| 1 | Surface excavation not exc. 30 cm deep and averaging 15 deep and getting out in soft/loose soil. Complete all as specified and directed. |
| 2 | Excavating in trenches, not exc 1.5 m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exc 10 sqm on plan and n exc 1.5 m in depth and getting out. Complete all as specified and directed. |
| 3 | M&L for Cement concrete (1:4:8) type D2 using 40mm graded stone aggregate asin foundations, filling and mass-concrete all as specified and directed. |
| 4 | Removing excavated material not exc. 50 m and depositing where directed at a level not exc. 1.5 m above the starting point. Complete all as specified and directed. |
| 5 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. Complete all as specified and directed. |
| 6 | M&L for brick work with sub class \"B\" brick (using old size bricks)straight or curved on plain exc 6m mean radious built in CM (1:6) complete all as specified and directed. |
| 7 | M&L for PCC (1:2:4) type B1 using 20mm graded stone aggregate as in coping including necessaryform work complete all as specified and directed. |
| 8 | M&L for rendering 15 mm thick in CM (1:4) on faces of brick or concrete surfaces and finishing fair and even complete all as specified and directed. |
| 9 | M&L for finishing wall with Acrylic smooth exterior paint of required shade on new surfaces (Two or more coats applied @ 3.28 ltr/10Sqm) over and including priming one coat of exterior primer applied @ 2.20 kg/10Sqm complete all as specified and directed. |
| 10 | S&F mild steel pipe frame work fixed to wall or any other section Fe 410-W (Gde-E 250) complete all as specified and directed. |
| 11 | M&L for preparation of new steel surface of any description exceeding 10cm width or girth and applying two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and direced. |
| 12 | Material & labour for Chemical earthingcomplete with copper plate electrode of size 900mm x 600mm x5mm burried directly in ground vertically to a depth not less than 4.70 mtr below normal ground level (with top edge ofearth plate not less than 3.60 mtrs below ground level ) of earth pit size 1200mm x 600mm x4700 mmconnected to copper strip of size 32 mm x 6 mm as main earthing lead by means of brass nut and bolt / brazing at all joints all as directed and connected to earth test pointall as specified and testing on completion with and including necessary excavation and earth work in any type of soil ,GI pipe medium grade 40 mm bore for protection of copper strip from earth electrode to earth test point with adequate quality of charcoal dust, common salt,magnesium sulphate,copper sulphate and bentonite powder solution in alternate layers of 150 mm thick layers all around the plate ,and precast PCC chamber/pit of size 300mm x 300mm x 300mm on 900mm x 600mm x 100mm of the PCC (1:4:8) using 40 mm graded crushed stone aggregate with RCC (1:2:4) type B1 (using 20 mm graded crushed stone aggregate) cover of size 400mm x400mm x50 mmreinforced with 8 mm dia TMT bars @75mm C/C both ways with mild steel flushed type handle 12 mm dia, PGI funnel with wire mesh, 25 mm dia GI pipe light grade for watering all as specified and shown of Note No 3 of SSR Part - I (2009). Complete all as specified and directed. Note- (a) Cost of copper strip and GI protection pipe up to distance 7.5 mtr shall be included in quotated rate of this items.(b) On testing after completion of job , If desird earth resistance e.i less than 2 ohm is not found the earthing shall be redone at no extra cost to govt. |
| 13 | M&L for earthing complete with copper plate electrode of size600x 600x 3.15 mm thick burried directly in ground vertically at a depth not less than 3.25 meter deep below normal ground level with top edge of the plate not lessthan2.50 metre below normal groundlevel surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using copper strip 20mm x3 mm as main earthing lead by means of brass nut and bolt / brazing at all joints and protected by light grade 40 mm dia GI pipe connected, and GI pipe light grade 25 mm bore for watering and including funnel, wire mesh, and precastPCC chamber/pit of size 300mm x 300mm x 300mm on 600mm x 600mm x100mm base of PCC (1:4:8) using 40 mm graded crushed stone aggregate, RCC pit cover with PCC (1: 2: 4) type C2 using 40mm graded stone aggregate cover of size400mm x400mm x50 mmreinforced with 8 mm dia TMT bars @75mm C/C both ways with mild steel flushed type handle 12 mm dia including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 3 of SSR Part I (2009), complete all as specified and directed.Note- (a)Cost of copper strip and GI protection pipe up to distance 7.5 mtr shall be included in quotated rate of this items.(b) On testing after completion of job , If desird earth resistancei.e less than 3 ohm is not found the earthing shall be redone at no extra cost to govt. |
