| 1 | Repair/ maint of street/ flood light fitting/ gate light LED fittings any type/ watt on poles/ walls/ high mast, making good all loose electric connections of street light/ junction box and making serviceable complete all as specified and directed. Note : 1. Accessories found unserviceable, if any shall be replaced & paid under respective items of BOQ.2.Contractor\"s supervisor or contractor shall collect the complaint slips from power house as directed.3.All the T&P and equiipments to facilitate to execute the workshall be provided by the contractor without any extra cost.4. Complaints of street/flood lights shall be done within two days and complaint slip shall be deposited to JE E/M immediate after completion the complaint. |
| 2 | Disconnecting, dismantling and taking down carefully unserviceable security /flood light /gate light any type /watt alongwith all connected accessories from pole or wall or high mast for repair, checking all wiring and serviceability of all components and deposited to MES store yard complete all as directed. |
| 3 | Fixing only security/ flood light/ gate light any type/watt (retrieved under item No 1 ) on pole or wall or high mast after checking all wiring and serviceability of all components alongwith all connected accessories and repair, complete all as specified and directed.Note: Componants shall be replaced and measured separately under respective item of BOQ. |
| 4 | Supply and fix in replacement ofbracket (as per sample) made out GI tubing 32mm dia not less than 1m longmedium grade suitable for LED light street light, bend to shape by welding including fixing arrangements i.e suitable clamps, nut, bolt and washers complete all as specified and directed. |
| 5 | Disconnecting, dismantling and taking out old steel tubular/PCC pole any size/ length and making good all disturbed surface to match with existing specifications complete all as specified and directed. |
| 6 | Supply, erection and installation of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long)duly painted with two coats of black bituminous paint through out, internally and externally up to planning depth and painting remaining portion of pole with two coats of aluminium paint to the entire exposed surfaces over one coat of red oxide primer, making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip with synthetic enamel paint and marking pole number with black paint (as per sample) complete all as specified and directed.Note : Excavation, earth work, PCC work shall be measured and paid separately under respective items of BOQ. |
| 7 | Supply only electronic driver suitable for LED street/ flood lights fittings upto 70 watt of any type/make (as per sample) complete all as specified and directed. |
| 8 | All as per item 7 butfor LED street/ flood lights fittings 71 to 120 watt. |
| 9 | All as per item 7 butfor LED street/ flood lights fittings 150 to 200 watt. |
| 10 | Supply only surge protection device 10 KV for LED street/flood lights fitting of any type/watt/make (as per sample) complete all as specified and directed. |
| 11 | Disconnecting, dismantling and taking down carefully street light junction box any type/size from steel/PCC pole alongwith all accessories setting aside and disposal all as specified and directed. |
| 12 | Fixing only street light junction box (retrieved from srl No 11 above) any type/size on steel/PCC pole alongwith all connected accessories after cleaning/repair all as specified and directed. |
| 13 | S&F of weatherproof junction box of size 328x239x129 mm outdoor type made out of thermo polycarbonate to accommodate 04 Nos aluminium bus bar of size 25x6 mm rating 200 Amps and MCB SP 6 Amps IP-65 with hinged door and triangular locks shock proof, rust proof, corrosion free, acid resistance/fire retardant and self-extinguishing UV resistance complete including fixing arrangement i.e clamps, nut, bolt and washers, fixed on steel/PCC pole complete all as specified and directed. |
| 14 | Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed. Note: Excavation and earth work, sand, bricks etc shall be measured and paid separately under respective item of BOQ. |
| 15 | All as per item No 14 but for LT cable 35 to 70 Sqmm 3.5 core. |
| 16 | All as per item No 14 but for LT cable 95 to 240 Sqmm 3.5 core. |
| 17 | All as per item No 14 but for LT cable 300 to 400 Sqmm 3.5 core. |
| 18 | Re-laying of LT cable up to 25 Sqmm 2/3.5/4 core (retrieved from above) after repairs in same or other indicated location and testing on completion complete all as specified and directed.Note : Quoted rate shall include making good all distributed wall surfaces/ flooring/ tilling/ road to match with existing specification. |
