| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | (Group B) |
| 3 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 6 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 8 | 3 x 1.5 sq. mm |
| 9 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 2 Pair |
| 11 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 12 | 20 mm |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 14 | 5/6 amps switch |
| 15 | 3 pin 5/6 amp socket outlet |
| 16 | 15/16 amps switch |
| 17 | 5 pin 15/16 amp socket outlet |
| 18 | Telephone socket outlet |
| 19 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 20 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 21 | 1 or 2 Module (75mmX75mm) |
| 22 | 6 Module (200mmX75mm) |
| 23 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 24 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 25 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 26 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 27 | 12 way, Double door |
| 28 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 29 | Single pole |
| 30 | Double pole |
| 31 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 32 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 33 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 34 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 35 | Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 36 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 37 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 38 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 39 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 40 | Providing installation testing and commissioning of ceiling fans decorative type of 1200 mm sweep, capacitor type with double ball bearing complete with capacitor, 300 mm down rod, canopies,with 1.5 sqmm FR PVC indulsted, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required suitable for single phase, AC 230 Volt, 50Hz supply.(Usha/Bajaj/Havells/Orient/CG or its Equivalent) |
| 41 | Supplying, installation , testing and commissioning of energy efficient pre wireLED tubelightof 20 W LED tube batten, decorative slim liner LED batten,polycarbonate housing & integrated electronic driver. ceiling surface mounted/suspention type, completed with all accessories inc etc. as required.(Make- Havells/Crompton/Bajaj/Philipsor its equivalent |
| 42 | PITC of 1.5 Ton A.C , wall split AC coolonghaving 230 V/ 50 Hz rated, BEE Star rating - 5, Coil Material (Condenser) - Copper, Cooling Rating 4500 Kcal/hr for 1.5 TR, Maximum Set Temperature 50 degree Celsius, 4-way air swing, minium length of copper pipe is 3 metres and suitable connecting electrical cable for installation and commiossioning - inclusive in the scope of supply (make like : Voltas/LG/Hitachi/Godrej or its equivalent) |
| 43 | PITCof4 KVA Automatic Servo voltage stabilizer having copper winding andsuitable for single phase sine wave(120V-280V) and output voltage is 230 Volt(make like : V-Gaurd/Servokon/Microtek or its equivalent) |
| 44 | Supplying and Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade (heavy duty )armoured UG electric cable with aluminium conductor of size 3.5 x 35 sq.mm. direct in ground including excavation andrefilling the trench but excluding sand cushioning & protective covering.(make Havells / KEI / Finolex / Gloster or its equivalent) |
| 45 | Supplying and Laying of one no PVC insulated/PVC sheathed XLPE power cable ,1.1 KV grade (heavy duty), armoured UG electric cable with aluminium conductor ofsize 3.5 x 35 sqmmin the existing masonry/open duct/in exisiting Conduit as required (make Havells / KEI / Finolex / Gloster or its equivalent) |
| 46 | SITC of control Paneldouble door made out of 16 SWG CRCA sheet duly primed with synthetic enamel gray paint of size800 mm X 700 mm X 350 mm deep having100 A, 04 nos insulated aluminium bus bars, R-Y-B LED indicators, angle iron frame of 700 mm X 350 mm with 300 mm long legs made out of 40 mm x 40 mm x 5 mm thick angle , grouting the same in suitable cement concrete foundation, arrangement for incoming & outgoing cables, P&F of internal connection with suitable size of cu wires, cable termination, earthing, locking, interconnectionetccomplete as per CPRI approved specifications and to accommodate the following accessories etc as required as per direction of Engineer-In-Charge. (i) 100 Amp Switch disconnector fuse unit (SDF) - 01 No (ii) 63 Amp Four Pole (FP) 25 KA MCCB. - 02 Nos, (ii) 32 Amp Four Pole (FP) 25 KA MCCB. - 02 Nos |
| 47 | Dismantling of existing fitting fixture and accessories, switch board, distribution board etc in building including making good the damange etc complete as required |
| 48 | Add GST 18 % on DSR 2022 item MF factor @ 0.0633 on DSR items |
| 49 | Add Labour Cess @1% |