| 14 | M&L for earthing complete with galvanized steel earth plate electrode of size600mm x 600mm x 6mm thick burried directly in ground vertically at a depth not less than 3.25 metredeep below normal ground level with top edge of the plate not lessthan 2.5 metre below normal groundlevel surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanized iron earth lead wire GI strip 32mm x 6mm mm as main earthing lead by means of brazing at all joints and protected by light grade 40 mm dia GI pipe connected to test point and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh,and PCC chamber/pit of size 300mm x 300mm x 300mm on 600mm x 600mm x 100mm base of PCC (1:4:8) using 40 mm graded crushed stone aggregate, precast RCC pit cover with PCC (1: 2: 4) type C2 using 40mm graded stone aggregate cover of size400mm x400mm x50 mmreinforced with 8 mm dia TMT bars @75mm C/C both ways with mild steel flushed type handle 12 mm dia including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 3 of SSR Part I (2009), completed all as specified and directed.Note:- (a)Cost of GI strip and GI protection pipe up to distance 7.5 mtr shall be included in quotated rate of this items.(b) On testing after completion of job , If desird earth resistance(less than 5 ohm) is not found the earthing shall be redone at no extra cost to govt. |
| 15 | M&L forboring underground of 100 mm dia upto 30 mtr depth below ground level in any kind of soil strata for insertion of pipe electrode 30 mtr length and coper strips etc. for bore earthingcomplete all as specified and directed. |
| 16 | M& L for loweringbore Galvanised iron tubing, 50mm bore, light grade with all fittingsaccessories for protection of earth stripscomplete all as specified and directed. |
| 17 | M&L forcopper strip of size 20mm x 3mm complete with saddles and fixing screws for fitting the strip for earth continuty conductor up to test points.complete all as specified and directed. |
| 18 | M&L for Galvanised iron strip of size 32mm x 6mm with saddles and fixing screws on porcelain insulators for roof conductors and down conductors above ground levelcomplete all as specified and directed. |
| 19 | M&L for Material and labour Aluminium strip of size 25mm x 3.15 mm with saddles and fixing screws Etc. for roof conductor and down conductor above ground level. complete all as specified and directed. |
| 20 | Supply install and testing of isolation transformer 2.0 kva ,240 Volts AC ,50 Hz 1:1 ratio of input and output voltage copper wound air cooled with MS sheet metal enclosure duly painted with 3 core copper conductor PVC insulated cable with plug top to maintain E_N voltage less than 2 volts .Make- Blue Bird/Sai electricals/Volino . |
| 21 | M& L for Earthing pit chamber ( pit ) of size 300mm x 300mm x 300mm (internal dimension) constructed with PCC (1:3:6) type C-1 , using 20 mm graded stone aggreegate RCC cover 40 mm thick in RCC (1:2:4) type B-1 , using 20 mm stone agreegate reinforced with 8 mm dia MS bars @ 75 mm C/C both ways including Pit/Chamber shall be provided on PCC base (1:4:8) of size 800mm x 800mm x 100mm thick using 40 mm stone agreegate including required necessary excavation and dismantling of broken pits complete all as specified and directed. |
| 22 | M&L for earthing pit indicator made of CRCA sheet for display of EP No & ER Value in ohm of size 300mm x 300mm x 3 mm of height 600mm.The MS angle iron 300mm x 300mm x 6mm will having planting depth of 300 mm below ground level and 300mm above ground level and should be embeded in PCC (1:3:6) type C1 using 20mm graded stone aggregate including necessary earth work. The MS angle iron with display shall be painted with synthetic enamelled paint over one coat of red oxide primer with writing of EP No ER Value complete all as specified and directed. |