| 19 | All as per item No 18 but of LT cable 35 to 70 Sqmm 3.5 core . |
| 20 | All as per item No 18 but of LT cable 95 to 240 Sqmm 3.5 core . |
| 21 | All as per item No 18 but of LT cable 300 to 400 Sqmm 3.5 core . |
| 22 | Supply, laying and testing of XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade, cross sectional area 10 Sqmm 4 core in trenches or fixing to wall/ pole or passing through pipe complete all as specified and directed.Note : Quoted rate shall include making good all distributed wall surfaces/ flooring/ tilling/ road to match with existing specification. |
| 23 | All as per item No 22but cable of size 16 Sqmm 4 core. |
| 24 | All as per item No 22 but cable of size 25 Sqmm 3.5 core. |
| 25 | All as per item No 22 but cable of size 35 Sqmm 3.5 core. |
| 26 | All as per item No 22 but cable of size 50 Sqmm 3.5 core. |
| 27 | All as per item No 22 but cable of size 95 Sqmm 3.5 core. |
| 28 | All as per item No 22 but cable of size 150 Sqmm 3.5 core. |
| 29 | All as per item No 22 but cable of size 185 Sqmm 3.5 core. |
| 30 | All as per item No 22 but cable of size 16 Sqmm 2 core. |
| 31 | All as per item No 22 but cable of size 10 Sqmm 2 core. |
| 32 | M&L for Cable jointing kit suitable for XLPE/PVC armoured aluminium conductor cable of size 16 to 35 Sqmm 3.5/4 core, 1100 volt grade cable, outdoor termination end joint, heat shrinkable type complete with jointing material and accessories complete all as specified and directed. |
| 33 | All as per item No 32 but for cable of size 50to 95 Sqmm 2/3.5 core. |
| 34 | All as per item No 32 but for cable of size 120 to 185 Sqmm 3.5 core. |
| 35 | M&L for Cable jointing kit suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm2/3.5/4 core, 1100 volt grade cable, straight through termination heat shrinkable type complete with jointing material and accessories complete all as specified and directed. |
| 36 | All as per item No 35 but for cable of size 25 to 50 Sqmm 3.5 core. |
| 37 | All as per item No 35 but for cable of size 70 to 150 Sqmm 3.5 core. |
| 38 | All as per item No 35 but for cable of size 185 to 240 Sqmm 3.5 core. |
| 39 | S&F in replacement of fully retroreflective sign boards of cut to sizes/ shape having written back ground made out of 18 SWG MS Sheet duly painted with two coats of synthetic enamel paint over a coat of primer including marking/writing letters, road sign any type with radium tape in different colours, duly mounted on stainless steel rod 40 mm dia, fancy type fixed with nut, bolt, washer and welding (height of rod as per site requirement) etc including all necessary excavation and earth work,PCC for foundation (all as per sample) complete all as specified and directed. |
| 40 | M&L for marking/writing feeder names/ SM No / MES No for HT/LT Electrical Equipments like VCB, Tfrs, RMU, Panels etc with synthetic enamel paint or with water proof stickers (all as per sample) complete all as specified and directed. |
| 41 | M&L for disconnecting, dismantling and taking out traffic signal light of any type/size, red colour from site and refixing in same or other location after repair and testing complete all as specified and directed. |
| 42 | S&F in replacement of traffic signal light of size 300mm dia, red colour blinking, polycarbonate body, UV stabilized, moulded, water clear polycarbonate, water proof, full circle LEDs, 12 watt, 1.5mm glass epoxy sheet LED PCB, input volts 230 volts AC, visibility 300-500 mtr, PF 0.9(complete as per sample), all as specified and directed. |
| 43 | Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth for laying of cables, foundation of poles or stays and for rerouting of cables complete all as specified and directed. |
| 44 | All as per item No 43 but depth exc 1.5 mtr but not exc 3.00 mtr. |
| 45 | Returning, filling inany type of soil including spreading , levelling, watering and well ramming in layers, each layer not exc 25 cm thick complete all as specified and directed. |
| 46 | Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 47 | M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, stretchingand testing the cable complete all as specified and directed.(Note: Only punned thickness i.e 18cm shall be measured and paid). |
| 48 | M&L for Sub class ‘B’ bricks (fly ash) old size laid dry flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed. |
| 49 | Relaying of old bricks, flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed. |
| 50 | M&L for plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregrate for foundation, filling as mass concrete including necessary form work complete all as specified and directed. |
