| 1 | COMMON ITEMS APPLICABLE FOR JOB \"A\"& \"JOB \"B\":- |
| 2 | Excavation in trenches not exc 1.5 m wide and n.exc 1.5 m in depth, getting out for electric cable complete in soft/ loose soil complete all as specified & directed. |
| 3 | Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point complete all as specified & directed |
| 4 | Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers not exc 25cm thick complete all as specified & directed |
| 5 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified & directed |
| 6 | M&L for sand filling (pulverized stone dust) for sand cushioning incl spreading & levelling for protection of cable complete all as specified & directed |
| 7 | ITEMS APPLICABLE FOR JOB \"A\" |
| 8 | S&F GI tubing light grade 40 mm bore with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete all as specified & directed |
| 9 | Supply and laying or fixing or passing through pipe, 1100V grade, heavy duty cable with XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed incl taking down of old/unsv cable complete all as specified & directed for following sizes :- |
| 10 | 16 sqmm 4 core |
| 11 | 10 sq mm 2 core |
| 12 | 6 sq mm 2 core |
| 13 | Dismantling old concrete poles any size/length including connected items complete all as specified & directed. |
| 14 | S&F Steel tubular electric pole, swaged type, type 410 SP-31 (9 metre long) complete with CIbaseplate, bolts, nuts & screws complete all as specified & directed including the following jobs :-Notes:-(a) Excavation in post hole not exceeding 1.5 m wide & 2 m deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole infoundation, ramming earth around in layers not exc 25 cm thick and disposal of surplus soil to a distance not exc 50 metres.(b) M&L for Providing PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) in foundation 600mm x 600mm x 1500 mm (planting depth) for concrete encasing the pole upto GL.(c) M&L for Providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) for plinth block /Collar aboveGL, 300 mm high and 450 mm dia.(d) M&L for painting of pole externally with one coatof blackbituminouspaint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands/strip 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 m above coping level. |
| 15 | S&F in repairs PVC cable loop box size not less than 200mm x 140mm x 95mm, outdoor type, duly fitted on wall/pole with suitable clamp, nuts, bolts & washers incl to accommodate & incl one no of MCB SP 6 amp, \"B\" series, suitable aluminium with bus bar of 3 phase porcelain insulated connectors incl suitable size of lugs & gland for Incoming and outgoing cables,complete all as specified & directed. |
| 16 | S&F energy saving LED street light fitting, pressure die-cast aluminium IP 66 roadway luminaire with high power LED as light source comprising with electronic driver and all accessories pre-wired, fitting to be mounted on new/ existing GI bracket complete all as specified & directed for the following wattages :-(Note :- New GI bracket with clamp shall be measured and paid seperately in respective item) |
| 17 | 70 watts |
| 18 | 90 watt |
| 19 | 100 watt |
| 20 | 120 watt |
| 21 | S&F Energy saving LED flood light fitting, envioronmental friendly, long life, die cast aluminium IP 66 comprising with electronic driver and all accessories, pre-wired, fitting to be fitted on wall / pole with necessary fixing arrangement with nut, bolts, washers etc as required/directed at site incl connection with PVC insulated copper conductor cable 1.5 Sqmm, 3 core complete all as directed for the following wattages:- |
| 22 | 80 watt |
| 23 | 100 watt |
| 24 | 120 watt |
| 25 | 150 watt |
| 26 | 200 watt |
| 27 | S&F LED post top light, 40 watt, 230 volts, AC, outdoor type with decorative post top for 360 degree indirect light IP 65 protection, made from aluminium housing with impact and corrosion resistant with driver and lamp, fitting to be fittied & incl GI pipe of required length & size, fixed at gate/wall incl connection complete all as specified & directed |
| 28 | S&F security light mounting bracket made out of 40 mm bore light grade GI tube of suitable length, bend to shape and fixed to wall / pole by means of 02 nos. of 40 x 5 mm flat iron clamps, nuts, bolts and washers etc complete all as specified and directed |
