directed. |
| 117 | Supply installation testing and commissioning of Addressable Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The Isolator module shall not occupy any address on loop. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be EN54. MAKE : NOTIFIER/ HONEYWELL/ EDWARDS/ SIEMENS |
| 118 | Supply installation testing and commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes. The control module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be EN 54 and FM approved. MAKE : NOTIFIER/ HONEYWELL/ EDWARDS/ SIEMENS |
| 119 | Supply installation testing and commissioning of Talk back unit. The talk back shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. The talk back shall be EN 54.MAKE : NOTIFIER/ HONEYWELL/ EDWARDS/ SIEMENS |
| 120 | Supply,installation,testing and commissioning of FireAlarm Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of +5 DB, range upto 1000m complete all as specified and as directed by the Engineer-in-Charge. EN 54 Make:- Notifier/Morley/Cooper/Honeywel or equivalentin other approved make |
| 121 | Supply and provide reinforced rubber cotton synthetic fibre circular woven jacketed fire delivery hose 63mm dia treated aginst rot/ mystex having 38 Kg/cm² working pressure bearing IS-636 type \"A\" 30 mtrs length with male and female coupling conforming to IS-903 for yard hydrant all as specified and as directed.Note :- Hoses shall be of synthetic fibre , circular woven jacketed, treated against rot, working pressure 12 Kg/cm². Burst pressure, 36 Kg/cm². Coupling shall be male and female parts, gunmetal, 63mm (2 ½\") size, heavy quality bearing conforming to IS 903 with IS mark and TAC approval |
| 122 | Supply and fix aviation obstruction LEDintegral aviation lightComprising of aluminium housing and polycarbonate enclosure with timer switchand one 10A MCB SP 230 Volts fixed in a sheet metyal enclosure.,Contactor MO9 1NO + 1NC contactor, MS Framework all as specified and as directed. |
| 123 | Supply and fix MCB distribution board SP 2 Way, single phase 240 volt rated without bus bar complete all as specified and as directed by Engr-in-charge. |
| 124 | S&F GI metal flush boxes 2 module with modular white plate all as specified and as directed. |
| 125 | Supply and fix RJ 45 NCN/NUD socket 1 module with cover plate all as specified and as directed. |
| 126 | Supply and fix TV socket 1 module with cover plate all as specified and as directed. |
| 127 | M&L Rigid non metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all Tees, bends, elbows, reducers, bell mouth, bell tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, dia of conduit 20mm ( Medium Grade) all as specified and as directed. |
| 128 | M&L Rigid non metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all Tees, bends, elbows, reducers, bell mouth, bell tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, dia of conduit 25mm (Medium Grade) all as specified and as directed. |
| 129 | Supply, installation,commissioning of Watercooler with inbuilt purifier HIMA 7 NHC (Ozonisation Technology) dispencing capacity 125ltr/hr fully stainless steel, electric driven single phase having approx storage 40 ltrs andnominal cooling 40 ltrs single, & 4 ltr Hot water phase 230 V AC power supply with all connecting accessories including PCC foundation complete all as specified and directed by engineer in charge. |
| 130 | Supply and Fixing Voltage stabliser for auto operation, single phase, naturally air cooled indoor type and designed for input variation between 170V to 280V with out voltage stablizer at 230 V with accuracy with in +/-2.5% and speed of correction 8 volts per second and of capacity 2.0KVA Capacity all as specified and as directed.Make: V-Guard or equivalent. |
| 131 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 1.5 TR with inverter compressor technology, R-32 refrigerent, anti dust filter, active carbon filter, anti microbial filter, anti viral filter and heavy duty cooling including provision of suitable bracket fixing arrangement, required copper pipe and insulation as per site requirement complete as specified and directed by Engr-in-charge. |
| 132 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 2 TR with inverter compressor technology, R-32 refrigerent, anti dust filter, active carbon filter, anti microbial filter, anti viral filter and heavy duty cooling including provision of suitable bracket fixing arrangement, required copper pipe and insulation as per site requirement complete as specified and directed by Engr-in-charge. |
| 133 | Supply and fix Voltage stablizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250V with output voltage stablized at 230Volts with accuracy of ±2.5% and of capacity 4KVA completed as specified and directed by Engr-in-Charge. |
| 134 | Supply and fix Voltage stablizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250V with output voltage stablized at 230Volts with accuracy of ±2.5% and of capacity 5 KVA.completed as specified and directed by Engr-in-Charge. |