| 23 | M&L for laying of single run of single core PVC insulated unsheathed multi stranded copper conductor cable of size 25 Sqmm 1100 volts gradeas earthcontinuity conductor drawn through into and including rigid non metallic PVC conduit of size not less than 25mm dia onroof/wall/ceiling includingmaking good the disturbed surfaces ofwall etc includingtaking out old unserviceable burnt/damaged wire from its existing position complete all as specified and directed.(Note : Non metallic PVC conduit rate included in the rate quoted). Make- Plaza/Finolex/ Palycab/ Havells. |
| 24 | S&F test point terminal block made of gun metal or phosphorus bronze size 75mm x 75mm x 25mm drilled and screwed including 3 nos 8 mm dia 25 mm long hexagonal head screw complete all as specified and directed. |
| 25 | Supply and fixing new air termination,multi pointed aluminium rod 12mm dia and 300 mm long connecting with lightening conductor system complete all as specified and directed. |
| 26 | Taking out existing strip and demolation of earth pit chamber including protection pipe of any size complete all as specified and directed. |
| 27 | Taking down of existing earth strip size 20mm x3 mm of copper complete all as specified and directed. |
| 28 | Taking down of existing earth strip of size 32mm x 6mmGI. complete all as specified and directed. |
| 29 | Taking down of existing earth strip size of 25 X 3.15 mm Alluminium. complete all as specified and directed. |
| 30 | Taking down ofold air termination rod of any sizes. complete all as specified and directed. |
| 31 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, bell, bell push, light fitting etc for taking credit and making good disturbed surfaces of walls, floors,etc.as directed. |
| 32 | M & L for point wiring with two single core PVC insulated & PVC unsheathed FRLS-H multistranded copper conductor cable of size 1.5 sqmm 1100 volt gradein non metallic rigid PVC concelled conduit medium grade 25 mm dia with all accessories mounting all the surface of wall/ceiling/roof/etc with suitable size of module metal flush boxes and including modular front coverplate & back plate for mounting modular type switches /socket/fan/ regulator etcincluding provision of one single corePVC insulated and unsheathed multi stranded copper cable of size 1.5 sqmm 1100 volt grade as earth continuty conductor connected to common earth dollyswitch board complete for following-Make of Cable- Plaza/Finolex/Havells/Polycab /RR CableMake of PVC conduit :- AKG/ Plaza/ Jindal / FinolexOne light point controlled by one switch SP 5 Amps ,240 V |
| 33 | One fan point controlled by one switch SP 5 Amps ,240 V |
| 34 | Ditto all as per item No 21 abpve but for One 3 pin 5 amps switch socket outlet point on independent board |
| 35 | Ditto all as per item No 21 abpve but for One 3 pin 5 amps socket point on same board |
| 36 | Ditto as per item No 21 above butfor one light point controlled by two 2 way switches. |
| 37 | Ditto as per Item No 21 above but for One bell/ buzzer pointcontrolled by one bell push |
| 38 | Ditto as per the item no 21 herein before but with 2.5 sqmm conductor for5 pin 15 Amps switch socket outlet. |
| 39 | M & L for point wiring with two single core PVC insulated & PVC unsheathed FRLS-H multistranded copper conductor cable of size 1.5 sqmm 1100 volt gradedrawn into and including non metallic rigid PVC Conduit/Casing Caping medium grade 25 mm dia with all accessories mounting all the surface of wall/ceiling/roof/etc with suitable size of module metal flush boxes and including modular front coverplate & back plate for mounting modular type switches /socket/fan/ regulator etcincluding provision of one single corePVC insulated and unsheathed multi stranded copper cable of size 1.5 sqmm 1100 volt grade as earth continuty conductor connected to common earth dollyswitch board complete for following-Make of Cable- Plaza/Finolex/Havells/Polycab / RR Cable.Make of PVC conduit :- AKG/ Plaza/ Jindal / FinolexOne light point controlled by one switch SP 5 Amps ,240 V |
| 40 | One fan point controlled by one switch SP 5 Amps ,240 V |
| 41 | One 3 pin 5 amps switch socket outlet point on independent board |
| 42 | One 3 pin 5 amps socket point on same board |
| 43 | Ditto as per Item No 23 above but for One bell/ buzzer pointcontrolled by one bell push |
| 44 | Ditto as per the item no 23 herein before but with 2.5 sqmm conductor for5 pin 15 Amps switch socket outlet. |