| 51 | M&L for plain cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregrate for foundation of stay complete all as specified and directed. |
| 52 | M&L for boring of holes under road, pavement, hard standing by mannually or trenchless technology using ultra sound technique for laying pipe/cables etc complete all as specified and directed. |
| 53 | S&F in replacement of heavy duty cable 1100 volts 6 Sqmm 2 core flat PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed for service connection complete all as specified and directed. |
| 54 | All as per item 53 but size 10 Sqmm 2 core. |
| 55 | M&L for GI tubing light grade 50mm bore with fittings laid for protection of cable under road crossing/ fixed to walls or pole cut to piece complete all as specified and as directed. Note: Clamps for fixing pipe, nuts, bolts washers shall be measured separately. |
| 56 | All as per srl item No 55 but GI tubing of size 40mm bore. |
| 57 | All as per srl item No 55 but GI tubing of size 80mm bore. |
| 58 | All as per item No-55 but of size 15 mm bore, cut to piece and fixed with PCC pole with and including suitable size clamps, nut, bolt and washers for cable protection (all as per sample) complete all as specified and directed. |
| 59 | Supply & fix in replacement cable PVC insulated flexible aluminium conductor cable of size 1.5 Sqmm 3 core cut to pieces all as required for connection with proper thimbles, drawn in existing GI /PVC pipe fixed to wall or PCC pole or drawn in steel pole including making hole in steel pole if required complete all as specified and directed. |
| 60 | S&F in repair MCB single pole 240 volts 5 to 32 amps, 10 KA, using thimbles of required size complete all as specified and directed. |
| 61 | Supply and fixing in replacement of LED street light 45 Watt, 230 volts with surge protection not less than 4 KV and 10 KV separate in the lighting housing, IP 65, Energy saving & environmental friendly, long life, Versatile, pressure die-cast aluminium roadway luminaire with high power LEDs as light source and electronic driver fixed on pole/wall along with service bracket as per sample, clamps, nuts, bolts, and washers as directed including making electric connection with PVC insulated 1.5 Sqmm multistranded twin core aluminium conductor cable complete all as specified and directed. |
| 62 | All as per item No 61 but LED street light 60 Watt. |
| 63 | All as per item No 61 but LED street light 90 Watt. |
| 64 | All as per item No 61 but LED flood light 90 Watt complete including fixing arrangements i.e suitable clamps, nut, bolt and washers. |
| 65 | All as per item No 61 but LED flood light 120 Watt complete including fixing arrangements i.e suitable clamps, nut, bolt and washers. |
| 66 | All as per item No 61 but LED flood light 150 Watt complete including fixing arrangements i.e suitable clamps, nut, bolt and washers. |
| 67 | S & F in replacement of LED post top lantern warm white made in die cast aluminium housing with decorative clear opal acrylic diffuser and IP-65 protection fixing with proper arrangements and making electrical connection complete all as specified and directed. |
| 68 | Dismantling, cross arms, clamps, supports made of channels or angle section etc including nuts and bolts and setting aside all, as required at site or directed. |
| 69 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed including painted with two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. |
| 70 | S&Fof automatic timer switch for ON/OFF street lights based on lux level of natural light with current rating of 40 Amps 2 pole 230 Volts AC, 50 Hz max and sensor based, timer should also having over voltage and low voltage trip with auto reset facility, complete with one MCB 40 Amps, single pole10KA, contactor of rating 25 amps and 10 sqmm wiring suitable for 5 KW to 8 KW load fixed in suitable size of SMC/Polycarbonate box IP-65 etc complete with all electric connection all as specified and directed. |
| 71 | Disconnecting electrically, dismantling and taking down all connections of street light timer box and making all connections after cleaning/repair complete all as directed. Note:- 1. Quoted rates shall deemed to included of Minor parts i.e nut, bolt, washers and thimbles etc nothing extra shall be admissible on this account.2. Other unserviceable items shall be measured and paid separately under respective items of BOQ. |
| 72 | Supply only power contactor 40 Amp, 3 Pole with AC-1, 3 NC with auto/manual switch all as specified and directed. |
| 73 | Supply only power contactor 63 Amp, 3 Pole with AC-1, 4 NC with auto/manual switch all as specified and directed. |