| 29 | S&F Street light timer distribution board enclosure, 3 phase, 230/415 V,factory made, including digital time switch, contactor assembly, 65 amps, 415 V, with auxilary contact, MCB TP 63 amps, with manual/auto by pass arrangement, contactor terminals & status indicator incl all incoming and outgoing wiring & connection complete all as specified & directed.(Make - Indo Asian Model Timelite cat pt No TL065DB0 or techno-commercially equivalent in Havells/C&S/Legrand/HPL) |
| 30 | S&F 1100 volt grade, heavy duty cable PVC insulated aluminium conductor, multistranded, served with inner sheathing of PVC tape and overall PVC sheathed in service/light connections suspended complete all as specified & directed for the following:- |
| 31 | 6 Sqmm, twin core, flat or circular |
| 32 | 10 Sqmm, twin core, flat or circular |
| 33 | S&F MCB TPN 63 amps, 240 Volts, AC of breaking capacity 10 KA,\"C\" curve for existing timer and connections by using suitable copper lugs complete all as specified & directed. |
| 34 | ITEMS APPLICABLE FOR JOB \"B\" |
| 35 | S&F GI tubing light grade 50 mm bore as in cable protection fixed to poles/walls or laid intrenches/under road crossing etc complete all as specified & directed. |
| 36 | All As per Item No 20.00 here-in-before but for 80 mm bore. |
| 37 | S&F in replacement of MCCB, 4 pole, 415 Volts, 63 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. |
| 38 | S&F in replacement of MCCB, 4 pole, 415 Volts, 100 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. |
| 39 | S&F in replacement of MCCB, 4 poles 415 Volts, 160 Amps, 36 kA, 50 Hz, AC, adjustable type type in theexisting LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. |
| 40 | S&F in replacement of MCCB, 4 poles 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. |
| 41 | S&F in replacement of MCCB, 4 poles 415 Volts, 250 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. |
| 42 | M&L for servicing of ACB 800/1200A rating by disconnecting and taking out the breaker after taking power shut down of the respective panel and overhauling/ servicingthe ACB by opening all parts and cleaning of electrical contacts with CTC/rust remover,lubricating electrical moving parts with petroleum jelly and mechanical moving parts withgrease & applying Becktrol red solution to the surface of the bus bars and spouts, applying Monoplast compound at the bus bar joints after tightening of joints and replacing defective spare partslike springs/ bolts/ nuts/ washers etc, including testing, calibrating , refixing the circuit breaker and making it functional complete all as directed and specified |
| 43 | M&L for Repair/Reconditiong of exisitng earth pit by removing damaged Earth PCC chambers and excavate pit soil upto 25% of earth plate/electrode and adding alternate layers of charcoal, mixture of salt and copper sulphate up to 15cm above the earth plate/electrode and moist the mixture using water,cleaning/replacing of funnel with wire mesh whereever necessary , testing the earthing after reconditioning and earth resistance value must be within 1.5 Ohms, making good to distrubed surface and complete all as specified and directed at site.Note: Rate quoted shall be inclusive of excavation, returning filling and connected items. |
| 44 | S&F in replacement of laying earth continuity conductor GI Strip 25 x 4mmfixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc complete all as specified and directed. |
| 45 | S&F in repair/replacementof damaged earth chamber withpre moulded PCC earth chamber withcast iron cover of size 300mm x300mm x 50mmincludingprovision of funnel, wire mesh necessary excavation and earth work in any type of soil including paninting , marking of earth values with date complete all as specified and directed |
| 46 | M&L for Testing of earthing resistance of existing earthing using calibrated 3/4 wire digital Earth resistance tester and recording the earth resistance value in register obtaining the signature of user and MES excecutive after varification complete all as specified and directed. Note : Contractor has to provide digital earth resistance tester and should be available all the time during the contract period. |