| 45 | M&L for point wiring complete for one light point or one fan pointcontrolled by one, one way 5 Amp switch with PVC (FRLS) insulated unsheathed multistranded copper conductor of size 1.50 sqmm nominal cross sectional area single core drawn into existing conduit, including pressed steel concealed terminal switch boxes not less than 1.6mm thick of reqd size factory made duly painted inside and outside with one coat red oxide primer, 3mm thick plastic laminated bakelite sheet top cover (ISI Marked) fitted with chromium plated brass screws & washers complete including 1.50 sqmm nominal cross sectional area PVC(FRLS) insulated unsheathed multistranded copper conductor green as earth wire connected to earth dolly with all accessories complete all as specified and directed. Make of Cable- Plaza/Finolex/Havells/Polycab / RR Cable.One light point controlled by one switch SP 5 Amps ,240 V |
| 46 | One fan point controlled by one switch SP 5 Amps ,240 V |
| 47 | One 3 pin 5 amps switch socket outlet point on independent board |
| 48 | One 3 pin 5 amps socket point on same board |
| 49 | Ditto as per Item No 33 above but for One bell/ buzzer pointcontrolled by one bell push |
| 50 | Ditto as per the item no 33 herein before but with 2.5 sqmm conductor for5 pin 15 Amps switch socket outlet. |
| 51 | S&Fmodular switches 1 way 6A,1 module.complete all as specified and as directed.Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 52 | S&F modular switches 1 way 16A,1 module,complete all as specified and as directed.Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 53 | S&F modular 6 A sockets-5 pin2 module complete.complete all as specified and as directed.Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 54 | S&F modular 6A/16A sockets-3/5 pin combine 2 module.complete all as specified and as directed.Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 55 | S&F modular bell push single pole one way 6/10 Amp, 240 volt,1 module, flush type as directed.Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 56 | S&F modular 5 Amps 2 way switchMake - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 57 | Supply and fix modular type blanking plates, one moudle complete all as specified and directed. Make - Goldmedal/cabtree(havells)/ABB / Legrand/ L&T. |
| 58 | Supply & fix modular fan regulator 120/100 W, 2 Module for ceiling fan fixed, in board and connecting as directed, after dismantling and removing unserviceable regulator.Make - Goldmedal/cabtree(Havells)/ABB / Legrand/ L&T. |
| 59 | S&F ceiling rose surface bakelitethree terminal complete all as specified and directed. |
| 60 | S&F call bell AC single pole 240 volt ding dongtype.Make- Anchor / Havells / Legrand/ L&T. |
| 61 | S&F batten type holder insulated body with back plate suitable for batten fittings complete all as specified and directed. |
| 62 | Supply and fixing wall/surface mounting luminaires (Mirror Light) integrated LED Batten( 2 feet) 10/12 W, 6500 K, 230V , minimum 120 lumens/watt,with extruded aluminium housing & integrated electronic driver completeincluding Electrical connection with PVC three core copper flexible wire & all necessary fixing arrngementscomplete all as per specified and directed .Make- Phillips /Bajaj/Havells/L&T. |
| 63 | Supply and Fixing wall/surface mountingluminaires integrated LED Batten 20/22 W, 6500/4000 K,100 lumens/watt , 230V with extruded Aluminium housing4 feet long with frosted PMMA/PC diffuser & integrated electronic driver, 25k burning hours ,2.5 KV surge protectioncomplete including Electrical connection with PVC three core copper flexible wire & all necessary fixing arrangementscomplete all as per specified and directed. Make- Phillips / Bajaj/ Havells/ L&T/ Crompton |
| 64 | S&F in repairs ofsurface type round/Square LED 10/12W downlighter 6500K 2.5 KV inbuit surg protectionminimum 110 lumens/watt, 50k burning hours aliminium PDC complete all as per specified and directed.Make- Phillips / Bajaj/ Havells/ L&T/ Crompton. |
| 65 | Supply and fixing in repair Material glass led tube ,voltage range 220-240v-50hz ,cct 6500k,lumen ,wattage 20/22W surge 2.5kv ,CRI 70 POWER FACTOR >_0.9 ,BURING HOURS 25K HOURS110 L/W ,6000 Kwith high efficency, with neccessary electrical connection incl disconnection old elecronic ballast if anycomplete all as directed.Make- Phillips / Bajaj/ Havells/ L&T/ Crompton. |