| 135 | Supply and fix Unplasticised PVC pipes of pressure rating 10 kgf/cm2 fixed complete to walls, ceilings or in floors etc., alongwith supporting clamps/saddles completed as specified and directed by Engr -in-charge. |
| 136 | Supply,install, testing and commissioning 3 phase AC input 300 to 450V and output 3 phase phase AC output voltage 440 ±5% Volts UPS of capacity 60KVA with back up 15 to 30 minute including 1 year warrranty for UPS as per site requirement complete as specified and directed by Engr-in-charge. |
| 137 | Supply and installation of Battery 150AH 12 Volts for charging the UPS including 2 year warranty alongwith interlink connection withUPS and cables as per site requirement complete as specified and directed by Engr-in-charge. |
| 138 | Supply and installation of battery rack alongwith interlink cables for ups and battery as above including testing and commissioning as per site requirement complete as specified and directed by Engr-in-charge. |
| 139 | Supply and install Static silent Diesel Engine with accoustic enclosure, capable of delivering 160 KVA, including (AMF panel) Automatic starting on main faiilure control panelwater cooled, 415 volts (AC three phase, 4 wire system of supply) , frequency 50 Hz, at power factor 0.80 minimum. The DG set shall consists of a diesel engine coupled to a matching the alternator through flexible coupling and mounted on a common based frameand complete with control panel standardized by the manufacturer, fuel tank with mounting arrangements and with standard fuel pipes for inlet, outlet and return inlet oil arrangements, exhaust pipe, silencer and asbestos rope protection completye and shall be suitable for conditions prevailed at Kochi.(Designed capacity of Diesel engine and alternator shall be worked out by considering all derating factors prevailed at the area to be installed) The foundation of Gen Set shall be as specified by the manufacturer and shall be mounted on a suitable Channel frame structure with anti-vibration pads and including all technical features to comply with latest CPCB guidelines and comprising of followings:- |
| 140 | (i) DIESEL ENGINE (Prime Mover): Diesel Engine 1500 RPM, direct injection, six cylinders, four stroke, confirming to ISO3046/BS5514, water cooled, natuarally turbo charged, capable of giving adequate BHP to drive alternator capable of delivering 50KW(62.5 KVA) at outdoor atmospheric conditions at palluruthy,kochi (Considering all derating factors prevailed in the area). Batteries 12/24 Volts and desired ampere hours (as per manufacturers recommendations), electric battery start, complete with fly wheel and all standard fittings and fixtures as per manufacturer and including suitable panel with tacho meter, lub oil temperature, pressure gauge and frequency meters. The engine shall have self starter, dynamo, FIP, oil pump, fuel electric control panel with mechanical governor (ECPG) and Engine protection system (Shut down, High water temperature, low lub oil, oil pressure, over speed etc. , recommented capacity of fuel tank and first filling of fuel and lub oil and other consumables etc. |
| 141 | (ii) ALTERNATOR: Brushless AC alternator, 3 phase, 415 Volts, 4 wire rated for output of 50 KW (62.5 KVA) minimum power factort 0.80, 1500 RPM, IP 23 ptotection class enclosure, insulation class \"H\", salient pole, revolving field, single bearing, automatic voltage regulator coupled through flexible coupling with and match the above engine.(iii) BASE PLATE:- Made of structural steel as per manufacturers recommended design/specifications. |
| 142 | (iv) ACOUSTIC ENCLOSURE:- Sheet metal fabricated canopy type, silent enclosure, manufactured on CNC machines as per CPCB norms and shall be powder coated. The enclosure shall be designed for reducing the sound level to 75 DB at a distance of 1 mtr at 75% load under field condition and 70DB at 3 M from Gen Set when DG set is working at full load along with testing performance, labeling certification etc. as laid down in GSR No. 371(E) dt 17 May 2002.(i) Foundation/Plinth/Base shall be provided as per manufacturers recommendations, however minimum 0.50 M space should be available all around the set and height of plinth shall not be less than 0.50 M.(ii) Standard Diesel Engine tank of adequate capacity for running the Gen Set continuously for 12 hours including standard pvc pipes from tank to FIP, overflow pipe from FIP to tank.(v) MISCELLANEOUS:- Tool kit, Operation and maintenance catalogue, spare parts list, overhauling manuals, guarantee cards, test certificate of Engine and alternator etc. shall be provided as per manufacturer standard practice. |
| 143 | M & L GI pipe light grade of size 40 mm under trench, floor or wall for protection of GI strip. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail