| 1 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour |
| 2 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
| 3 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
| 4 | MCCB 4pole, 100Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -06 No (Outgoing) |
| 5 | Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 6 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 7 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 8 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour |
| 9 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
| 10 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
| 11 | MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -06 No (Outgoing) |
| 12 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 13 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 14 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 15 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 250 Amps rating for phase and neutral 4 strips with colour |
| 16 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
| 17 | MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
| 18 | MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 10KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -06 No (Outgoing) |
| 19 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -03 No (Outgoing) |
| 20 | Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 21 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 22 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 23 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 630 Amps rating for phase and neutral 4 strips with colour |
| 24 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
| 25 | MCCB 4pole, 630 Amps, with adjustable thermal and magnetic settings, 25 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
| 26 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -04 No (Outgoing) |
| 27 | Digital Ammeter 0 to 800 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 28 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 29 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 30 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour |
| 31 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
| 32 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
| 33 | MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -07 No (Outgoing) |
| 34 | Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 35 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 36 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 37 | Digital Voltmeter0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 38 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 39 | S&F in repairs Weather proof outdoor bus bar chamber made out of 3mm thick MS sheet comprising MCCB 4pole 125 Amps 25KA capacity thernal and magnetic setting asincommer and4 Nosaluminium strips each of 200 Amps as outgoing , 90cm long duly insulated mounted on insulatorswith 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), andconnections with suitable size of aluminium thimbles, nuts, bolts & washers, cable glands at entry and outlet points and excavation, earth work, returning filling in and removal of surplus soils including taking out old unserviceable bus bar chamber complete all as specified and directed. |
| 40 | Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 8 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 100 KVAR (2No X 5 KVAR+ 3No X 10 KVAR+ 3 x 20 KVAR) including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating100 KVAR 2NoX5 KVAR+3No X 10 KVAR+ 3X20 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alaram if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacurer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/Hager/ Legrand/ ABB/ Havells.(f) MCCB 200 Amps4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/Hager/ Legrand/ ABB/ Havells. |
| 41 | Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 7 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR)including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alaram if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacurer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS.(f) MCCB 125 Amps4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS. |
| 42 | Repair / maintenance, exluding major spares but including regular maintenance of the Automatic Power factor correction control panel capacity 50 to 125 KVAR and 3 to 8 stages installed at various locationsat AGE E/M No Iincluding carrying out complete maintenance / repairsas requiredof all the sub systems viz, based control panels, feeder pillar,APFC relay,Power capacitor bank, Power contactors, Controlwiring, MonitoringCT, MCBs / MCCBsfor isolation (withall the accessories) anybreakdown maintenanceand replacement of unserviceable parts / newparts if any,project completionand troubleshooting responsibility alsolies with the contractor including following provisions complete all as specified and directed.Notes :-(i)Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring,small parts such as Pushbuttons, lugs, any auxilary contacts, auto selector switch etc and necessary servicing repair by expert technician and register will be maintained for the same.(ii)The scope of workincludes the labour charges required for removing, repairing , refixing, carrying outelectrical termination capacitor bank etc complete(iii) Major Spare parts will be measured as supply only under respective item. |
| 43 | Supply only powerfactor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old existing capacitor complete all as specified and directed. |
| 44 | All as per item No 11 above but 10 KVAR Capactor. |
| 45 | All as per item No 11 here-in-before but 15 KVAR Capactor. |
| 46 | All as per item No 11 here-in-before but 20 KVAR Capactor. |
| 47 | All as per item No 11 here-in-before but 25 KVAR Capactor.Make for item No 11 to 15- L&T or equivalent make in Schneider/HPL |
| 48 | S&F in repairs APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens |
| 49 | S&F in repairs APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens |
| 50 | S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 51 | S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 52 | S&F in repairs, 4pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 53 | S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 54 | S&F in repairs, 4pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 55 | S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 56 | S&F in repairs, 4pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 57 | S&F in repairs, 4pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 58 | S&F in repairs, 4pole 630Amp MCCB, 50KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 59 | Supply and fix in repaire, 3 phase street light control DB Box internally prewired comprising of Aestronomical timer swich, power contactor, and MCCBfor maximum load of 65 Amps complete all as specified and directed by Engh in charge.Make IndoAsian cat no TL065ASO with astronomical switch TDA45163 OR equivalant in L&T/Scheinde |
| 60 | M&L in repairs, Earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to GI strip 25x4mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed by Eng-in-charge. |
| 61 | Note 1: The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, 50mm thick RCC 1:2:4 type B-1 using 20mm graded stone aggregate cover slab reinforced with 6 Nos of 8mm dia TMT bars both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe medium grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub-heading earthing, specified on Sl Page No. 422 of SSR Part-II. |