| 47 | S&F in replacement of Saftey protection relay 415 VAC, 3 Ph 4 Wire, 2 C/O with adjustable under voltage,over voltage, on delay,Neutral fail protection for LT Panel complete all as specified and directed.Make : L&T Cat No MAC04 D0100 or techno-commercially equivalent in ABB/Siemens |
| 48 | S&F in replacment of Power contactor , 3/4 pole, 415 Volts, 265 Amps, 50 Hz, AC fixed in the existing ATSLT panel board including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. |
| 49 | Taking down old U/S UG cable of any size complete all as specified and as directed. |
| 50 | S&F LT UG cable 4 core x 16 sq mm 1100 Volts grade XLPE insulated , flat steel armoured, heavy duty with aluminium conductor laid in trenches or fixed to walls/ poles or passing through pipes with and including,cable glandlugs/ thimbles/ ferrules including connecting, testing and commissioning completeincluding taking down existing LT UG cable of any sizeat site all as specified and as directed.Notes:(a)Excavation, sand cushioning ,brick protection and connected worketc shall be measured and paid separately under relevant item of schedule (b)Rate quoted deemed to include for cutting and removing of defective jointswhere required as directed. |
| 51 | All as per Item No 35.00 here-in-before but for 3.5core x25 Sqmm |
| 52 | All as per Item No 35.00 here-in-before but for 3.5core x35 Sqmm |
| 53 | All as per Item No 35.00 here-in-before but for 3.5core x50 Sqmm |
| 54 | All as per Item No 35.00 here-in-before but for 3.5core x70 Sqmm |
| 55 | All as per Item No 35.00 here-in-before but for 3.5core x95 Sqmm |
| 56 | All as per Item No 35.00 here-in-before but for 3.5core x120 Sqmm |
| 57 | Supply and laying in replacementof 1100 volts grade heavy duty cable with PVC insulated aluminium stranded conductor served with an inner sheathing of PVC tape unarmoured with galvanised steel tape and overall PVC sheathed 10 sq.mm , 2 core nominal cross section in service connections. |
| 58 | S&F in replacment of ON LOAD change over switch with sheet metal enclosure 415V , 4 pole of capacity 250 Amps including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.. |
| 59 | S&F in replacment of ON LOAD change over switch with sheet metal enclosure, 415V , 4 pole of capacity 315/320 Amps including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. |
| 60 | S&F in replacement of sheet metal enclosure made out of 2mm thick CRCA sheet duly powder coated suitable for fixing/mounting MCCB of 160A Amps 4 pole duly fixed on wall with all fixing arrangements complete all as specified and as directed. |
| 61 | S&F in replacement of sheet metal enclosure made out of 2mm thick CRCA sheet duly powder coated suitable for fixing/mounting MCCB of 250A Amps 4 pole duly fixed on wall with all fixing arrangements complete all as specified and as directed. |
| 62 | S&F in replacement of power contactor AC coil 240V ,50Hz suitable for MNX 70 Contactor complete all as specified and as directed. |
| 63 | S&F in replacement of power contactor AC coil 240V ,50Hz suitable for MNX110/95/140Contactor complete all as specified and as directed. |
| 64 | S&F in replacement of power contactor AC coil 240V ,50Hz suitable for MNX300/MNX400Contactor complete all as specified and as directed. |
| 65 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 110 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. |
| 66 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip of size 32 x 6 mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in elecrticalplate No 3 of SSR pt I, connected to DB/earthing test point includingPCC chamber , RCC cover 50mm thick with 8 mm dia bars, protection pipe, funnel etc including excavation, earth work, disposal of surplus soiland earth strip protection pipe of GI 40 mmbore light grade upto 7.5 metre including testing on completion all as specified and as directed. |
| 67 | M&L forLoose filling with aggregates of gauge 40 mm filling in Panel surrounding upto 1 to 3 mtr as per ground availability of area, cleaning the area, making level, and filling the aggregate complete all as specified and as directed. |