| 66 | S & F in repairs integrated LED type Post top lantern with high power 25/30 W LED as light source, energy saving, environmental friendly, long life asethetically designed with symmetrical light distribution,spun aluminium landscape lumainaire including LED driver complete and incl neceesary electrical connection all as directed .Make-Phillips / Bajaj/ Havells/ L&T/ Crompton. |
| 67 | S & F in repairs integrated LED type Bollard , 10/12 W LED as light source, IP 65, energy saving, environmental friendly, long life asethetically designed with symmetrical light distribution incl LED driver with base plate and pcc and earth work for grouting the lightcomplete and incl neceesary electrical connection complete all as specified and directed . Make- Phillips / Bajaj/ Havells/ L&T/ Crompton. |
| 68 | S&Fsquare recessed / surface/suspendedmounting LED ceiling light with extruded aluminium housing and milky diffuser of 36 W 2\"X 2\"panel complete with LED driver 240 V ,50 Hz,3600 lumen 6500 k complete all as specified & approved by EIC . Make- Phillips / Bajaj/ Havells/ L&T/ Crompton. |
| 69 | S&F in replacemet for submain wiring with two run of single core PVC insulated unsheathed multi stranded copper conductor cable of size 4 Sqmm 1100 volts grade and onerun of PVCinsulated unsheathed multi standed copper conductorcable of size 4Sqmm 1100 volts grade as earthcontinuity conductor drawn through in and includingrigid non metallic PVC concealed / surface conduit of size not less than 25mm dia onroof/wall/ceiling includingmaking good the disturbed surfaces ofwall etc. Complete all as specified and directed.(Note : Two run of single core cable and one run of earth wire will be measured as one lengthandconduit and its accessoriesis deemed to be included in the quoted unit rate for this office).Make- Polycab/Havells/RR kables/plaza/ Finolex. Make of PVC conduit :- AKG/ Plaza/ Jindal / Finolex. |
| 70 | S&F Submain wiring with two single core PVCinsulated FRLSH multistrand copper conductor cable of size 10Sq mmdrawn into and including non metallic heavy duty rigid concealedPVCcondute not less than 25mm size ISI marked ivory colour (Pressfit or similar brand ) with allfittings / accessories and 10Sq mm FRLS multistrand copper conductorcable as continuous earth wire complete. (Note :- for submain wiring: Two run of single core cable and one run of earth wire will be measured as one lengthandconduit and its accessoriesis deemed to be included in the unit rate quoted for this items.)Make- Polycab/Havells/RR kables/plaza/ Finolex. Make of PVC conduit :- AKG/ Plaza/ Jindal / Finolex |
| 71 | Takingdown old unserviceablemainswitches/DB’s up to 100 Amps capacity fixed in wall and making good of all disturbed surfaces as perexisting. Complete all as specified and directd. |
| 72 | S&F sheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 4 way, AC,240 volt with 200 Amp bus bar rating Complete all as specified and directd.Make :- Havells / Legrand /Seimens/ABB/ L&T. |
| 73 | S&F sheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 8 way, AC,240 volt with 200 amp bus bar ratingcomplete all as directedMake :- Havells / Legrand /Seimens/ABB/L&T. |
| 74 | S&Fsheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 12 way, AC,240 volt with 200 Amp bus bar rating complete all as directed .Make :- Havells / Legrand /Seimens/ ABB/L&T. |
| 75 | S&Fsheet metal enclosure double door (MCB DB) three phase and neutral with 200 Amps rated bus bar TPN,4 wayverticall type, with provision of MCB incommer, AC, 415 Voltcomplete all as specified & directed.Make :- Havells / Legrand /Seimens/ABB/ L&T. |
| 76 | S&Fsheet metal enclosure double door (MCCB DB) three phase and neutral with 200 Amps rated bus bar VTPN,4 way vertical type, with provision of MCCB incommer, AC, 415 Voltcomplete all as specified & directed.Make :- Havells / Legrand /Seimens/ABB /L&T. |
| 77 | S&F MCBsingle pole, 6 to 32Amps, 240 Volts 50 HZ, 10 KA breaking capacity complete all as directed.Make :- Havells / Legrand /Seimens/ABB / L&T. |
| 78 | S&F MCB DP 40 to 63 Amps 240 Volts, 50 Hz, 10 KA breaking capacity complete all as directed.Make :- Havells / Legrand /Seimens/ABB / L&T. |
| 79 | S&F MCB Four Pole 40 to 63 Amps 415 Volts, 50 Hz, 10 KA breaking capacity complete all as directed.Make :- Havells / Legrand /Seimens/ABB /L&T. |
| 80 | S&F MCCB 4 pole 100 / 125 Amp 415 volts 50 HZ25 KA breakingcapacity complete all as directed.Make :- Havells / Legrand /Seimens/ABB / L&T. |