| 74 | Supply street light Astro time switch 16A multi functional digital 2 modules, 2 channels for automatic switching on & offstreet lights at a preset time of make Legrand cat part No 412657 or equivalent in Make of Siemens/Schneider complete all as specified and directed. |
| 75 | M&L for preparation of old iron/steel surfaces of any description (duly scratching old paint) and painting to steel tubular pole up to 11 mtr height including cross arms, (without removing accessories)and painting the pole (above coping) with 5 Nos circular strips each of 30 cm (of colour combination as directed) with synthetic enamel paint (duly marked pole number in a 12 cm dia yellow circle duly number writing with black synthetic enamel paint), remaining pole shall be painted with two coats of aluminium paint, cross arms shall be painted with one coat of aluminium paint, PCC coping of pole shall be painted with one coat of cement base paint complete all as specified and directed. |
| 76 | M&L for painting of PCC pole 9/11 mtr long including cross arms without removing accessories after preparation of surfaces, the pole shall be painted (above coping) with 5 Nos strips each of 30 cm (of colour combination as directed) with synthetic enamel paint duly marked pole number in a 12 cm dia yellow circle with number writing with black synthetic paint. |
| 77 | Cleaning grass/mud all, in and around the earth pits after taking out pit cover, pouring of salt solution (appx 15 ltr) to existing pit with salt and water ratio 1:5, putting existing pit cover on pit, checking/making connection to the DBs with new/existing GI wire complete all as specified and directed. Note : GI wire shall be measured and paid seperately under respective item of BOQ. |
| 78 | M&L for construction of earth pit (excluding pit cover) as required at site and as per specification of Electrical plate No-03 of SSR part-1 complete all as specified and directed. |
| 79 | M&L for precast cover of RCC 1:2:4 type B1 using 20mm graded stone aggregate including necessary reinforcement steel bars, formwork etc for earth pit cover of size 0.45x0.45x0.075 mtr along with lifting handle (complete as per sample) and placing on earth pit complete all as specified and directed. |
| 80 | M&L for earth continuity conductor or main earthing lead 4.00 mm dia GI wire fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required in repair complete all as specified & directed. |
| 81 | Disconnecting, dismentling and taking down carefully GI strip of any size up to 32x6mm and seggregating U/S or serviceable parts setting aside for reuse and disposal complete all as specified & directed. |
| 82 | Fixing only GI strip obtained under item No 81, buried in ground upto 50 cm depth or fixed to wall etc including jointing by welding for loop earthing as directed by Engineer-in-Charge. Note: Excavation and earth work shall deemed to be included in the quoted rates under this item. |
| 83 | Supply & fixGI strip 32x6mm, buried in ground upto 50 cm depth or fixed to wall with nut, bolt & saddles/ insulators etc for loop earthing including weldingfor joints all as required at site or directed by Engr In Charge. Note: Excavation and earth work shall deemed to be included in the quoted rates under this item. |
| 84 | Supply and fix in replacement of electronic driver suitable for LED street/ flood lights fittings upto 90 watt of any type/make (as per sample) complete all as specified and directed. |
| 85 | S&F in replacement of MCB SP 3 Amp for contactor coil protection complete all as specified and directed. |
| 86 | M&L for Earthing complete with galvanisedsteel earth plate electrode 600mmx600mm thickness not less than 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised iron strip 32x6mmEarthing lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to new earth test point all as specified and indicated compete with funnel, charcoal, dust, salt etc and GI protection pipe, medium grade 15mm bore and GI watering pipe 20mm bore light grade, precast RCC M-15 (nomial mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar, excavation and earth work in any type of soil and connected all as specified or indicated including testing on completion complete all as specified and directed. |
| 87 | All as per item No 86 here in above but using GI wire 4mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers. |
| 88 | M&L for painting of street light junction box any type/size with two coats of synthetic enamel paintand painting of cross arms without removing accessories after preparation of surfaces, with one coat of aluminium paint complete all as specified and directed. |